Electrical Wiring Plan for Commercial Building

The document outlines the specifications and requirements for electronics and communication installation in a commercial building, including adherence to local regulations and supervision by a licensed engineer. It details the types of materials and wiring to be used, as well as the necessary mounting heights for devices. Additionally, it emphasizes the need for verification of equipment layout and any discrepancies with the owner or representatives.

Uploaded by

ferdz C
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views1 page

Electrical Wiring Plan for Commercial Building

The document outlines the specifications and requirements for electronics and communication installation in a commercial building, including adherence to local regulations and supervision by a licensed engineer. It details the types of materials and wiring to be used, as well as the necessary mounting heights for devices. Additionally, it emphasizes the need for verification of equipment layout and any discrepancies with the owner or representatives.

Uploaded by

ferdz C
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

N

A
2
W E

B
4
4'
H
TC
S UT
ILIT
Y HA

D
KEY PLAN

GENERAL NOTES:
1. ALL ELECTRONICS & COMMUNICATION INSTALLATION WORKS HEREIN
SHALL BE DONE IN ACCORDANCE WITH THESE PLANS AND
SPECIFICATIONS, THE APPLICABLE PROVISIONS, THE RULES AND
REGULATIONS OF THE LOCAL ENFORCING AUTHORITY, AND THE
REQUIREMENTS OF THE LOCAL TELEPHONE COMPANIES. SHALL BE UNDER
THE IMMEDIATE SUPERVISION OF A DULY LICENSED ELECTRONICS
ENGINEER.

2. THE TELEPHONE & POS SERVICE SHALL BE PROVIDED BY CASINO AND


SHALL BE TAPPED TO THE STUBOUT/PROVISION INSIDE THE MERCHANT.

3. THE ELECTRICAL WIRING INSTALLATION SHALL BE DONE IN


INTERMMEDIATE METAL CONDUIT (IMC), COMPLETE WITH FITTINGS.
FLEXIBLE CONDUIT SHALL BE USED WHEN REQUIRED. MINIMUM SIZE
SHALL BE 15mm NOMINAL INSIDE DIAMETER OF ELECTRICAL TRADE SIZE.

4. ALL WIRES SHALL BE OF CAT6 UTP CABLE UNLESS OTHERWISE


INDICATED. THE MINIMUM SIZE OF CABLE SHALL BE OF AWG#22, OR AS
SPECIFIED ELSEWHERE ON PLANS

5. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL


LOCATION OF TAPPING/STUB-OUT OF THE BUILDING CONNECTION AND
ALSO THE ACTUAL LOCATION OF TELEPHONE SYSTEM FOR
CONNECTION TO THE LOCAL TELEPHONE CABLE FACILITIES.

6. ALL PIPE SLEEVES SHALL BE PROVIDED WITH PROPER SUPPORT OR


ANCHORAGE NECESSARY FOR PERMANENT CONNECTION WITH
CONCRETE WALLING OR BEAM.

7. ANY DISCREPANCY IN LOCATION AND RATINGS OF EQUIPMENT, LENGTH


OF WIRE, SHALL BE VERIFIED WITH THE OWNER OR ANY OF HIS
REPRESENTATIVES.

8. ALL MATERIALS TO BE USED AND THE EQUIPMENT TO BE INSTALLED


SHALL BE BRAND NEW AND MUST BE OF THE APPROVED TYPE FOR THE
PARTICULAR LOCATION AND PURPOSE INTENDED. BRAND NAME SHALL BE
AS PRESCRIBED BY THE OWNER OR AS REQUIRED BY MALL ADMIN.

9. THE MOUNTING HEIGHTS OF WIRING DEVICES SHALL BE AS FOLLOWS:


A) POINT OF SALE OUTLETS............. 0.3M ABOVE FLOOR FINISH OR AS
REQUIRED.
B) TELEPHONE OUTLETS................. 0.3M ABOVE FLOOR FINISH OR AS
TYPICAL BUILDING-SINGLE REQUIRED. ALL MOUNTING HEIGHTS SHALL BE SUBJECT TO ENGINEER'S
230 L-L
APPROVAL PRIOR TO INSTALLATION.
VOLTS 3W+G WIRE 60 Hz.

3HP BOOSTER PUMP


PANEL 'DBM' 800AT MAIN C.B. 1500 AF 3 POLE

60AT, 3POLE, 230V


FEEDER WIRE : 3SETS OF 3-200.0mm² THHN Wire
10. THE CONTRACTOR SHOULD ALWAYS VERIFY THE ACTUAL
LAYOUT FOR EQUIPMENTS, DEVICES, WIREWAY, AND OTHER

3HP BOOSTER PUMP


1-30.0mm² THHN (GW)
PARTICULARS THAT MIGHT BE CHANGED FROM TIME TO TIME FOR THE

60AT, 3POLE, 230V


90mmØ RSC PIPE / 110mmØ uPVC Pipe DB1

2HP JOCKEY PUMP


REASON OF UNFORESEEN PROBLEMS.

60AT, 3POLE, 230V


CKT. LOAD DESCRIPTION BRANCH CIRCUIT
NO. PROTECTION AB BC CA 3PH VA V WIRE SIZE CONDUIT SIZE
DB2
1 DB1 - ADMIN 3P - 40AT,50AF 13.26 12.36 12.72 10,776 230 SEE DETAILS SEE DETAILS

LINE OF FOURTH FLOOR LEVEL


LINE OF SECOND FLOOR LEVEL
LINE OF GROUND FLOOR LEVEL

LINE OF THIRD FLOOR LEVEL


2 DB2- ADMIN 3P - 200AT,250AF 24.00 12,120 230 SEE DETAILS SEE DETAILS

3 TDPB-TENANT UNIT 1-19 3P - 200AT,250AF 271.40 86,602 230 SEE DETAILS SEE DETAILS

4 FIRE PUMP @ 15HP 3P - 200AT,250AF 15.00 11,190 230 SEE DETAILS SEE DETAILS MCCB1

3-30mm2 THHN +
1-8.0mm2 THHN (G) IN
32mmDIA. PVC PIPE
DTB TP "UNIT-1" TP "UNIT-5" TP "UNIT-10" TP "UNIT-15"
ADMIN KWHR METER M
BUSBAR GUTTER
19HP FIRE PUMP 200AT TP "UNIT-2" TP "UNIT-6" TP "UNIT-11" TP "UNIT-16"
SERVICE ENTRANCE 100AT, 3POLE, 230V 3POLE M M M M M M M M M
DBM MCCB 2 TP "UNIT-3" TP "UNIT-7" TP "UNIT-12" TP "UNIT-17"
M M M M M M M M M M
3 SETS OF 3-200mm2 THHN + 3-30mm2 THHN + TP "UNIT-4" TP "UNIT-8 TP "UNIT13" TP "UNIT-18
VOLTAGE DROP CALCULATION:
TOTAL CONNECTED LOADS 13.26 12.36 12.72 310.40 120,628 1-30mm2 THHN (G) IN 1-8.0mm2 THHN (G) IN
VD = 2 x 12 x 51.47 x 100 ACB TP "UNIT-9 TP "UNIT-14" TP "UNIT-19
41740 90mmDIA. RSC PIPE / 110mmDIA. PVC PIPE 32mmDIA. PVC PIPE BREAKER GUTTER
VD = 2.96 V
DEMAND FACTOR 70% 800AT
%VD = 2.96 x 100% 3POLE
230
VD = 1.29 % (with-in PEC limit of 3%) TOTAL DEMAND LOADS I = [(13.26x1.732) + (0.25 x 271.40) + 310.40@ 70% DF)] = 300 Amps.

SINGLE LINE DIAGRAM

AS SHOWN E2
FOUR STOREY W/ ROOF DECK COMMERCIAL BLDG MR. JOSUE MEQUIAS [Link] AND MRS. REINA [Link]

15 15