DN 60959
DN 60959
General
The FireWarden-100X (NFW-100X) is the latest intelligent address-
able Fire Alarm Control Panel (FACP) within the FireWarden Series
and is a direct replacement for the FireWarden-100 (NFW-100). The
NFW-100X comes with a pre-installed communicator and supports
up to 198 addressable devices (99 detectors and 99 modules). With
an extensive list of powerful features, the NFW-100X programs just
like FireWarden-100 products, yet fits into applications previously
served only by conventional panels.
The pre-installed IPOTS-COM is a dual technology (POTS and IP)
communicator. The POTS transmits system status (alarms, troubles,
AC loss, etc.) to a Central Station via the public switched telephone
network. The IP communicator’s internet monitoring capability sends
alarm signals over the Internet saving the monthly cost of two dedi-
cated business telephone lines. Although not required, the second-
ary telephone line may be retained providing backup communication
over the public switched telephone line. Optional cellular reporting is
available using the CELL-MOD or CELL-CAB-N.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can
be uploaded/downloaded via the panel’s USB port (and USB cable)
or via an ethernet connection using the IPOTS-COM communicator.
The USB port also allows for the download or upload of the entire
program, history file, walk-test data, current status and system volt-
ages by means of a USB flash drive.
• Maintenance alert warns when smoke detector dust accumula-
The power supply and all electronics are contained on a circuit tion is excessive
board supported on a new quick install chassis and housed in a • One-person audible or silent walk test with walk-test log and
metal cabinet. Available accessories include local and remote printout
upload/download software, remote annunciators, and reverse polar- • System alarm verification selection per detector point
ity/city box transmitter (4XTM). • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA
Features 72 compliant)
• Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
• Listed to UL Standard 864, 10th edition • Remote Acknowledge, Alarm Silence, Reset and Drill via
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- addressable modules or remote annunciator
phone Service) Central Station Communicator over AlarmNet • Upload/Download of program and data via USB with optional FS-
• Optional CELL-MOD or CELL-CAB-N GSM Central Station Com- Tools Programming Utility
municator over AlarmNet®
• Automated activation of the NFC-50/100 Emergency Command SLC COMMUNICATION LOOP
Center • Supports FlashScan® and CLIP protocols
• NFC-FFT Firefighter Telephone option • SLC operates up to 10,000 ft. (3,000 m) in FlashScan mode with
• Compatible with SWIFT® wireless devices twisted, unshielded wire
• Auto-programming (learn mode) reduces installation time.
• Single addressable SLC loop which meets NFPA Class B and
Reports two devices set to the same address
Class A requirements
• Four built-in, independently programmable Style Z (Class A) or
Style Y (Class B) NAC circuits • 198 addressable device capacity (99 addressable detectors and
• Selectable strobe synchronization for System Sensor, Wheelock, 99 modules)
and Gentex devices • Compatible with NOTIFIER FireWarden and ONYX Series
• Notification Appliance Circuit End of Line resistor matching addressable devices (refer to the FireWarden SLC Wiring Man-
• Four programmable function keys for ease of maintenance ual)
• Two programmable relays and one fixed trouble relay NOTIFICATION APPLIANCE CIRCUITS (NACS)
• Built-in Programmer
• Integral 80-character LCD display with backlighting • Four independently programmable output circuits. Circuits can be
• Real-time clock/calendar with automatic daylight savings control configured for the following outputs:
• History file with 1,000 event capacity – Style Y (Class B)
• Addressable sounder base compatibility – Style Z (Class A)
• Control module delay timer • Silence Inhibit and Autosilence timer options
• Automatic detector sensitivity testing (NFPA 72 compliant) • Continuous, March Time, Temporal, or California code for main
• Automatic device type-code verification circuit board NACs with two-stage capability
• Point trouble identification
• Selectable strobe synchronization per NAC
• Waterflow selection per module point
• Alarm verification selection per detector point • 2.5 A special application, 250mA regulated, total power for NACs
NOTE: Maximum or total 24VDC system power shared between all NAC
circuits and the ANN-BUS is 2.7 A
DN-60959:C • 7/16/2018 — Page 1 of 4
PROGRAMMING AND SOFTWARE vised output for local energy municipal box transmitter, alarm and
• Autoprogramming (learn mode) reduces installation time trouble. Includes a disable switch and disable trouble LED.
• Custom English labels (per point) may be manually entered or PWRMOD24 Power Expander Module: Optional power module.
selected from an internal library file Increases alarm power output to 6 amps.
• Two programmable Form-C relay outputs COMPATIBLE ANNUNCIATORS
• 99 software zones N-ANN-80: Remote LCD annunciator mimics the information dis-
• Continuous fire protection during online programming played on the FACP LCD display. Recommended wire type is un-
• Program Check automatically catches common errors not linked shielded. (Basic model is black; order -W for white; see DN-7114.)
to any zone or input point N-ANN-100R: Remote LCD annunciator mimics the information dis-
• OFFLINE PROGRAMMING: Create the entire program in your played on the FACP LCD display. Recommended wire type is un-
office using FS-Tools, a Windows®-based software package, and shielded. For use in FM applications only. (Basic model is black;
upload/download system programming locally. Offline program- order R for red.)
ming requires an ethernet connection. FS-Tools is available on N-ANN-I/O: LED Driver Module provides connections to a user sup-
www.notifier.com. plied graphic annunciator. (See DN-7105.)
N-ANN-LED: Annunciator Module provides three LEDs for each
User interface zone: Alarm, Trouble, and Supervisory. Ships with red enclosure.
(See DN-60242.)
LED INDICATORS
N-ANN-RLED: Provides alarm (red) indicators for up to 30 input
• Fire Alarm (red) • CO Alarm (red) zones or addressable points. (See DN-60242.)
• AC Power (green) • Supervisory (yellow) N-ANN-RLY: Relay Module provides 10 programmable Form-C
• Trouble (yellow) • Ground fault (yellow) relays. Can be mounted inside the cabinet. (See DN-7107.)
• Battery fault (yellow) • Disabled (yellow) N-ANN-S/PG: Serial/Parallel Printer Gateway module provides a
connection for a serial or parallel printer. (See DN-7103.)
• Maintenance (yellow) • Communication (yellow)
• Alarm Silenced (yellow) • F1-F4 Programmable Function ADDRESSABLE DEVICES
Keys (yellow) FSP-951: Addressable low-profile photoelectric smoke detector.
FlashScan only.
KEYPAD FSP-951-IV: Addressable low-profile photoelectric smoke detector.
• 16 key alpha-numeric pad • Acknowledge Ivory. FlashScan and CLIP mode.
• Alarm Silence • Drill (Manual Evacuate) NP-200: Addressable low-profile photoelectric smoke detector.
• Four (4) programmable function keys • Reset (lamp test) B300-6 base included, FlashScan only.
NP-200-IV: Addressable low-profile photoelectric smoke detector.
PRODUCT LINE INFORMATION Ivory, B300-6-IV base included. FlashScan and CLIP mode.
NFW-100X: Addressable Fire Alarm Control Panel with one SLC FSP-951T: Addressable low-profile photoelectric smoke detector
loop. Includes main circuit board with display chassis with trans- with thermal sensor. FlashScan only.
former, backbox with door, plastic bag containing screws, cables, FSP-951T-IV: Addressable low-profile photoelectric smoke detector
key, etc. with thermal sensor. Ivory. FlashScan and CLIP mode.
FS-Tools: Programming software for Windows®-based PC com- NP-200T: Addressable low-profile photoelectric smoke detector with
puter. Available for download at www.notifier.com. thermal sensor. B300-6 base included. FlashScan only.
CELL-CAB-N/CELL-MOD: Optional GSM communicators.
NP-200T-IV: Addressable low-profile photoelectric smoke detector
IPOTS-COM: Dual technology (POTS and IP) communicator. with thermal sensor. Ivory, B300-6-IV base included. FlashScan and
(replacement board) CLIP mode.
DP-ES-R: Optional dress panel for the NFW-100X (red).
FSP-951R: Remote test capable addressable photoelectric smoke
DP-ES-B: Optional dress panel for NFW-100X (black). detector for use with DNR(W) duct detector housing. FlashScan
TR-CE-B: Optional trim ring for semi-flush mounting. (Black. For only.
red, order TR-CE.) FSP-951R-IV: Remote test capable addressable photoelectric
BB-XP: Optional cabinet for one or two modules. smoke detector for use with DNR(W) duct detector housing. Ivory.
BB-25: Optional cabinet for up to six modules mounted on CHS-6 FlashScan and CLIP mode.
chassis. NP-200R: Remote test capable addressable photoelectric smoke
BB-26: Battery backbox, holds up to two 25 AH batteries and CHG- detector for use with DNR(W) duct detector housing. FlashScan
75. only.
NFS-LBB: Battery box, houses two 55 AH batteries NP-200R-IV: Remote test capable addressable photoelectric smoke
CHS-6: Chassis, mounts up to six multi-modules in a BB-25 cabinet. detector for use with DNR(W) duct detector housing. Ivory, FlashS-
CHG-75: Battery charger for lead-acid batteries with a rating of 25 to can and CLIP mode.
75 AH. FST-951: Low-profile 135°F fixed thermal sensor. FlashScan only.
CHG-120: Remote battery charging system for lead-acid batteries FST-951-IV: Low-profile 135°F fixed thermal sensor. Ivory. FlashS-
with a rating of 55 to 120 AH. Requires additional NFS-LBB for can and CLIP mode.
mounting. NH-200: Low-profile 135°F fixed thermal sensor. B300-6 base
NOTE: CHG-120 or CHG-75 required for batteries larger than 18AH. included, FlashScan only.
BAT Series: Batteries, see data sheet DN-6933. NH-200-IV: Low-profile 135°F fixed thermal sensor. Ivory. B300-6-IV
PRN Series: UL listed compatible event printer. Uses tractor-fed base included, FlashScan and CLIP mode.
paper. FST-951R: Low-profile, intelligent, rate-of-rise thermal sensor.
FlashScan only.
OPTIONAL MODULES
FST-951R-IV: Low-profile, intelligent, rate-of-rise thermal sensor.
4XTM Reverse Polarity Transmitter Module: Provides a super- Ivory. FlashScan and CLIP mode.