Single Bus System
Single Bus System is simplest and cheapest one. In this scheme all the feeders and
transformer bay are connected to only one single bus as show.
Advantages of Single Bus System
1. This is very simple in design.
2. This is very cost effective scheme.
3. This is very convenient to operate.
Disadvantages of Single Bus System
1. One but major difficulty of these type of arrangement is that, maintenance of
equipment of any bay cannot be possible without interrupting the feeder or
transformer connected to that bay.
2. The indoor 11 KV switch boards have quite often single bus bar arrangement.
Single Bus System with Bus Sectionalizer
Some advantages are realized if a single bus bar is sectionalized with circuit
breaker. If there are more than one incoming and the incoming sources and
outgoing feeders are evenly distributed on the sections as shown in the figure,
interruption of system can be reduced to a good extent.
Advantages of Single Bus System with Bus Sectionalizer
If any of the sources is out of system, still all loads can be fed by switching on the
sectional circuit breaker or bus coupler breaker. If one section of the bus bar
system is under maintenance, part load of the substation can be fed by energizing
the other section of bus bar.
Disadvantages of Single Bus System with Bus Sectionalizer
1. As in the case of single bus system, maintenance of equipment of any bay
cannot be possible without interrupting the feeder or transformer connected to
that bay.
2. The use of isolator for bus sectionalizing does not fulfil the purpose. The
isolators have to be operated ‘off circuit’ and which is not possible without total
interruption of bus – bar. So investment for bus-coupler breaker is required.
Double Bus System
1. In double bus bar system two identical bus bars are used in such a way that any
outgoing or incoming feeder can be taken from any of the bus.
2. Actually every feeder is connected to both of the buses in parallel through
individual isolator as shown in the figure.
By closing any of the isolators one can put the feeder to associated bus. Both of the
buses are energized and total feeders are divided into two groups, one group is fed
from one bus and other from other bus. But any feeder at any time can be
transferred from one bus to other. There is one bus coupler breaker which should
be kept close during bus transfer operation. For transfer operation, one should first
close the bus coupler circuit breaker then close the isolator associated with the bus
to where the feeder would be transferred and then open the isolator associated with
the bus from where feeder is transferred. Lastly after this transfer operation he or
she should open the bus coupler breaker.
Advantages of Double Bus System
Double Bus Bar Arrangement increases the flexibility of system.
Disadvantages of Double Bus System
The arrangement does not permit breaker maintenance without interruption.
Double Breaker Bus System
In double breaker bus bar system two identical bus bars are used in such a way that
any outgoing or incoming feeder can be taken from any of the bus similar to
double bus bar system. Only difference is that here every feeder is connected to
both of the buses in parallel through individual breaker instead only isolator as
shown in the figure. By closing any of the breakers and its associated isolators one
can put the feeder to respective bus. Both of the buses are energized and total
feeders are divided into two groups, one group is fed from one bus and other from
other bus similar to previous case. But any feeder at any time can be transferred
from one bus to other. There is no need of bus coupler as because the operation is
done by breakers instead of isolator. For transfer operation, one should first close
the isolators and then the breaker associated with the bus to where the feeder
would be transferred and then he or she opens the breaker and then isolators
associated with the bus from where feeder is transferred.
One and A Half Breaker Bus System
This is an improvement on the double breaker scheme to effect saving in the
number of circuit breakers. For every two circuits only one spare breaker is
provided. The protection is however complicated since it must associate the central
breaker with the feeder whose own breaker is taken out for maintenance. For the
reasons given under double breaker scheme and because of the prohibitory costs of
equipment even this scheme is not much popular. As shown in the figure that it is a
simple design, two feeders are fed from two different buses through their
associated breakers and these two feeders are coupled by a third breaker which is
called tie breaker. Normally all the three breakers are closed and power is fed to
both the circuits from two buses which are operated in parallel. The tie breaker acts
as coupler for the two feeder circuits.
Advantages of One and A Half Breaker Bus System
During any fault on any one of the buses, that faulty bus will be cleared instantly
without interrupting any feeders in the system since all feeders will continue to
feed from other healthy bus.
Disadvantages of One and A Half Breaker Bus System
This scheme is much expensive due to investment for third breaker.
Main and Transfer Bus System
This is an alternative of double bus system. The main conception of Main and
Transfer Bus System is, here every feeder line is directly connected through an
isolator to a second bus called transfer bus. The said isolator in between transfer
bus and feeder line is generally called bypass isolator. The main bus is as usual
connected to each feeder through a bay consists of circuit breaker and associated
isolators at both side of the breaker. There is one bus coupler bay which couples
transfer bus and main bus through a circuit breaker and associated isolators at both
sides of the breaker. If necessary the transfer bus can be energized by main bus
power by closing the transfer bus coupler isolators and then breaker. Then the
power in transfer bus can directly be fed to the feeder line by closing the bypass
isolator. If the main circuit breaker associated with feeder is switched off or
isolated from system, the feeder can still be fed in this way by transferring it to
transfer bus.
Switching Operation for Transferring a Feeder to Transfer Bus from Main
Bus without Interruption of Power
1. First close the isolators at both side of the bus coupler breaker.
2. Then close the bypass isolator of the feeder which is to be transferred to transfer
bus.
3. Now energized the transfer bus by closing the bus coupler circuit breaker from
remote.
4. After bus coupler breaker is closed, now the power from main bus flows to the
feeder line through its main breaker as well as bus coupler breaker via transfer
bus.
5. Now if main breaker of the feeder is switched off, total power flow will
instantaneously shift to the bus coupler breaker and hence this breaker will serve
the purpose of protection for the feeder.
6. At last the operating personnel open the isolators at both sides of the main
circuit breaker to make it isolated from rest of the live system.
So, it can be concluded that in Main and Transfer Bus System the maintenance of
circuit breaker is possible without any interruption of power. Because of this
advantage the scheme is very popular for 33 kV and 13 kV systems.
Double Bus System with Bypass Isolators
This is combination of the double bus system and main and transfer bus system. In
Double Bus System with Bypass Isolators either bus can act as main bus and
second bus as transfer bus. It permits breaker maintenance without interruption of
power which is not possible in double bus system but it provides all the advantages
of double bus system. It however requires one additional isolator (bypass isolator)
for each feeder circuit and introduces slight complication in system layout. Still
this scheme is best for optimum economy of system and it is best optimum choice
for 220 kV system.
Ring Bus System
The schematic diagram of the system is given in the figure. It provides a double
feed to each feeder circuit, opening one breaker under maintenance or otherwise
does not affect supply to any feeder. But this system has two major disadvantages.
One as it is closed circuit system it is next to impossible to extend in future and
hence it is unsuitable for developing system. Secondly, during maintenance or any
other reason if any one of the circuit breaker in ring loop is switch of reliability of
system becomes very poor as because closed loop becomes opened. Since, at that
moment for any tripping of any breaker in the open loop causes interruption in all
the feeders between tripped breaker and open end of the loop.