HFO Storage Tank Steam Requirement Analysis

HFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil Sizing

Uploaded by

Saeed Rehman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
1K views1 page

HFO Storage Tank Steam Requirement Analysis

HFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil SizingHFO Bulk Storage Tank Steam Coil Sizing

Uploaded by

Saeed Rehman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Steam Requirement Calculation

SUPPLYCHAIN SERVICES FAUJI FOODS

Prepared By: MMS


Determination of Steam Requirement & Heating Coil Sizing For Un-Insulated Fuel Oil Tanks based on " KELLOGG" METHOD Checked By: ANA
Date: 11/12/2017
CONSULTANT: Supply Chain Services
EQUIPMENT: HFO Bulk STORAGE Tank
CLIENT: IM & S Engineering ( Pvt.) Ltd.
REVISION: 0

TANK DETAILS
Tank Height = 27.89 ft 8.5 m Input Values
Tank Diameter = 22.97 ft 7 m Calculated Values
Area of Tank Walls = 2012 ft2
Area of Tank Top = 0 ft2 Not Applicable
Area of Tank Bottom = 414 ft²
Total Surface Area of Tank to be heated (Ae) = 2427 ft²
Tank Volume = 11553.8 ft3
Density of Fluid in Tank = 58.9 lb/ft3 945 kg/m3 (from Hysys, FO)
Mass of Fluid in tank = 646,769 lb 95 % Filled of Tank Volume

OPERATING PARAMETERS
Specific Heat of Fluid in Tank = 0.42 Btu/lb/F (from Hysys, FO)
Temperatre of Environment (Te) = 32 F 0.0 C
Temperature of Tank Interior (Ti) = 122 F 50.0 C
Steam Quality = Saturated Steam at 8 barg.
Temperature of Steam at Saturation (Ts) = 347.61 F 175.3 C
Pressure of Steam = 116 psig
Latent Heat of Vapourization of Steam (ΔHv) = 896.40 BTU/Lb
Density of Steam at Saturated Condition (ρs) = 0.2598 Lb/ftᶟ

HEAT TRANSFER RATES


2
Heat Transfer Rates of Coil for Uninsulated Tank (Ue) = 5 BTU/hr/ft /F From "KELLOGG" Vessel Design Manual
Heat Transfer Rates of Coil for Tank Contents [Natural Convection Only, No Agitation] (Us) = 15 BTU/hr/ft²/F From "KELLOGG" Vessel Design Manual

HEAT DUTY & STEAM REQUIREMENT CALCULATIONS


Temprature Differential Across the Tank External Surface (ΔTe) = 90 F
Heat Duty Requirement (Qe) = 1,091,934.91 BTU/hr
Temprature Differential Across the Coil (ΔTs) = 226 F
Steam Flow Rate Requirement (W) = 1,218 Lbs/hr 553 Kg/hr

COIL DETAILS
Coil Surface Area (As) = 323 ft²
Coil Pipe Size NPS = 1.25 in SCH # 40
Inside Diameter of Pipe (d) = 1.38 in
Pipe Surafce Area of Heating Coil/ ft² (Ao) = 0.434 ft²/ft
Total Length of Coil (L) = 743 ft 227 m
Actual Length of Coil Used Based on Bottom Surface Area = 1,020 ft 311 m
Steam Flow Splitter = Yes Tank Diameter > 5m
Steam Flow in each set of Coil (W) = 406 Lbs/hr Number of Steam Coil Set=03 Nos.

STEAM PRESSURE DROP CALCULATION IN COIL


Pressure Drop per ft of Pipe (ΔP/L) = 0.0166 psid/ft
pressure drop/ 100 ft found Ok.
Pressure Drop per 100 ft of Pipe [(ΔP/L)*100] = 1.66 psid/100ft ( Normal range 1.5 to 2 psid)
Total Pressure Drop = 16.94 psid

FILE: HFO Bulk Storage Tank Steam Coil Sizing SHEET 1 OF 1