COMPUTATION
COMPUTATION
FOR S2-5
Stone Concrete ------------------------------------------------------------------- 0.023 KPa
Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Electrical ---------------------------------------------------------------------------- 0.0125 KPa
Wood studs, plastered (two plastered) ------------------------------------ 0.57 KPa
TOTAL LOAD PRESSURE---------------------------------------------------------- 2.1355 KPa
FOR S2-6
Stone Concrete ------------------------------------------------------------------- 0.023 KPa
Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa FOR S2-13
Wood studs, plastered (two plastered) ------------------------------------ 0.57 KPa Stone Concrete ------------------------------------------------------------------ 0.023 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 2.1355 KPa Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa
FOR S2-7 TOTAL LOAD PRESSURE------------------------------------------------------- 1.0125 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa
Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa FOR S2-14
Electrical ------------------------------------------------------------------------ 0.0125 KPa Stone Concrete ------------------------------------------------------------------- 0.023 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 1.5655 KPa Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Electrical --------------------------------------------------------------------------- 0.0125 KPa
FOR S2-8 TOTAL LOAD PRESSURE-------------------------------------------------------- 1.5655 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa
Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa FOR S2-15
Electrical ------------------------------------------------------------------------ 0.0125 KPa Stone Concrete ------------------------------------------------------------------- 0.023 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 1.5655 KPa Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa
Electrical --------------------------------------------------------------------------- 0.0125 KPa
FOR S2-9 Plumbing --------------------------------------------------------------------------- 0.0375 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa TOTAL LOAD PRESSURE---------------------------------------------------------- 0.843 KPa
Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa FOR S2-16
TOTAL LOAD PRESSURE------------------------------------------------------ 1.5655 KPa Stone Concrete ------------------------------------------------------------------- 0.023 KPa
Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa
FOR S2-10 Electrical --------------------------------------------------------------------------- 0.0125 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa Plumbing --------------------------------------------------------------------------- 0.0375 KPa
Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa TOTAL LOAD PRESSURE--------------------------------------------------------- 0.843 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 1.0125 KPa FOR S2-17
Stone Concrete ------------------------------------------------------------------- 0.023 KPa
FOR S2-11 Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa Electrical ---------------------------------------------------------------------------- 0.0125 KPa
Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa Plumbing --------------------------------------------------------------------------- 0.0375 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa TOTAL LOAD PRESSURE--------------------------------------------------------- 0.843 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 1.0125 KPa
FOR S2-18
FOR S2-12 Stone Concrete ------------------------------------------------------------------- 0.023 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa Electrical ---------------------------------------------------------------------------- 0.0125 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa Plumbing --------------------------------------------------------------------------- 0.0375 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 1.0125 KPa TOTAL LOAD PRESSURE---------------------------------------------------------- 1.603 KPa
FOR S2-19 Electrical ------------------------------------------------------------------------ 0.0125 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa Railings ----------------------------------------------------------------------------- 0.30 KPa
Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa TOTAL LOAD PRESSURE ----------------------------------------------------- 1.8655 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 0.8055 KPa FOR S2-26
Stone Concrete ------------------------------------------------------------------ 0.023 KPa
FOR S2-20 Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa Electrical ------------------------------------------------------------------------ 0.0125 KPa
Ceramic or Quarry Tile (20mm)----------------------------------------------- 0.77 KPa Railings ---------------------------------------------------------------------------- 0.30 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa TOTAL LOAD PRESSURE ----------------------------------------------------- 1.8655 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 0.8055 KPa
FOR S2-27
FOR S2-21 Stone Concrete ------------------------------------------------------------------ 0.023 KPa
Stone Concrete ------------------------------------------------------------------ 0.023 KPa Cement Finish (25mm) on Stone Concrete fill ---------------------------- 1.53 KPa
Ceramic or Quarry Tile (20mm) ----------------------------------------------- 0.77 KPa Electrical -------------------------------------------------------------------------- 0.0125 KPa
Electrical ------------------------------------------------------------------------ 0.0125 KPa Railings ---------------------------------------------------------------------------- 0.30 KPa
TOTAL LOAD PRESSURE------------------------------------------------------ 0.8055 KPa TOTAL LOAD PRESSURE ----------------------------------------------------- 1.8655 KPa
FOR S2-3
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ---------------- 1.90 kPa
FOR S2-4
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ---------------- 1.90 kPa
FOR S2-5
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ---------------- 1.90 kPa
FOR S2-6
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ---------------- 1.90 kPa
FOR S2-7
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ----------------- 1.90 kPa
FOR S2-8
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ---------------- 1.90 kPa
FOR S2-9
Classroom ----------------------------------------------------------- ----------------- 1.90 kPa
TOTAL LOAD PRESSURE ------------------------------------------ ---------------- 1.90 kPa
FOR S2-10 FOR S2-20
Classroom -------------------------------------------------------------------------- 1.90 kPa Office Use ---------------------------------------------------------------------------- 2.40 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 1.90 kPa TOTAL LOAD PRESSURE ----------------------------------------------------------- 2.40 kPa
FOR S2-35
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 3.80 kPa
FOR S2-36
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 3.80 kPa
FOR S2-37
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 3.80 kPa
FOR S2-38
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 3.80 kPa
FOR S2-39
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 3.80 kPa
FOR S2-40
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE -------------------------------------------------------- 3.80 kPa
B. FOR THIRD FLOOR TOTAL LOAD PRESSURE ----------------------------------------------------------- 1.90 kPa
FOR S3-41
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
TOTAL LOAD PRESSURE -------------------------------------------------------- 3.80 kPa
FOR S2-42
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
Stairs --------------------------------------------------------------------------------- 4.79 kPa
TOTAL LOAD PRESSURE --------------------------------------------------------- 8.59 kPa
FOR S2-43
Corridors above Ground Floor ------------------------------------------------ 3.80 kPa
Stairs --------------------------------------------------------------------------------- 4.79 kPa KN
TOTAL LOAD PRESSURE --------------------------------------------------------- 8.59 kPa W LANDING =(1.3 m)(0. 2 m)(4 m)(23. 6 )
m3
¿24 . 544 KN
22. 411
R1 =
4
∑M @ R 2
=0
¿ 5. 60 kN /m
;
STAIR 2: SECOND FLOOR STAIRS TO THIRD FLOOR 20 .734
R2 =
LANDING 4
∑M @ R 2
=0
¿ 5. 18 kN /m
;
KN
W LANDING=(1.3 m)(0. 2 m)(4 m)(23. 6 )
m3
¿24 . 544 KN
10. For 6” CHB exterior (plastered both sides) with windows @ 4x8
m Slab
(2. 7 )(4 x 3 . 4 )−(0 . 85 x 1 .3 x 6)(0 . 38)
Weight wall =
4
8.55015 KN / m
SECOND FLOOR SUMMARY:
SLAB FLOOR AREA (m2) DEAD LOAD LIVE LOAD
REFERENCE
PRESSURE (kPa) WEIGHT (KN) PRESSURE (kPa) WEIGHT (KN)
V =0.11C a IW t G. The remaining portion of the base shear shall be distributed over the
height of the structure, including Level n, according to:
Wx (kN) hx (m) Wxhx Fx (V −F t )W x h x
Fx=
1083.8108 10.6 11488.39448 46.37+3.33 ∑ W i hi
1379.0013 7 9653.0091 38.97
1315.52725 3.6 4735.8981 19.11
TOTAL 25895.30168 kN 107.78 kN
V =0.11(0.44)(1)(14214.9573 )
=130 .42 KN
0 . 85 zN v IW t
V=
R
0 .85(0.4)(1)(1)(14214 .9573 )
V=
8 .5
=107 .78 KN