Project: Sino Bangla Consultant: DAVEEN
Location: Bangladesh Date: 7/19/21 10:43 AM
Tag: CHILLER ACHX-B-1
PERFORMANCE SUMMARY
Location:
Screw Compressor Air Cooled Package Chiller
Model # ACHX-B 120S - AU N Manufacturer DBM
Quantity 1 Rating version ACHXB3
Physical Specifications
Compressors (Qty) HSC 1616HHL6V6K(1) Shipping weight (lb) 7,329
Length (in) 152.00 Operating weight (lb) 7,535
Width (in) 89.00 Approx. refrigerant charge (lb) 287
Height (in) 89.00 Refrigerant R-134a
Conditions of service
Percent of full load 100% Compressor power (kW) 120.1
Capacity (Tons) 111.4 Total Fan Power (kW) 15.12
Unit power (kW) 135.2 Cooling Efficiency (EER, Btu /[Link]) 9.889
[Link] (EER, Btu /[Link]) 13.35
Evaporator
Model (Qty) C5R Leaving fluid temp. (°F) 44.60
Fluid Water Fouling factor (h·ft²·°F/Btu) 0.000100
Fluid flow rate (USgpm) 296.9 Pressure drop (psi/ft.H2O) 4.97/11.5
Entering fluid temp. (°F) 53.61 Fluid freezing point (°F) 32.00
Condenser
Design ambient (°F) 107.0 Altitude (ft) 0.000
Fan Motor Power (kW) (Qty) 2.520 (6)
Electrical characteristics
Unit power supply 400V/3ph/50.0Hz Unit rated load amps 231
Unit max. fuse size (A) 450 Unit min. circuit ampacity (A) 281
Total Comp. RLA (A) 199
Notes
- Refrigerant charge may vary. Unit nameplate will show final - Certified in accordance with the AHRI Air Cooled Water-
factory charge. Chilling Packages Using the Vapor Compression Cycle
Certification Program, which is based on AHRI Standard-
550/590(I-P) and AHRI Standard 551/591(SI). Certified units
may be found in the AHRI Directory at [Link].
[Link] Points
% Full load Tons Unit kW Comp. kW Fan kW EER Ambient(°F)
100% 111.4 135.2 120.1 15.12 9.889 107.0
75% 83.58 88.80 78.72 10.08 11.29 87.5
50% 55.72 41.89 34.33 7.560 15.96 68.0
25% 27.86 30.28 25.59 4.690 11.04 55.0
Sound Data
Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level (free field) at 32.80 ft 46 53 57 57 57 55 50 37 63
*Sound Pressure Level (free field) ± 2 dB(A) Tolerance
Standard Equipment
Cabinet Construction Unit Construction
▪ (Cabinet construction information not available) ▪ Unit shall be constructed of heavy gauge G90 galvanized steel
▪ All sheet metal parts are painted with oven baked epoxy /
polyester powder paint, sustaining 1000 hour salt spray test in
accordance with ASTM B-117
▪ Rigid Structural base to prevent unit deformation and damage
during hoisting
▪ Bolted construction for easy semi knockdown at site in case
hoisting problem
355100 19-Jul-21 Page 10 of 12 SPEC ver. 7.0, 18809
Project: Sino Bangla Consultant: DAVEEN
Location: Bangladesh Date: 7/19/21 10:43 AM
Tag: CHILLER ACHX-B-1
PERFORMANCE SUMMARY
Location:
▪ Control panel IP54
Compressor
▪ (Compressor information not available) ▪ Oil level Sight glass
▪ HSC horizontal screw ▪ One year warranty
▪ Cast iron housing ▪ Compressor liquid injection, and vapour injection (only available
▪ IP55 Terminal box in selected models)
▪ Slide valve unloading ▪ External Oil separator for R134a unit
▪ Suction shut off valve (Optional) ▪ Soft starter
▪ Discharge check valve ▪ Oil separator
▪ Semi-hermetic compressors ▪ Integral lubrication system using pressure differential
▪ Compressor oil sump heaters
Air Cooled Condenser Code Compliance
▪ (Condenser information not ▪ Hydrophilic Coated Fins ▪ (Compliance information ▪ Rated in accordance with
available) not available) AHRI 550/590 std.
▪ IEEE
Air Cooled condenser
▪ Inner ridged copper tubes ▪ 6 pole fan motor, IP55, class F insulation
▪ 450 psig test pressure for condenser coils ▪ Fan cycling low ambient control down to 45°F, and reduce unit
▪ Low noise direct driven propeller and axial fans power input at low ambient
▪ Galvanized steel tubesheet ▪ Hydrophilic Coated Fins
▪ Close blade tip clearance with the fan venturis to assure smooth,
quiet operation
Evaporator
▪ (Evaporator information not available) ▪ 150 psig on water side design pressure
▪ Flooded design for higher capacity and easy maintenance ▪ Drain and vent plugs
▪ Cleanable integral fin copper tubes for easy serviceability ▪ Relief valve
▪ Removable water heads ▪ 1" thick PE foam closed cell evaporator insulation,thermal
▪ Optional Flanged water connection for quick installation and/or conductivity 0.040W/m.K at 40°C (0.28Btu in/hr.ft2°F at 104°F.)
service ▪ 1" thick PE foam closed cell suction line insulation/thermal
▪ Full pump-down capacity in condenser, therefore, pump out unit conductivity 0.040W/m.K at 40°C (0.28Btu in/hr.ft2°F at 104°F)
not required ▪ Carbon steel header, shell and tube sheet
▪ 200 psig on refrigerant side design pressure
Refrigeration Specialties Controls
▪ (Refrigeration information not available) ▪ (Controls information not available)
Refrigerant Specialties
▪ Discharge superheat level control ▪ Replaceable core filter drier
▪ Economizer usage to boost capacity (Only available for selected ▪ Charging and gauge connections
models) ▪ Pressure relief valves
▪ Sight glass with moisture indicator ▪ Refrigerant charge
▪ Electronic Expansion valve ▪ Oil Charge
Standard Electrical Components
▪ Compressor cirucit breaker and contactors ▪ Fan control contactors
▪ Compressor overloads ▪ Control circuit transformer
▪ Low voltage/phase failure/phase reversal relay ▪ Current transformer
▪ On-off in the unit control circuit and each compressor control ▪ Optional Ambient temperature sensor
circuit ▪ (Electrical information not available)
Warranty and Testing Analog readouts
▪ Standard one year warranty on unit and on compressors ▪ Evaporator and condenser refrigerant pressure
▪ Factory run tested ▪ Compressor amps (each compressor)
▪ Water sensor: Evaporator leaving - Standard sensor to provide
temperature readout for water leaving the evaporator.
Controller
▪ Vision 2020i Advanced microprocessor based DDC controller ▪ Fluid temperature reset value
with DBG3 touch screen display panel with menu driven ▪ Water flow switch status
software digital readout, push button keyboard ▪ External stop/start command status
▪ Selection on English (Imperial) or metric display units ▪ Condenser fan cycling
▪ Remote monitoring via RS-485 port ▪ Low ambient lockout
▪ Leaving chilled fluid temperature ▪ Identification of up to 99 most recent alarms with critical data
▪ Evaporator and condenser pressure stamping
▪ Single phase amp draw, each compressor ▪ OPTIONAL (BMS Communication option)
▪ No. of compressor starts ▪ Optional Ambient temperature sensor
▪ Elapsed run time, each compressor ▪ Optional Return water temperature sensor
▪ Oil level status ▪ Optional Remote and stop signal
Digital readouts Capacity control Setpoints
355100 19-Jul-21 Page 11 of 12 SPEC ver. 7.0, 18809
Project: Sino Bangla Consultant: DAVEEN
Location: Bangladesh Date: 7/19/21 10:43 AM
Tag: CHILLER ACHX-B-1
PERFORMANCE SUMMARY
Location:
▪ Compressor contactor ▪ Elapsed compressor run ▪ Leaving water temperature ▪ Amp limit
status time ▪ Freeze up temperature ▪ Ramp up
▪ Flow switch status ▪ External enable/disable ▪ High and low pressure
▪ Oil level status status
▪ Number of compressor ▪ Liquid injection solenoid
starts state
Unit Protection
▪ High and low pressures
▪ High discharge temperature
▪ Freeze protection
▪ Low pressure differential
▪ Low oil level
▪ Compressor run error and over current
▪ Power loss
▪ Chilled water flow loss
▪ High/Low System voltage
▪ Sensor error
▪ Compressor anti-recycle
Optional Equipment/Service Included
Factory Mounted Options Included Accessories (Shipped Loose)
▪ Poly fin condenser (PCF) - Hydrophilic pre-coated aluminum ▪ Spring isolators (SPG) - designed for 1" deflection, these
condenser fins. housed spring assemblies have a neoprene friction pad on the
bottom to help prevent the passage of noise and a spring locking
leveling bolt at the top. Neoprene inserts prevent contact
between the steel upper and lower housings. Suitable for more
critical applications than RIS isolators.
355100 19-Jul-21 Page 12 of 12 SPEC ver. 7.0, 18809
Dunham-Bush Industries Sdn. Bhd. (166302-K), Lot 5755-6, Kidamai Industrial Park, Bukit Angkat, 43000 Kajang, Selangor Darul Ehsan, Malaysia.
Tel:603-8924 9000 Fax:603-8739 5020 Email:info@[Link]