SILENT
KNIGHT COMMERCIAL
~
(!)
FIREEQUIPMENT
Model 5128 and Model 5129
4 Channel Slave Fire Communicator

FEATURES
. UL 864 listed for NFPA 71 and 72C
. UL listed as slave communicator for connection to
UL listed 24 VDC local fire alarm control panels
'.- -:-:,:; ,..",..-""",.-
~ . .
. Four fully supervised input channels ~;~oo::::" .;.::::. =.
::;:; . .
. Remote programming (up/downloading)
'1E<:: ~t-:' ~~,
. Dual phone line interface and line fault monitors T;"""-,,, ~~~:,~,:,

. Automatic 24 hour test ,1 "' ,.


..'~
..~
-
--
" " =-- ::::
-" .
MODEL

-.-
51"flR[Link]'MU

.------.-------------------------
.
NICATOR

.-
. Reports in most major communication formats
. Compact size allows mounting in most local con-
trols, also available in metal cabinet (Model 5129)
tact closure input. The inputs can be wired as either
,,--.. supervised or non-supervised.
DESCRIPTION
The Silent Knight Model 5128 is a four channel The input channel types are preset. Their descrip-
tions are programmable as follows:
"slave" digital communicator designed to monitor UL
listed local fire alarm systems. The Model 5128 is a Channel W Default Options
cost effective answer to most fire communicator 1 ALARM FIRE SPRINKLER
applications and is easy to install and service. 2 TROUBLE FIRE SPRINKLER
3 SUPERVISORY SPRINKLER FIRE
Telephone Interface 4 ALARM UNDEFINED
The Model 5128 monitors and reports via two sepa-
rate phone lines. Built-in line fault monitors and a Audible Alarm
ring detector are provided.
An on-boardnon-silencingaudiblealarmis
provided.
AC Monitoring
An electrically isolated AC monitoring input is provid-
Programming/Downloading
ed. The input monitors the main power input of the
local fire control panel. The Model 5128 can be pro- The unit is programmable with a 5230 fire annuncia-
grammed to report AC trouble immediately or report tor. There is a connector for temporary connection of
can be delayed from 6 to 12 hours. 5230 for programming, but not for permanent
installation.

Power Input Downloading will allow remote programming, interro-


The Model 5128 communicator has been designed gation of current status and the ability to change the
to be powered from a UL-listed 24 VDC fire alarm 24 hour test time. A ring detector for one-call down-
control panel. loading is provided.
......

Channel Inputs Test Functions


The Model 5128 communicator has four channel The Model5128communicatorincorporatesa
inputs. The installer can configure the inputs as watchdogcircuiton the microprocessor.A power-up
either a voltage input, active high or low, or a con-
self-test will check the system. A 24-hour auto Requirement:
dialer test can be programmed to a precise time so FCC Registration No: AC6USA-75160-AL-E
installers can send the test to the central station at Ringer Equivalence: 0.98
a time of their choosing. Type of Jack: RJ41X (2 required)
'\
Relay Output Mechanical Specifications:
A socket for a single form C relay output rated at 1A Model 5128
is provided. The relay (Model 5211) is purchased Dimensions: 8-3/4"H x 4"W x 1-1/4"D
separately. Enclosure: Vinyl/Acrylic that meets UL 94V0
Connections Color: Red
Phone line and optional relay output connections Weight: 2 pounds
are made via screw terminals. Color coded flying Model 5129
leads are provided for the connections on the Dimensions: 10-3/8"H x 10-1/8"W x 3"D
control end.
Enclosure: Sheet metal cabinet
Color: Red
SPECIFICATIONS Weight: 6 pounds
Electrical Specifications:
Input: 24 VDC from a UL Listed FACP Approvals:
Total DC Load: 84 mA maximum at 24 VDC, UL Listed-UL 864, NFPA 71, 72C
standby 154 mA maximum at 24 VDC, alarm New York City: MEA 429-92-E Vol. III
AC Monitor Input: AC trouble output from host panel California State Fire Marshal: 7300-0559:120
or separate 24 VAC transformer.
Accessories:
Indicator Lights (LEDs): Model 9230
Green power LED
24 VAG transformer required for AC monitoring
Red LEDs for phone line trouble
output if AC trouble output from host panel is not
Yellow LED for faulted input and system trouble used. UL listed.
Reporting Formats:
Communicators via SK 3/1, Sescoa 3/1, SK 4/2, SK
FSK (4/2), Radionics 8FSK and SIA formats.
'1

ffi
G

UL LISTED
LOCAL FIRE
CONTROL

~ @
SILENT
KNI GHT
7550 Meridian Circle, Maple Grove, MN 55369-4927
800-446-6444 or in Minnesota 612-493-6435
FAX: 612-493-6475
MADE IN AMERICA
FORM# 350780, Rev. 7/97
'"

World Wide Web: [Link] Copyright @ 1997 Silent Knight Security Systems