This document provides specifications for a water cooled screw compressor chiller. Key details include: - Model WCFX60TR from manufacturer DBM with 2 compressors, 1502 kW cooling capacity - Physical dimensions of 4,997mm x 2,032mm x 2,337mm and operating weight of 9,400 kg - Uses R134a refrigerant with an operating COP of 6.091 and NPLV IP COP of 8.631 - Includes standard equipment such as hermetic screw compressors, flooded heat exchangers, insulation, relief valves and refrigerant charge.

Uploaded by

thilina lakhitha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
289 views4 pages

13-2-2020revised Screw chiller-1502KW

This document provides specifications for a water cooled screw compressor chiller. Key details include: - Model WCFX60TR from manufacturer DBM with 2 compressors, 1502 kW cooling capacity - Physical dimensions of 4,997mm x 2,032mm x 2,337mm and operating weight of 9,400 kg - Uses R134a refrigerant with an operating COP of 6.091 and NPLV IP COP of 8.631 - Includes standard equipment such as hermetic screw compressors, flooded heat exchangers, insulation, relief valves and refrigerant charge.

Uploaded by

thilina lakhitha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Project: DHQ-BLOCK 08 Consultant:

Location: Date: 2020-02-13


Tag: WCFX-E
PERFORMANCE SUMMARY
Location:

Screw Compressor Water Cooled Package Chiller


Model # WCFX60TR Component code AUKBRT5R
Manufacturer DBM Rating version WCFXE216

Physical Specifications
Compressors (Qty) MSC1230(2) Shipping weight (kg) 8,423
Length (mm) 4,997.00 Operating weight (kg) 9,400
Width (mm) 2,032.00 Refrigerant R134a
Height (mm) 2,337.00 Approx. refrigerant charge (kg) 595

Cooling Conditions of service


Percent of full load 100.00% Unit power (kW) 246.6
Capacity (kW) 1502 Cooling efficiency (COP, W/W) 6.091
NPLV.IP (COP, W/W) 8.631

Evaporator Condenser
Model (Qty) KBR(1) Model (Qty) T5R(1)
Number of passes 2.0 Number of passes 2.0
Fluid Water Fluid Water
Fluid flow rate (l/s) 72.00 Fluid flow rate (l/s) 90.00
Pressure drop (kPa) 43.6 Pressure drop (kPa) 49.0
Entering fluid temp. (°C) 12.22 Entering fluid temp. (°C) 32.00
Leaving fluid temp. (°C) 7.25 Leaving fluid temp. (°C) 36.67
Fouling factor (m^2·k/kW) 0.01800 Fouling factor (m^2·k/kW) 0.04400
Fluid freezing point (°C) 0.00 Fluid freezing point (°C) 0.00

Electrical characteristics
Unit power supply 400V/3P/50.0Hz Comp. rated amps(A) 203/203/0
Unit max. fuse size(A) 630 Comp. 1st Step inrush amps(A) 468/468/0
Unit min. circuit ampacity(A) 456 Comp. locked rotor amps(A) 949/949/0

Notes
- Certified in accordance with the AHRI Water Cooled Water- - Meets ASHRAE 90.1-2016 Path A and Path B chiller minimum
Chilling and Heat Pump Water-Heating Packages Using the efficiency guidelines
Vapor Compression Cycle Certification Program,which is based - Unit dimension stated in Physical Specification is for 2 passes
on AHRI Standard-550/590 (I-P) and AHRI Standard 551/591 vessels without any add-on option.
(SI). Certified units may be found in the AHRI Directory at
www.ahridirectory.org.
- Refrigerant charge may vary. Unit nameplate will show final
factory charge

NPLV.IP Points
% Full load kWr Unit kWe COP Evap. Flow(l/s) Cond. EFT(°C) Cond. Flow(l/s)
100% 1502 246.6 6.091 72.00 32.00 90.00
75.0% 1126 143.2 7.863 72.00 25.15 90.00
50.0% 750.9 78.74 9.537 72.00 18.33 90.00
25.0% 375.5 46.17 8.133 72.00 18.33 90.00

33064 13-Feb-20 Page 1 of 4 SPEC ver. 17762


Project: DHQ-BLOCK 08 Consultant:

Location: Date: 2020-02-13


Tag: WCFX-E
PERFORMANCE SUMMARY
Location:

Part load points


% Full load kWr Unit kWe COP Evap. Flow(l/s) Cond. EFT(°C) Cond. Flow(l/s)
100% 1502 246.6 6.091 72.00 32.00 90.00
90.0% 1352 205.2 6.589 72.00 29.26 90.00
80.0% 1201 161.4 7.441 72.00 26.52 90.00
70.0% 1051 127.6 8.237 72.00 23.78 90.00
60.0% 901.1 96.55 9.334 72.00 21.04 90.00
50.0% 750.9 78.74 9.537 72.00 18.33 90.00
40.0% 600.7 64.25 9.349 72.00 18.33 90.00
30.0% 450.6 52.64 8.560 72.00 18.33 90.00
20.0% 300.4 40.86 7.352 72.00 18.33 90.00

Sound Data
Total
Frequency (Hz) 63 125 250 500 1000 2000 4000 8000 dB(A)
Sound Pressure Level dB(A) @ 3.3ft [1m] 72.0 63.0 67.0 71.0 80.0 77.0 76.0 61.0 84.0
*Sound Pressure1 Level +- 2 dB(A) Tolerance

Standard Equipment
Compressor
▪ Infinite slide valve unloading capacity control ▪ Compressor vapour injection available
▪ Integral high efficiency oil separator ▪ Compressor oil sump heater(s)
▪ Suction check valve and service valve ▪ Double delta Starter
▪ Integral lubrication system using pressure differential ▪ Pressure relief valve if required
▪ Discharge check valve (Multiple compressor unit) or service ▪ Solid state motor protector
valve (Single compressor units) ▪ Optical oil level sensor
▪ One (1) year warranty ▪ Suction Filter
▪ Fully hermetic design
Evaporator/Condenser
▪ Flooded Design for higher capacity and easy maintenance ▪ Victaulic groove water connections
▪ Full pump down capacity in condenser ▪ 1" thick PE foam closed cell suction line insulation/thermal
▪ Cleanable integral fin copper tubes for easy serviceability conductivity 0.040W/m.K at 40C (0.28Btu in/hr.ft2F at 104F)
▪ 1"thick PE foam closed cell evaporator insulation,thermal ▪ Pressure relief valve(s), 3/4"FPT
conductivity 0.040W/m.K at 40 C(0.28Btu in/hr.ft2F at 104 F .) ▪ Drain and vent plugs
▪ Removable water heads ▪ Carbon steel header, Shell and Tube sheet
Refrigerant Specialties
▪ High Pressure relief valves ▪ Discharge check valves on multiple compressor units
▪ Refrigerant charge ▪ Replaceable core filter drier
▪ Sight glass with moisture indicator ▪ Automatic oil balancing control
▪ Oil Charge ▪ Charging and gauge connections
Standard Electrical Components
▪ Compressor MCCB and contactors ▪ Current transformer
▪ Single point power connection ▪ On-off switch in the unit control circuit and each compressor
▪ Compressor solid state overloads control circuit
▪ Control circuit transformer ▪ Under voltage/Phase failure-Phase sequence relay
▪ Low voltage/phase failure/phase reversal relay
Indicator lights Warranty and Testing
▪ Compressor overloads, ▪ High motor temperature, ▪ Standard one year warranty on unit and on compressors
each compressor each compresor ▪ Factory run tested
▪ High pressure ,low ▪ Control power
pressure, and freeze
Unit Protection Analog Readouts
▪ High and low pressures ▪ Evaporator and condenser refrigerant pressure
▪ High discharge temperature ▪ Compressor amps(each compressor)
▪ Freeze protection ▪ Water sensor:Evaporator leaving -Standard sensor to provide
▪ Low pressure differential temperature readout for water leaving the evaporator
▪ Low oil level
▪ Compressor run error and over current

33064 13-Feb-20 Page 2 of 4 SPEC ver. 17762


Project: DHQ-BLOCK 08 Consultant:

Location: Date: 2020-02-13


Tag: WCFX-E
PERFORMANCE SUMMARY
Location:

▪ Chilled water flow loss


▪ Compressor anti-recycle
▪ Sensor error
Controllers
▪ Vision 2020i Advanced microprocessor based DDC controller ▪ No. of compressor starts
with DBG3 touch screen display panel with menu driven ▪ Elapsed run time, each compressor
software digital readout, push button keyboard ▪ Oil flow status
▪ Selection on English (Imperial) or metric display units ▪ Fluid temperature reset value
▪ Remote monitoring via RS-485 port ▪ Water flow switch status
▪ Leaving chilled fluid temperature ▪ External stop/start command status
▪ Evaporator and condenser pressure ▪ Identification of up to 99 most recent alarms with critical data
▪ Single phase amp draw, each compressor stamping
Digital Readouts Capacity control Setpoints
▪ Compressor contactor ▪ External enable/disable ▪ Leaving water temperature ▪ Amp limit
status status ▪ Freeze up temperature ▪ Ramp up
▪ Oil flow status ▪ Liquid injection solenoid ▪ High and low pressure
▪ Number of compressor state
starts ▪ Flow switch status
▪ Elapsed compressor
runtime
Additional Features as Factory Installed Options
▪ Soft-starter with bypass
▪ Various BMS communication protocol's interface card

33064 13-Feb-20 Page 3 of 4 SPEC ver. 17762


Project: DHQ-BLOCK 08 Consultant:

Location: Date: 2020-02-13


Tag: WCFX-E
PERFORMANCE SUMMARY
Location:

33064 13-Feb-20 Page 4 of 4 SPEC ver. 17762


Dunham-Bush Industries Sdn. Bhd. (166302-K), Lot 5755-6, Kidamai Industrial Park, Bukit Angkat, 43000 Kajang, Selangor Darul Ehsan, Malaysia.
Tel:603-8924 9000 Fax:603-8739 5020 Email:[email protected]