Concrete and Reinforcement Specifications

The document outlines construction notes and specifications for a proposed mixed-use development, detailing requirements for concrete, reinforcement, and masonry. It emphasizes the importance of proper splicing, anchorage, and securing of materials before concrete placement, as well as adherence to building codes. Additionally, it provides guidelines for concrete strength, dimensions, and the placement of reinforcing bars to ensure structural integrity.

Uploaded by

warrenavilleta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views6 pages

Concrete and Reinforcement Specifications

The document outlines construction notes and specifications for a proposed mixed-use development, detailing requirements for concrete, reinforcement, and masonry. It emphasizes the importance of proper splicing, anchorage, and securing of materials before concrete placement, as well as adherence to building codes. Additionally, it provides guidelines for concrete strength, dimensions, and the placement of reinforcing bars to ensure structural integrity.

Uploaded by

warrenavilleta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

SDA-2023-0368

PERSPECTIVE

Anchorage or Development Length


CONSTRUCTION NOTES AND SPECIFICATIONS
6. SPLICES SHALL BE SECURELY WIRED TOGETHER & SHALL LAP OR EXTEND IN
ACCORDANCE WITH TABLE 1 (TABLE OF LAP SPLICE & ANCHORAGE LENGTH)
& Splicing Schedules for Rebars CRITICAL SECTION CRITICAL SECTION

A. GENERAL UNLESS OTHERWISE SHOWN ON DRAWINGS, SPLICES SHALL BE STAGGERED REBAR REBAR

12 x db
1. CONSTRUCTION NOTES & TYPICAL DETAILS APPLY TO ALL DRAWINGS UNLESS WHENEVER POSSIBLE. MIN. LAP SPLICE
OTHERWISE SHOWN OR NOTED, MODIFY TYPICAL DETAILS AS DIRECTED TO MEET ANCHORAGE OR DEVELOPMENT
7. ALL ANCHOR BOLTS, DOWELS, & OTHER INSERTS, SHALL BE PROPERLY LENGTH OF COL
SPECIAL CONDITIONS. BAR LENGTH OF REBARS IN METERS
POSITIONED & SECURED IN PLACE PRIOR TO PLACING OF CONCRETE. LAP SPLICES (M) UNIT REINFORCEMENT
2. SHOP DRAWINGS WITH ERECTION & PLACING DIAGRAMS OF ALL STRUCTURAL
8. CONTRACTOR SHALL NOTE & PROVIDE ALL MISCELLANEOUS CURBS, SILLS, DIAMETER
WEIGHT

°
INDIVIDUAL BARS

90
STEEL, MISCELLANEOUS IRON, PRE-CAST CONCRETE ETC. SHALL BE SUBMITTED db - DIAMETER db - DIAMETER
FOR ENGINEER'S APPROVAL BEFORE FABRICATION.
STOOLS, EQUIPMENT, & MECHANICAL BASES THAT ARE REQUIRED BY THE
ARCHITECTURAL, ELECTRICAL, & MECHANICAL DRAWINGS.
in STRAIGHT W/ STANDARD HOOK TENSION BAR COMP. BAR
(kg/m)
OF REBAR OF REBAR

3. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE ALL WORK IS TO BEGIN, (mm)
CHECK WITH MECHANICAL & ELECTRICAL CONTRACTORS FOR CONDUITS, PIPE 9. ALL CONCRETE SHALL BE KEPT MOIST FOR A MINIMUM OF SEVEN (7) (NO HOOK) 90° 180° 133° TOP BAR BOT BAR TOP BAR BOT BAR W/ TIES W/ SPIRAL DEVELOPMENT
LENGTH
KEY PLAN
SLEEVES, ETC. TO BE EMBEDDED IN CONCRETE. CONSECUTIVE DAYS IMMEDIATELY AFTER POURING BY THE USE OF WET BURLAP, DEVELOPMENT

SHORINGS & BRACINGS OF THE STRUCTURE FOR ALL LOADS THAT MAYBE FOG SPRAYING, CURING COMPOUNDS OR OTHER APPROVED METHODS. 10 0.60 0.10 0.13 0.10 0.42 0.30 0.42 0.30 0.617 0.30 0.30 LENGTH

IMPOSED DURING CONSTRUCTION. 10. STRIPPING OF FORMS & SHORES:


FOUNDATION/COLUMNS ..................................24 HRS. 12 0.60 0.14 0.16 0.12 0.42 0.30 0.42 0.30 0.889 0.30 0.30 DEVELOPMENT LENGTH FOR STRAIGHT DEVELOPMENT LENGTH FOR REBARS WITH
REBARS ANCHORED TO CONCRETE 90° STANDARD HOOK ANCHORED TO CONCRETE
B. CONCRETE & REINFORCEMENT SUSPENDED SLAB EXCEPT WHEN
0.52 0.47
1. ALL MATERIALS & WORKMANSHIP SHALL CONFORM WITH THE LATEST BUILDING
ADDITIONAL LOADS ARE IMPOSED......................8 DAYS 16 0.60 0.22 0.18 0.14. 0.73 0.52 0.87 0.62 1.580 (NO HOOK PROVIDED)
WALLS ..............................................................18 HRS.
CODE OF AMERICAN CONCRETE INSTITUTE (ACI - 318)
BEAMS ..............................................................14 DAYS 20 0.60 0.30 0.20 0.20 0.91 0.65 1.10 0.78 2.469 0.65 0.58
2. ALL CONCRETE SHALL DEVELOP A MINIMUM COMPRESSIVE STRENGTH AT THE
END OF TWENTY EIGHT (28) DAYS WITH CORRESPONDING MAXIMUM SIZE C. MASONRY & CONCRETE BLOCKS
AGGREGATE & SLUMP AS FOLLOWS: 25 0.68 0.40 0.28 0.26 1.40 1.00 1.40 1.00 3.858 0.80 0.73
LOCATION 28 DAYS STRENGTH MAX. SIZE AGGREGATE MAX. SLUMP 1. ALL NON-LOAD BEARING TYPE CONCRETE BLOCKS SHALL HAVE A UNIT WEIGHT
CURBS & SLAB 3,000 PSI 1 IN. (25MM.) 4 IN. (100MM) NOT TO EXCEED 80 PCF. FOR LOAD BEARING TYPE CONCRETE BLOCKS, A 28 0.86 0.48 0.38 1.76 1.26 1.53 1.09 4.840 0.90 0.82
ON GRADE MINIMUM COMPRESSIVE STRENGTH OF 6.90 MPA. SHALL BE DEVELOPED. PODIUM
EXCEPT FOUND. 32 1.12 0.56 0.43 2.31 1.65 1.74 1.24 6.327 1.03 0.93 DEVELOPMENT DEVELOPMENT
2. PROVIDE 1- Ø 16 VERTICAL BARS AT CORNERS, INTERSECTIONS, END OF
LENGTH LENGTH
WALLS & EACH SIDE OF OPENINGS.
FOUNDATION & 36 1.38 0.61 0.48 2.95 2.10 2.00 1.40 8.000 1.20 1.05 CRITICAL SECTION CRITICAL SECTION
RETAINING WALL 6,000 PSI 3/4 IN. (19MM.) 4 IN. (100MM) 3. LINTEL BEAMS SHALL BEAR AT LEAST 8 INCHES (200 MM.) ON EACH SIDE OF
MASONRY WALL OPENING.
ALL OTHERS REBAR REBAR
INCLUDING BEAMS 4. WALL REINFORCEMENTS (UNLESS INDICATED) SHALL BE AS FOLLOWS: NOTES:

°
SUSPENDED SLABS 6,000 PSI 3/4 IN. (19MM.) 4 IN. (100MM)

133
WALL THICKNESS VERTICAL REINFORCEMENT HORIZONTAL REINFORCEMENT
1. ACI SECTION 12.4 STATES THAT:

180°
& COLUMNS 8 IN. (200 MM.) Ø 12 @ 400 MM. Ø 10 @ 600 MM.

12
3. ALL REINFORCING BARS SHALL CONFORM TO ASTM A615 GRADE 40 FOR DIA.12mm 6 IN. (150 MM.) Ø 10 @ 400 MM. Ø 10 @ 600 MM. DEVELOPMENT LENGTH OF INDIVIDUAL BARS WITHIN A BUNDLE IN TENSION OR COMPRESSION

x
db - DIAMETER db - DIAMETER

db
& SMALLER BARS & GRADE 60 FOR DIA. 16 & LARGER BARS. COLUMN OF REBAR OF REBAR
4 IN. (100 MM.) Ø 10 @ 400 MM. Ø 10 @ 600 MM.
HOOPS ARE ALL GRADE 60 BARS. SHALL BE THAT FOR THE INDIVIDUAL BAR. INCREASED 20 PERCENT FOR THREE-BAR
4. IN GENERAL, THE LATEST EDITION OF ACI-315, MANUAL OF STANDARD PRACTICE 5. REINFORCING BARS SHALL BE LAPPED A MINIMUM OF 30 BAR DIAMETERS WHERE
DETAILING REINFORCED CONCRETE STRUCTURES SHALL BE ADHERED TO UNLESS SPLICED. DOWELS FROM CONCRETE FOOTINGS OR SLABS SHALL EXTEND INTO
BUNDLE AND 33 PERCENT FOR FOUR-BAR BUNDLE. 12 x db

OTHERWISE SHOWN OR NOTED. THE BLOCK WALL A MINIMUM OF 30 BAR DIAMETERS, & DOWELS TO MATCH
5. MAINTAIN MINIMUM CONCRETE COVER FOR REINFORCING STEEL AS FOLLOWS: VERTICAL REINFORCEMENTS OF WALL. 2. FOR COLUMNS AT ANY LEVEL NO MORE ALTERNATE BARS SHOULD BE SPLICED NOT
DEVELOPMENT LENGTH FOR REBARS WITH DEVELOPMENT LENGTH FOR REBARS WITH
SUSPENDED SLABS ................................................. 3/4 IN. (19MM.) 6. ALL CELLS CONTAINING REINFORCING BARS OR INSERTS SHALL BE SOLIDLY MORE THAN 33% OF THE BARS SHALL BE SPLICED WITHIN THE REQUIRED LAP LENGTH 180° STANDARD HOOK ANCHORED TO CONCRETE 133° STANDARD HOOK ANCHORED TO CONCRETE
SLAB ON GRADE ......................................................1 1/2 IN. (38MM.)
FILLED WITH CONCRETE GROUT. (REFER TO SPECIFICATIONS)
MINIMUM DISTANCE BETWEEN TWO ADJACENT BAR SPLICES SHALL BE 600MM. OWNER
D. FOUNDATION
WALLS ABOVE GRADE ..............................................1 IN. (25MM.) 1. FOUNDATION IS DESIGNED FOR ASSUMED ALLOWABLE SOIL BEARING 3. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 300 MM DEPTH OF CONCRETE CAST
BEAM STIRRUPS & COLUMN TIES ............................1 1/2 IN. (38MM.) CAPACITY OF 6,500 PSF. BELOW THE REINFORCEMENT.
2. FOUNDATION SHALL REST ON NATURAL SOIL. UNLESS OTHERWISE NOTED BY
WHERE CONCRETE IS EXPOSED TO EARTH 4. AS MUCH AS POSSIBLE SPLICES SUBJECTED TO TENSILE STRESSES ARE DISCOURAGE.
THE ENGINEER, NO PART OF THE FOUNDATION SHALL REST ON FILL.
BUT POURED AGAINST FORMS .................................2 IN. (50MM.)
3. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AFTER FOOTING EXCAVATION THESE SHOULD BE AVOIDED OR PROVIDED WITH STANDARD HOOKS.
MEASUREMENTS OF DEVELOPMENT LENGTH
WHERE CONCRETE IS DEPOSITED HAVE BEEN COMPLETED & PRIOR TO CONCRETING TO CONFIRM THE DESIGN
DIRECTLY AGAINST EARTH .......................................3 IN. (75MM.) SOIL BEARING CAPACITY. 5. ASSUMED SPECIFIED COMPRESSIVE STRESS FOR CONCRETE f'c = 6,000 PSI FOR REINFORCING STEEL
(SEE SEPARATE TABLE FOR CORRECT DIMENSION)

ARCHITECT

INTERMEDIATE
BEAM
EARTH SIDE

16mmØ VERT. BARS on OPEN SIDE


spaced @ 100mm O.C.

16mmØ VERT. BARS on EARTH SIDE


spaced @ 100mm O.C. STRUCTURE
3500mm Max Ht.

OPEN SIDE
300mm thk Wall

12mmØ HOR. BARS on OPEN SIDE


spaced @ 200mm O.C.

12mmØ HOR. BARS on EARTH SIDE


spaced @ 200mm O.C.

CONTRACTOR

FOOTING TIE
BEAM

SLAB-TYPE RET WALL DETAIL


(RW1)
SHOP DRAWING
PROJECT TITLE :

A PROPOSED MIXED-USE DEVELOPMENT

DRAWING TITLE :

PODIUM CONSTRUCTION NOTES, SCHEDULES AND


DETAILS
A DRAWING NO. :

TP-RF-0055 NTS CCTEB-RLD-SDW-ST-RF-TP-0055


DRAWN BY DWIGHT SCALE NTS
CHECKED BY ANSON HAO DATE 27APR2023
SDA-2023-0368
PERSPECTIVE

KEY PLAN

C2 TB1 C2 TB1 C3 TB1 C4 TB1

RW1
C4
ON TOWER E FOUNDATION
PODIUM

TB1

TB1

TB1

TB1

TB1

TB1
OWNER
TB1
TB1 TB1 TB1 TB1

F1C1 F2C2 F2C3


F3C4 F3C4
F2AC2
A1
TP-FW-0006-B
TB1

TB1

TB1

TB1

TB1

TB1
ARCHITECT
RW1

F2C2
TB1
TB1 TB1 TB1 TB1
F2C2 F2C3
F1C1 F3C4 F3C4 STRUCTURE
TB1

TB1

TB1

TB1

TB1

TB1
150mm THICK SLAB-ON-GRADE WITH
10mmØ REBARS SPACED @ 600mm
O.C. BOTHWAYS. WITH 100mm THICK
WELL-COMPACTED GRAVEL BASE AND
SUB-GRADE @ 95% MAXIMUM DRY DENSITY
RW1

CONTRACTOR
TB1

TB1 TB1 TB1 TB1


F2C2 F2C2 F2C3
F1C1 F3C4 F3C4
A2
TP-FW-0008-B
TB1

TB1

TB1

TB1

TB1

TB1
SHOP DRAWING
PROJECT TITLE :
RW1

A PROPOSED MIXED-USE DEVELOPMENT

DRAWING TITLE :

TB1 PODIUM FOUNDATION LAYOUT PLAN


DRAWING NO. :
TB1 TB1 TB1 TB1
F2C2 CCTEB-RLD-SDW-ST-RF-TP-0056
F2C2 F2C3
F1C1 F3C4 F3C4 DRAWN BY DWIGHT SCALE 1:75
CHECKED BY ANSON HAO DATE 27APR2023
SDA-2023-0368
GL LEFT OF A/8-12 PERSPECTIVE

16mmØ VERT. BARS on OPEN SIDE/EARTH SIDE 16mmØ VERT. BARS on OPEN SIDE/EARTH SIDE 16mmØ VERT. BARS on OPEN SIDE/EARTH SIDE 16mmØ VERT. BARS on OPEN SIDE/EARTH SIDE
spaced @ 100mm O.C. spaced @ 100mm O.C. spaced @ 100mm O.C. spaced @ 100mm O.C.
12mmØ HOR. BARS on OPEN SIDE/EARTH SIDE 12mmØ HOR. BARS on OPEN SIDE/EARTH SIDE 12mmØ HOR. BARS on OPEN SIDE/EARTH SIDE 12mmØ HOR. BARS on OPEN SIDE/EARTH SIDE KEY PLAN
spaced @ 200mm O.C. spaced @ 200mm O.C. spaced @ 200mm O.C. spaced @ 200mm O.C.
C1 C1 C1 C1 TE C9
GROUND FLR ±102.45 1B27P 1B27 1B27 1B27

1CB3P

PODIUM

NGL ±99.20

TOP OF TB1 ±98.90

TB1 TB1 TB1 TB1


OWNER
TB5
TOP OF F5 ±97.85
TB1 TB1 TB1 TB1

TOP OF F1 ±97.20 TOP OF F1 ±97.20 TOP OF F1 ±97.20 TOP OF F1 ±97.20


TE F5
BOTTOM OF FOOTING ±96.70

F1 F1 F1 F1

A
TP-RF-0057 1:50
ARCHITECT

GL LEFT OF A/8-12
STRUCTURE

C1 C1 C1 C1 TE C9
GROUND FLR ±102.45 1B27P 1B27 1B27 1B27
1CB3P [Link]-VB.1: 81 - 16Ø x 4500 [Link]-VB.2: 81 - 16Ø x 4500 [Link]-VB.3: 81 - 16Ø x 4500 [Link]-VB.4: 79 - 16Ø x 4500
@ 100mm O.C. (2 sets) @ 100mm O.C. (2 sets) @ 100mm O.C. (2 sets) @ 100mm O.C. (2 sets)
[Link]-HB.1: 8pcs - 12Ø x 2400 [Link]-HB.3: 8pcs - 12Ø x 9000 [Link]-HB.5: 8pcs - 12Ø x 9000 [Link]-HB.7: 8pcs - 12Ø x 9000 [Link]-HB.9: 8pcs - 12Ø x 7500
@ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) CONTRACTOR

[Link]-HB.2: 7pcs - 12Ø x 7500 [Link]-HB.4: 7pcs - 12Ø x 9000 [Link]-HB.6: 7pcs - 12Ø x 9000 [Link]-HB.8: 7pcs - 12Ø x 9000 [Link]-HB.10: 7pcs - 12Ø x 2400
@ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets) @ 200mm O.C. (2 Sets)

NGL ±99.20

TOP OF TB1 ±98.90

TB1 TB1 TB1 TB1


TB5
TOP OF F5 ±97.85
TB1 TB1 TB1 TB1 SHOP DRAWING
TOP OF F1 ±97.20 TOP OF F1 ±97.20 TOP OF F1 ±97.20 TOP OF F1 ±97.20 PROJECT TITLE :
TE F5
BOTTOM OF FOOTING ±96.70

A PROPOSED MIXED-USE DEVELOPMENT


F1 F1 F1 F1
DRAWING TITLE :

A PODIUM RETAINING WALL (RW1) CUTTING LIST

TP-RF-0057 1:50 DRAWING NO. :

CCTEB-RLD-SDW-ST-RF-TP-0057
DRAWN BY DWIGHT SCALE 1:50
CHECKED BY ANSON HAO DATE 27APR2023