04 May 2018
Project : Proposed Holy Angel University High School Building
Client : Holy Angel University
Location : Angeles, Pampanga
Subject : Structural Design Criteria, Guidelines and Standards
STRUCTURAL DESIGN CRITERIA AND STANDARDS
1.1 Applicable Codes and Standards
A. Appropriate structural loading criteria, materials, analysis / design methods from
the following:
1. Uniform Building Code (UBC – 1997)
2. Building Code Requirements for Reinforced Concrete (ACI – 318 – 2000)
3. National Structural Code of the Philippines (NSCP – 2015)
4. American Institute of Steel Construction Manual (AISC – 2016)
5. Association of Structural Engineers of the Philippines (ASEP) Steel Handbook
2000 Edition
1.2 Design Criteria
A. Design Loads
1.0 Dead Loads
Materials Unit Weight
Reinforced Concrete 23.54 kN/cu.m. (150 pcf.)
Soil 17.00 kN/cu.m. (107 pcf.)
Steel 77.00 kN/cu.m. (485 pcf.)
Seasoned Dry Wood 7.00 kN/cu.m. (45 pcf.)
Water 9.81 kN/cu.m. (62.4 pcf)
Floor Topping (50mm max) 1.20 kPa. (25 psf.)
Floor Finish 0.60 kPa. (12.5 psf.)
Electrical, Mechanical & Sanitary Utilities 0.24 kPa. (5 psf.)
Ceiling (including ceiling joists) 0.38 kPa. (8 psf.)
Movable Partition 0.48 kPa. (10 psf.)
150 mm. CHB (mostly tool joint finish) 2.73 kPa. (57 psf.)
100 mm. CHB (mostly tool joint finish) 2.11 kPa. (44 psf.)
2.0 Live Loads
Occupancy/Use Floor Live Load
Classrooms 4.785 kPa. (100 psf.)
Lobbies 4.785 kPa. (100 psf.)
Library 7.178 kPa. (150 psf.)
PALAFOX ASSOCIATES | 5/F PCCI Corporate Center, 118 L.P. Leviste St., Salcedo Village, Makati City 1227, Philippines
T: +[Link] to 55 | F: +[Link] | architecture@[Link] | [Link]
Canteen 4.785 kPa. (100 psf.)
Offices 4.785 kPa. (100 psf.)
Faculty Area 4.785 kPa. (100 psf.)
Conference Rooms 4.785 kPa. (100 psf.)
Hallways 4.785 kPa. (100 psf.)
Storage Areas 4.785 kPa. (100 psf.)
Restrooms 3.828 kPa. (80 psf.)
Stairs 4.785 kPa. (100 psf.)
Laboratories 4.785 kPa. (100 psf.)
Server/ CCTV Rooms 4.785 kPa. (100 psf.)
Roof Deck 4.785 kPa. (100 psf.)
Mechanical & Electrical Rooms 7.178 kPa. (150 psf.)
Concrete Ledges 3.828 kPa. (80 psf.)
Minimum Roof Live Loads
Tributary Loaded Area For Any Structural Member
Roof Slope 0 to 20 sq.m. 21 to 60 sq.m. Over 60 sq.m.
1. Flat or rise less 1.0 Kpa. 0.75 Kpa. 0.60 Kpa.
than 1 vertical in 3 (20.88 psf.) (15.67 psf.) (12.53 psf.)
horizontal
2. Rise 1 vertical to 0.75 Kpa. 0.70 Kpa. 0.60 Kpa.
less than 3 vertical (15.67 psf.) (14.62 psf.) (12.53 psf.)
in 3 horizontal
3. Rise 1 vertical in 0.60 Kpa. 0.60 Kpa. 0.60 Kpa.
1 horizontal or greater (12.53 psf.) (12.53 psf.) (12.53 psf.)
3.0 Wind Loads
The design wind pressures for elements of the structure are determined by the
applicable velocity pressure, considering the correction coefficient for height, and
multiplied by the applicable pressure coefficient as given by NSCP. Considering the
basic wind speed of 250 kph and for exposure C, the design wind pressure shall be
determined in accordance with the following formula:
p = qGCp – qi(GCpi)
where:
p = Design wind pressure
q = Velocity pressure
= 0.613KzKztKdV^2
Kz = Velocity pressure exposure coefficient
Kzt = Topographic factor; 1.00
Kd = Wind directionality factor; 0.85
V = Design wind velocity (in m/s)
G = Gust effect factor; 0.85
PALAFOX ASSOCIATES | 5/F PCCI Corporate Center, 118 L.P. Leviste St., Salcedo Village, Makati City 1227, Philippines
T: +[Link] to 55 | F: +[Link] | architecture@[Link] | [Link]
Cp = External pressure coefficient
qi = Internal pressure
GCpi = Internal pressure coefficient
4.0 Earthquake Forces
4.1 Static Force Procedure
The design base shear shall be computed as:
V = Cv I W
RT
But shall not exceed:
V = 2.5 Ca I W
R
But shall not be less than:
V = 0.11 Ca I W and V = 0.8 Z Nv I W
R
Where:
V = Design base shear
Ca, Cv = Seismic coefficients
I = Importance factor for Standard Occupancy; 1.00
Z = Seismic zone factor; 0.40 (Zone 4)
Na, Nv = Near source factors
W = Total seismic dead load
R = Numerical coefficient representative for inherent over-
strength & global ductility capacity
T = Elastic fundamental period of the structure in the
` direction under consideration
Method A
T = Ct(Hn)3/4
with
Ct = 0.0731 (reinforced concrete)
Method B
T = 2π[(Σwidi2) / (g Σfidi)] 1/2
PALAFOX ASSOCIATES | 5/F PCCI Corporate Center, 118 L.P. Leviste St., Salcedo Village, Makati City 1227, Philippines
T: +[Link] to 55 | F: +[Link] | architecture@[Link] | [Link]
Where the value of T from method B shall not be over 30 percent greater
than the value of T obtained from method A in Seismic Zone 4 and 40
percent in Seismic Zone 2.
The total force shall be distributed over the height of the building in
conformance with the following:
Fx = [(V-Ft)wxhx] / Σ (wihi)
Where:
Ft = 0.07 TV < 0.25v
Note: Ft may be considered zero if T is less than or equal to 0.70 sec.
and
V = Ft + Σ Fi
hi, hn, hx = height of the structure in meters above the base level to level i,
n or x.
wi = Portion of W which is located at or assigned to level I
g = Acceleration due to gravity
Fi = Lateral force applied to level I
W = Total dead load
The design storey shear in any storey shall be distributed to the various elements
of the lateral force-resisting system in proportion to their rigidities assuming that
the lateral force acts at the center of mass and center of rigidity.
5.0 Basic Load Combinations
U = 1.4D
U = 1.2D + 1.6L + 0.5Lr
U = 1.2D + 1.6Lr + f1L
U = 1.2D + 1.0W + f1L + 0.5Lr
U = 1.2D + 1.0E + f1L
U = 0.9D +1.0W
U = 0.9D +1.0E
1. Material Strengths
1.0 Concrete – The minimum cylinder compressive strengths of concrete at
28 days period are as follows:
1.1 For columns, beams, suspended slabs, & other structural walls
(From Ground Level up to Roof Level) F’c = 35.00 MPa.
(5,000 psi.)
1.2 Footings & Tie Beams F’c = 35.00 MPa.
(5,000 psi.)
1.3 Stairs F’c = 35.00 MPa.
(5,000 psi.)
PALAFOX ASSOCIATES | 5/F PCCI Corporate Center, 118 L.P. Leviste St., Salcedo Village, Makati City 1227, Philippines
T: +[Link] to 55 | F: +[Link] | architecture@[Link] | [Link]
1.4 For the slab on fill, stair on fill, Ramp on fill F’c = 20.68 MPa.
(3,000 psi.)
2.0 Reinforcing Steel shall be deformed bars conforming to ASTM 615;
2.1 For bars 20mm diameter and higher Fy = 415 MPa.
(60 ksi.)
2.2 For bars 16mm diameter and smaller Fy = 276 MPa.
(40 ksi.)
2.3 For Low-relaxation, stress-relieved, Fpu= 1860 MPa.
High-strength, seven-wire strand (270 ksi.)
3.0 Structural Steel
3.1 All steel sections, bars and plates shall be Fy = 248 MPa.
A36 steel, (36 ksi.)
3.2 All bolts should be A325 Steel
Allowable Tension Ft = 275 MPa.
(40 ksi.)
Allowable Shear, with threads in Shear Plane Fv = 150 MPa.
(22 ksi.)
3.3 Welding electrodes shall be E70xxx Fy = 340 MPa.
(49 ksi.)
4.0 Foundation
The allowable soil bearing pressure is 8,360 psf (400 kPa) based on the
Geotechnical Report prepared by Geotesting, Inc.
Prepared By:
Arthur E. Lazaro
Civil-Structural Engineer
Reg. No. : 35382
PTR No. : 6623577
Date: 08 Jan. 2018
Place: Makati City
TIN: 130-680-388