BFP Siargao DWG Structural

The document outlines structural engineering guidelines for the design, fabrication, and construction of a project, referencing national codes and standards. It specifies requirements for materials, including concrete and steel, and details on reinforcement, footing, and construction joints. Additionally, it includes notes on the placement and specifications of various structural components to ensure compliance with engineering standards.

Uploaded by

joooma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views4 pages

BFP Siargao DWG Structural

The document outlines structural engineering guidelines for the design, fabrication, and construction of a project, referencing national codes and standards. It specifies requirements for materials, including concrete and steel, and details on reinforcement, footing, and construction joints. Additionally, it includes notes on the placement and specifications of various structural components to ensure compliance with engineering standards.

Uploaded by

joooma
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

STRUCTURAL

GENERAL N O T E S: 3.15.
OF THE ENGINEER PRIOR TO FABRICATION & INSTALLATION.
DEVELOPMENT LEGTH ( Ld ) OF REINFORCING BARS SHALL BE AS FOLLOWS:
CONCRETE WALL NOTES
SIZE OF REBARS DEVELOPMENT LENGTH
10 mm 170 mm
1. STANDARDS AND REFERENCES 12 mm 220 mm
THE FOLLOWING SHALL GOVERN THE DESIGN, FABRICATION AND 18 mm 270 mm
CONSTRUCTION OF THE PROJECT. 20 mm 360 mm
1.1. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES ( NSCP ) VOL. 1, 6TH EDITION. 25 mm 600 mm
2015. 4. STRUCTURAL STEEL
4.1. ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM A36 AND SHALL HAVE A
2. FOUNDATION MINIMUM YIELD STRESS, Fy = 248 MPA (36,000 Psi)
2.1. NO FOOTING SHALL REST ON FILL. 4.2. ALL STRUCTURAL STEEL BE FABRICATED AND ERECTED IN ACCORDANCE WITH THE
2.2. BOTTOM OF FOOTING SHALL BE AT LEAST 1.00m. BELOW NATURAL GRADE LINE. AISC SPECIFICATIONS AND CODE OF STANDARD PRACTICE AS AMMENDED TO
2.3. SOIL BEARING CAPACITY SHALL BE INCREASED BY 33% WHEN IN COMBINATION DATE.
WITH SEISMIC OR WIND LOAD 4.3. ALL BOLTS SHALL CONFORM TO ASTM A-307 UNLESS OTHERWISE INDICATED.
2.4. ALL COLUMN FOOTINGS AND TIE BEAMS SHALL REST ON 100mm THK. WELL 4.4. SHOP AND FIELD WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1 AND
COMPACTED GRAVEL BASE COURSE. PERFORMED BY QUALIFIED
2.5. BACK FILL SHALL BE PLACED IN LAYER AND EACH LAYER SHALL BE 200mm THK. 4.5. UNLESS OTHERWISE INDICATED, WELDING ELECTRODES SHALL BE E60. 5.1 VERTICAL REINFORCEMENTS FOR SHEAR WALLS SHALL BE PROVIDED WITH TIES NOT
AND SHALL BE COMPACTED TO 95% MAXIMUM DRY DENSITY. 4.6. NO STEEL SHALL BE FABRICATED OR ERECTED UNTIL SHOP DRAWINGS HAVE BEEN LESS THAN 12mm DIA BARS AT EVERY OTHER BAR LOCATION AT THE SAME SPACING
AS THE HORIZONTAL REINFORCEMENTS.
2.6. WHERE LOOSE / SOFT MATERIAL ID ENCOUNTERED AT DEPTH OF EMBEDMENT APPROVED BY THE STRUCTURAL ENGINEER.
INDICATED, EXCAVATE TO FIRM LAYER AND REPLACE LOOSE / MATERIALS 4.7. WELDS / ( CONFORM WITH AMERICAN WELDING STANDARDS ) USING E 60xx
UNDERNEATH THE FOOTING AREA PLUS 21 DEPTH OF SOFT MATERIAL ON ALL SIDES ELECTRODES. Fy = 93.77 MPa.
WITH SELECT GRANULAR BACKFILL. COMPACT SELECT GRANULAR BACKFILL TO 4.8. ANCHOR BOLTS ( CONFORM WITH ASTM A - 307 ) ft. = 96.60 MPa. fv = 69 MPa.
95% OF MAXIMUM DRY DENSITY. 4.9. CONCRETE HOLLOW BLOCKS ( CHB ):
4.10. UNLESS OTHERWISE INDICATED, CHB USED IN THIS WORK SHALL HAVE A
3. MATERIALS MINIMUM ULTIMATE COMPRESSIVE STRENGTH f' m = 3.45 MPa ( 500 psi )
3.1. CONCRETE: CONCRETE COVER OVER REINFORCING BARS SHALL BE AS FOLLOWS 4.11. ALL CHB CELL SHALL BE FILLED SOLIDLY WITH GROUT.
FOOTINGS, FOOTING-TIE BEAMS ( CAST AGAINST EARTH ) 75mm
BEAMS AND COLUMNS ( TO STIRRUPS AND TIES ) 40mm 5. CONSTRUCTION JOINT
WALLS, SIDE OF FOOTING-TIE BEAMS ( CAST AGAINST FORMS ) 40mm 5.1. CONSTRUCTION JOINT NOT INDICATED ON THE PLANS SHALL BE MADE SO AS TO
SUSPENDED SLAB 20mm LEAST IMPAIR THE STRENGTH OF THE STRUCTURE AND SHALL BE SUBJECT TO THE
3.2. BEFORE CONCRETE IS POURED, CHECK WITH ALL TRADES TO ENSURE PROPER APPROVAL OF THE ENGINEER EXCEPT SLAB ON GRADE.
PLACEMENT OF ALL OPENINGS, SLEEVES, CURBS, CONDUITS, ETC. RELATING TO 5.2. UNLESS SHOWN OTHERWISE, SLAB ON GRADE SHALL HAVE CONTROL JOINTS
THE WORK SPACED AT 600mm MAXIMUM CENTER TO CENTER.
3.3. REINFORCING BARS 5.3. BEAMS CONSTRUCTION JOINTS SHALL BE LOCATED WITH IN THE MIDDLE THIRD OF
3.4. ALL REINFORCING BARS SHALL BE CLEAN OR RUST, GREASE OR OTHER MATERIALS THE SPAN, IT SHALL BE PROVIDED WITH 3 EXTRA STIRRUPS @ 75mm O.C. ON EACH
THAT WILL IMPAIR BOND. SIDE OF THE JOINT.
3.5. ALL REINFORCING BARS SHALL BE ACCURATELY AND SECURELY PLACED BEFORE
POURING CONCRETE OR APPLYING MORTAR OR GROUT.
3.6. LAPPED SPLICES SHALL BE STAGGERED WHERE POSSIBLE.
3.7. UNLESS OTHERWISE INDICATED. SPLICING OF REINFORCEMENT SHALL BE IN TYP FLOOR SLAB OPENING REINFORCEMENTS
ACCORDANCE WITH ACI-318M. EXCEPT THAT THE MINIMUM LAP SPLICE SHALL BE 40
BAR DIAMETER BUT NOT LESS THAN 600mm.
3.8. UNLESS SHOWN OTHERWISE ON PLANS, SPLICES SHALL BE AS FOLLOWS:
3.9. INTERMEDIATE BEAMS; TOP BARS SHALL BE SPLICED AT MID-SPAN, AND BOTTOM
BARS AT THE SUPPORT.
3.10. BEAMS FRAMING TO COLUMNS; TOP BARS SHALL BE SPLICED AT MID-SPAN
AND BOTTOM BARS SHALL NOT BE SPLICED W/IN A DISTANCE OF TWICE THE
MEMBER DEPTH FROM THE FACE OF THE COLUMN. THE SPLICED LENGTH SHALL
NOT BE LESS THAN 1.4 TIMES THE DEVELOPMENT LENGTH ( Ld ) IN 4.2.8 BELOW BUT
NOT LESS THAN 600mm.
3.11. COLUMNS; LAP SPLICES SHALL BE MADE WITHIN THE CENTER HALF OF
HEIGHT AND THE SPLICE SHALL NOT BE LESS THAN 30 BAR DIAMETER. WELDING
OR THE USE OF APPROVED MECHANICAL DEVICES MAY BE PERMITTED PROVIDED
NOT MORE THAN ALTERNATE BARS ARE WELDED OR SPLICED AT ANY LEVEL AND
THE MINIMUM VERTICAL DISTANCE BETWEEN TWO ADJACENT BAR SPLICES SHALL
BE 600mm.
3.12. CHB WALLS; VERTICAL BARS SHALL BE SPLICED AT THE TOP OF WALL
FOOTINGS OR FOOTING-TIE BEAMS AND AT THE BOTTOM OF REINFORCED
CONCRETE LINTEL BEAMS OR BEAMS.
3.13. UNLESS OTHERWISE INDICATED: ALL BEAMS TERMINATING AT A COLUMN
SHALL HAVE TOP AND BOTTOM BARS EXTENDING TO THE FAR FACE OF THE
COLUMN. TERMINATING IN A STANDARD 90 HOOK LENGTH OF ANCHORAGE SHALL
NOT BE LESS THAN 600mm. FOR SQUARE OR RECTANGULAR
3.14. SHOP DRAWING FOR REINFORCEMENT SHALL BE SUBMITTED FOR APPROVAL OPENINGS

S E A L CONTRACTOR: PREPARED BY: TIN #: PROJECT NAME: PROJECT OWNER: SHEET CONTENT:

PROPOSED (COMPLETION) REHABILITATION OF


PRC #:

DATE VALIDITY: -AS SHOWN


ENGR. CHRISTIAN RESTOR
ENGINEER
PTR #:
BUREAU OF FIRE PROTECTION - SIARGAO BUILDING BUREAU OF FIRE PROTECTION - SIARGAO

DATE ISSUED: PROJECT LOCATION: ADDRESS: SURIGAO CITY


STD HOOK WHERE REQD.
30 BAR DIA. 30 BAR DIA.

VERIFY DEPRESSION
2. D = USE MAXIMUM COLUMN DIMENSION,
IF EXTENSION CANNOT

VERIFY ARCHITECTURAL
U-FORM RADIAL BARS (FOR TWO LAYERS 1/6 CLEAR HEIGHT OR 18" (450mm)
BE OBTAINED. ONLY) SAME SIZE OF SLAB OR WALL WHICHEVER IS GREATER.
REBAR SPACED @ 300 OC. 3. NUMBER OF HOOP TIES SAME AS PER
COLUMN TIES SCHEDULE.

D=FOR BEAM
4. ALL CONCRETE REINFORCEMENT DETAIL
2-16Ø CIRCULAR BAR
SHOULD BE DONE IN ACCORDANCE WITH
ACI DETAILING MANUAL 1980 PUB SP-66
40
BA
R

D=FOR BEAM
D
IA

TRIMMING BARS SHALL HAVE AN AREA

LR
C

)
EQUAL TO HALF THE AREA OF THE

AX
75 BARS CUT AT THE OPENING AND BE 30 BAR DIA.
(M
PLACED IN THE SAME LAYERS TYPICALLY
SHOWN FOR THE SLAB OR WALL W/ A

DIAGONAL BARS SAME SIZE OF SLAB OR


WALL REBAR OR 16Ø WHICHEVER IS
LARGER AND ARRANGED TO MATCH LAYERS NOTE : IF OPENING IS MORE THAN 900 mmØ,
OF TRIMMING BARS. MINIMUM OF 2-16Ø. CONSULT STRUCTURAL ENGINEER.

TYPICAL CIRCULAR WALL OPENING REINFORCEMENTS

NOTES ON CONCRETE SLABS

D
A. ALL SLAB REINFORCEMENTS SHALL BE 20 MM CLEAR MINIMUM FROM BOTTOM AND FROM THE TOP OF SLAB

JOINT REINF.
B. UNLESS OTHERWISE DETAILED, REINFORCING BARS SHALL BE EXTENDED, OR CUT AS FOLLOWS:

DISC. END CONT. END CONT. END


TYP. DET. FOR SLEEVES
.25L .3L OR .3L .3L OR .3L .3L 2/3L THRU CONCRETE BEAM

D
GREATER GREATER

COLUMN TIES AS
MIDSPAN .125L .125L MIDSPAN .125L

300 L L 300

D
C. IF SLABS ARE REINFORCED BOTH WAYS, BARS ALONG THE SHORTER SPAN SHALL BE PLACED BELOW THOSE ALONG THE
SPAN AT THE CENTER AND OVER THE LONGER SPAN FOR REINFORCING BARS NEAR THE SUPPORTS. THE SPACING OF

JOINT REINF.
THE BARS AT THE COLUMN STRIPS SHALL BE APPROXIMATELY ONE AND ONE-HALF (1 1/2) THAT IN THE MIDDLE STRIPS
BUT IN NO CASE GREATER THAN TWO AND ONE-HALF (2 1/2) SLAB THICKNESS OR FORTY FIVE (45) CENTIMETERS.

D. TEMPERATURE BARS FOR SLABS SHALL BE GENERALLY PLACED NEAR THE FACE IN TENSION AND SHALL NOT BE LESS
THAN 0.002 BT. ( SEE SCHEDULE BELOW )

D
SCHEDULE OF MINIMUM SLAB REINFORCEMENT
THICKNESS MINIMUM TEMPERATURE BARS
100 mm 10Ø @ 375 mm EACH WAY
112 mm 10Ø @ 350 mm EACH WAY
125 mm 10Ø @ 300 mm EACH WAY
138 mm 10Ø @ 275 mm EACH WAY
150 mm 10Ø @ 250 mm EACH WAY
CHB WALL OPENING DETAILS 2. WINDOW OPENING DETAILS
200 W=1200 MAX 200 (MIN)
STANDARD HOOKS STANDARD HOOKS FOR
A
FOR MAIN REINFORCEMENTS STIRRUPS / TIE REINFORCEMENTS
E. UNLESS OTHERWISE NOTED IN THE PLANS ALL BEDDED SLABS SHALL BE REINFORCED WITH 10 MM Ø AT 250 MM. O.C.
EACH WAY AT CENTER OF SLAB AND CONSTRUCTION JOINTS FOR SAME SHALL NOT BE LESS THAN 3650 MM. APART. 200 W=1200 MAX 200
F. PROVIDE EXTRA REINFORCEMENTS FOR CORNER SLABS ( TWO ADJACENT DISCONTINUOUS EDGES ) AS SHOWN BELOW. MIN
DETAILING HOOK DETAILING

50 MAX
5 - 10 MM BARS @ 0.20 M DIMENSION DIMENSION
BEAM
O.C. BOTTOM BARS "L" IS
6db FOR 10Ø TO 16Ø
A
A
2-Ø 16 12db FOR 20Ø TO 25Ø
WINDOW C VERT. BARS
OPENING
BEAM

LINTEL BEAM WITH 2-Ø16

H
CONTINUOUS HORIZONTAL
DOOR REINFORCEMENT B
H

OPENING
20mm (MIN)
(TYPICAL)

2-Ø 16 135° HOOK 90° HOOK


VERT. BARS

600

20mm (MIN)
B
5 - 10 MM BARS @ 0.20 M
FLOOR LINE MINIMUM FINISHED
O.C. TOP BARS FLOOR LINE BAR SIZE
BEND DIAMETER-D

10Ø TO 16Ø 4db

S E A L CONTRACTOR: PREPARED BY: TIN #: PROJECT NAME: PROJECT OWNER: SHEET CONTENT:

PROPOSED (COMPLETION) REHABILITATION OF


PRC #:

DATE VALIDITY: -AS SHOWN


ENGR. CHRISTIAN RESTOR
ENGINEER
PTR #:
BUREAU OF FIRE PROTECTION - SIARGAO BUILDING BUREAU OF FIRE PROTECTION - SIARGAO

DATE ISSUED: PROJECT LOCATION: ADDRESS: SURIGAO CITY


A B A B
A B
3.35
10x80mm VINYL TILE PLANK
1.97 1.39 FLOORING (TYP)
4.02

2.36 1.66
2 2

2
2"x2" S4S WOOD JOIST (STAIRS)

0.92
2"x2" S4S WOOD JOIST (STAIRS)
1.23

B
S

C
S
2.26
1.03 2.25
2"x6" S4S WOODEN BEAM

2.71
1"X3" S4S WOOD HANDRAIL
2.69

0.65
0.20
0.93
O F F I C E 150x150mm WOODEN POST
L O F T

5.45
( ELEV. +2.100 m )
6.54

10x80mm VINYL TILE PLANK


FLOORING

ACRYLIC FLOOR ADHESIVE

3.85
(APO POWERBOND)

2.99
4.62

3.19
3
4 4'X8' MARINE PLYBOARD
3.59

FLOOR DECK - SINGLE LAYER

3.69
2"x4" S4S WOOD JOIST

(TYP)
2"x4" S4S WOOD JOIST SPACER

0.35
2"x6" S4S WOODEN BEAM

0.21
3 3
3
0.40
(TYP)
2"x4" S4S WOOD JOIST SPACER
2"x4" S4S WOOD JOIST

OFFICE LOFT FLOOR PLAN


SCALE 1:50MTS.
OFFICE LOFT FLOOR PLAN ASSEMBLY
SCALE 1:40MTS.

150x150mm WOODEN POST


150x150mm WOODEN POST

2"x2" S4S WOOD JOIST


VINYL TILE INTERLOCKS
2"x2" S4S WOOD JOIST ACRYLIC FLOOR ADHESIVE
1"x2" S4S WOOD HANDRAIL
ACRYLIC FLOOR ADHESIVE
(APO POWERBOND)
3
2"x2" S4S WOOD RAILINGS 4 4'X8' MARINE PLYBOARD
2"x2" S4S WOOD JOIST (STAIRS)
FLOOR DECK - SINGLE LAYER
10X80mm VINYL TILE PLANK FLOORING 0.40 0.40
(TYP) (TYP)
3
3/4" MARINE PLYBOARD 4 4'X8' MARINE PLYBOARD

2"x6" S4S WOODEN BEAM


1.50

2"x6" S4S DIAGONAL WOODEN


2"x6" S4S DIAGONAL
BEAM
WOODEN RAILING BEAM
0.30

THIN RUBBER MATTING

THIN RUBBER MATTING


0.20

2"x6" S4S WOODEN BEAM 2"x6" S4S WOODEN BEAM


FINISH FLOOR LINE FINISH FLOOR LINE

SECTION - B DETAIL SECTION - C DETAIL


SECTION - D DETAIL
SCALE 1:20MTS. SCALE 1:20MTS.

SCALE 1:10MTS.

S E A L CONTRACTOR: PREPARED BY: TIN #: PROJECT NAME: PROJECT OWNER: SHEET CONTENT:

PROPOSED (COMPLETION) REHABILITATION OF


PRC #:

DATE VALIDITY: -AS SHOWN


ENGR. CHRISTIAN RESTOR
ENGINEER
PTR #:
BUREAU OF FIRE PROTECTION - SIARGAO BUILDING BUREAU OF FIRE PROTECTION - SIARGAO

DATE ISSUED: PROJECT LOCATION: ADDRESS: SURIGAO CITY