ETP48400-C3B1/C3B2 Power User Manual

The document is a user manual for the ETP48400-C3B1 and ETP48400-C3B2 embedded power systems, detailing installation, operation, maintenance, and safety precautions. It is intended for sales, technical support, and maintenance engineers, and includes a comprehensive overview of components and procedures. The manual emphasizes adherence to safety standards and provides guidelines for avoiding equipment damage and personal injury.

Uploaded by

Dac D
Copyright
© All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views126 pages

ETP48400-C3B1/C3B2 Power User Manual

The document is a user manual for the ETP48400-C3B1 and ETP48400-C3B2 embedded power systems, detailing installation, operation, maintenance, and safety precautions. It is intended for sales, technical support, and maintenance engineers, and includes a comprehensive overview of components and procedures. The manual emphasizes adherence to safety standards and provides guidelines for avoiding equipment damage and personal injury.

Uploaded by

Dac D
Copyright
© All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

ETP48400-C3B1 and ETP48400-C3B2 Embedded

Power

User Manual

Issue 07
Date 2022-06-28

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2022. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: [Link]
Email: support@[Link]

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. i


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual About This Document

About This Document

Purpose
This document describes DC power systems in terms of product overview,
components, installation, commissioning, maintenance, and operations for the site
monitoring module (SMU) and rectifiers.

Figures provided in this document are for reference only.

Intended Audience
This document is intended for:

● Sales engineers
● Technical support engineers
● Maintenance engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk which, if not


avoided, will result in death or serious injury.

Indicates a hazard with a medium level of risk which, if not


avoided, could result in death or serious injury.

Indicates a hazard with a low level of risk which, if not


avoided, could result in minor or moderate injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. ii


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual About This Document

Symbol Description

Supplements the important information in the main text.


NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.

Change History
Changes between document issues are cumulative. The latest document issue
contains all the changes made in earlier issues.

Issue 07 (2022-06-28)
Added the cable connection description for the DCDB48-400-4C.

Issue 06 (2021-05-10)
Modified 2.1 Product Overview, 4.1.2 Tools.

Issue 05 (2020-03-25)
Modified 6.8 Setting DCDB Parameters.

Issue 04 (2019-12-17)
Optimized the content of the document.

Issue 03 (2019-11-18)
Optimized the content of the document.

Issue 02 (2019-10-25)
The DCDB parameter is added.
Deleted contents about the app.

Issue 01 (2019-05-30)
This is the first official release.
The SMU software version is SMU V500R003C00.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. iii


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual Contents

Contents

About This Document................................................................................................................ ii


1 Safety Precautions...................................................................................................................1
1.1 General Safety.......................................................................................................................................................................... 1
1.2 Personnel Requirements....................................................................................................................................................... 5
1.3 Electrical Safety........................................................................................................................................................................ 6
1.4 Installation Environment Requirements.......................................................................................................................... 7
1.5 Mechanical Safety................................................................................................................................................................... 9
1.6 Battery Safety......................................................................................................................................................................... 12

2 Product Overview.................................................................................................................. 16
2.1 Product Overview..................................................................................................................................................................16
2.2 Product Introduction............................................................................................................................................................ 16

3 Components............................................................................................................................22
3.1 Monitoring Module SMU02C............................................................................................................................................ 22
3.2 User Interface Module UIM05B1..................................................................................................................................... 26
3.3 Communications Expansion Module NIM01C3.......................................................................................................... 27
3.4 Communications Expansion Module CIM02C............................................................................................................. 30
3.5 Rectifier.................................................................................................................................................................................... 33
3.6 Digital Temperature and Humidity Sensor.................................................................................................................. 34

4 System Installation............................................................................................................... 36
4.1 Preparing for the Installation........................................................................................................................................... 36
4.1.1 Preparing Cables................................................................................................................................................................ 36
4.1.2 Tools....................................................................................................................................................................................... 38
4.1.3 Installation Dimensions................................................................................................................................................... 39
4.2 Installing Devices.................................................................................................................................................................. 40
4.3 Installing Ground Cables.................................................................................................................................................... 41
4.4 Installing a Rectifier............................................................................................................................................................. 43
4.5 Installing a Circuit Breaker................................................................................................................................................ 44
4.6 Installing a Digital Temperature and Humidity Sensor........................................................................................... 44
4.7 Installing a Communications Expansion Module NIM01C3...................................................................................46
4.8 Installing a Communications Expansion Module CIM02C...................................................................................... 48
4.9 (Optional) Installing Dry Contact Signal Cables........................................................................................................ 48
4.10 (Optional) Installing Communications Cables......................................................................................................... 49

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. iv


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual Contents

4.10.1 WebUI Management......................................................................................................................................................49


4.10.2 Using the U2000-SPM for Management................................................................................................................ 50
4.10.3 NetEco Management..................................................................................................................................................... 51
4.10.4 Third-Party NMS Management (over SNMP)....................................................................................................... 53
4.11 Installing Sensor Cables................................................................................................................................................... 54
4.11.1 Installing Door Status Sensor Cables....................................................................................................................... 54
4.11.2 Installing Battery Temperature Sensor Cables...................................................................................................... 54
4.11.3 Installing Smoke Sensor Cables................................................................................................................................. 55
4.11.4 Installing a Water Sensor Cable.................................................................................................................................55
4.12 Installing Cables.................................................................................................................................................................. 56
4.12.1 Installing DC Output Power Cables.......................................................................................................................... 56
4.12.2 Installing a 220/380 V AC Three-Phase Four-Wire Input Power Cable........................................................ 59
4.12.3 Installing 220 V AC Single-Phase Input Power Cables....................................................................................... 60
4.12.4 Installing 120/240 V AC Dual–Live Wire Input Power Cables......................................................................... 62
4.12.5 Installing Cables for an Intelligent Power Distribution Unit............................................................................ 63
4.12.6 Installing Cables for a Lead-Acid Battery Box....................................................................................................... 67
4.12.7 Installing Lithium Batteries and Cables...................................................................................................................70

5 Verifying the Installation.................................................................................................... 73


5.1 Checking Hardware Installation.......................................................................................................................................73
5.2 Checking Electrical Connections...................................................................................................................................... 73
5.3 Checking Cable Installation............................................................................................................................................... 73

6 Commissioning....................................................................................................................... 74
6.1 Powering on Lead-Acid Batteries.................................................................................................................................... 74
6.2 Connecting the Lithium Battery Supply........................................................................................................................ 75
6.3 Setting the Display Language.......................................................................................................................................... 75
6.4 Setting Deployment Wizard.............................................................................................................................................. 76
6.5 Setting the Date and Time................................................................................................................................................ 76
6.6 Setting the AC Input System............................................................................................................................................. 77
6.7 Setting the 57 V Constant Voltage Parameter........................................................................................................... 77
6.8 Setting DCDB Parameters.................................................................................................................................................. 78
6.9 Setting AC Peak Clipping Parameters............................................................................................................................ 78
6.10 Setting Sensor Parameters.............................................................................................................................................. 79
6.11 Setting the Mains Collection Channel......................................................................................................................... 80
6.12 Setting Communications Parameters.......................................................................................................................... 80
6.12.1 (Optional) Setting Parameters for WebUI Management..................................................................................80
6.12.2 (Optional) Setting Parameters Before Using U2000-SPM................................................................................87
6.12.3 (Optional) Setting Parameters Before Using NetEco......................................................................................... 88
6.12.4 (Optional) Setting Parameters Before Using SNMP Management............................................................... 89
6.13 Connecting the AC Power Supply................................................................................................................................. 91
6.14 Subsequent Operations.................................................................................................................................................... 91

7 Maintenance........................................................................................................................... 92

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. v


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual Contents

7.1 Routine Maintenance.......................................................................................................................................................... 92


7.1.1 AC and DC Power Distribution..................................................................................................................................... 92
7.1.2 Rectifier................................................................................................................................................................................. 93
7.1.3 Monitoring Unit................................................................................................................................................................. 94
7.1.4 Parameters on the SMU.................................................................................................................................................. 95
7.1.5 Cables.................................................................................................................................................................................... 96
7.2 Identifying Component Faults.......................................................................................................................................... 96
7.2.1 Identifying SMU Faults.................................................................................................................................................... 97
7.2.2 Identifying Rectifier Faults............................................................................................................................................. 97
7.2.3 Identifying Circuit Breaker Faults................................................................................................................................. 97
7.2.4 Locating AC Input Module Faults................................................................................................................................ 97
7.3 Replacing Components....................................................................................................................................................... 98
7.3.1 Replacing an SMU02C..................................................................................................................................................... 98
7.3.2 Replacing a UIM05B1.......................................................................................................................................................99
7.3.3 Replacing an NIM01C3................................................................................................................................................. 100
7.3.4 Replacing a CIM02C....................................................................................................................................................... 101
7.3.5 Replacing a DMU02C1.................................................................................................................................................. 103
7.3.6 Replacing a Rectifier...................................................................................................................................................... 104
7.3.7 Replacing a Circuit Breaker..........................................................................................................................................105
7.3.8 Replacing an AC Input Module.................................................................................................................................. 106
7.3.9 Replacing a Digital Temperature and Humidity Sensor.................................................................................... 107

A How Do I Install a Hall Effect Sensor?.......................................................................... 109


B Technical Specifications.....................................................................................................110
C Electrical Conceptual Diagrams...................................................................................... 113
D Associations Between UIM Dry Contacts and Alarms............................................... 114
E How Do I Change the Communications Protocol for COM4 and COM5?..............116
F Acronyms and Abbreviations............................................................................................118

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. vi


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

1 Safety Precautions

1.1 General Safety


Statement
Before installing, operating, and maintaining the equipment, read this document
and observe all the safety instructions on the equipment and in this document.

The "NOTICE", "CAUTION", "WARNING", and "DANGER" statements in this


document do not cover all the safety instructions. They are only supplements to
the safety instructions. The Company will not be liable for any consequence
caused by the violation of general safety requirements or design, production, and
usage safety standards.

Ensure that the equipment is used in environments that meet its design
specifications. Otherwise, the equipment may become faulty, and the resulting
equipment malfunction, component damage, personal injuries, or property
damage are not covered under the warranty.

Follow local laws and regulations when installing, operating, or maintaining the
equipment. The safety instructions in this document are only supplements to local
laws and regulations.

The Company will not be liable for any consequences of the following
circumstances:

● Operation beyond the conditions specified in this document


● Installation or use in environments which are not specified in relevant
international or national standards
● Unauthorized modifications to the product or software code or removal of the
product
● Failure to follow the operation instructions and safety precautions on the
product and in this document
● Equipment damage due to force majeure, such as earthquakes, fire, and
storms
● Damage caused during transportation by the customer

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 1


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

● Storage conditions that do not meet the requirements specified in this


document

General Requirements
● Before installing, operating, or maintaining the equipment, remove any
conductive objects such as watches or metal jewelry like bracelets, bangles,
and rings to avoid electric shock.
● When installing, operating, or maintaining the equipment, wear dedicated
protective gears such as insulation gloves, goggles, and safety clothing,
helmet, and shoes, as shown in the following figure.

● Use insulated tools or tools with insulated handles, as shown in the following
figure.

● Follow the specified procedures for installation, operation, and maintenance.


● Ensure that bolts are tightened with a torque wrench and marked using red or
blue color. Installation personnel mark tightened bolts in blue. Quality
inspection personnel confirm if the bolts are tightened and then mark them in

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 2


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

red. (The marks should cross the edges of the bolts, as shown in the following
figure.)

● Before installing, operating, or maintaining a cabinet, clean up any water, ice,


snow, or other sundries on the top of the cabinet to prevent sundries from
falling into the cabinet when you open the cabinet door.
● Do not install, use, or operate outdoor equipment and cables (including but
not limited to moving equipment, operating equipment and cables, inserting
connectors to or removing connectors from signal ports connected to outdoor
facilities, working at heights, and performing outdoor installation) in harsh
weather conditions such as lightning, rain, snow, and level 6 or stronger wind.
● Before handling a conductor surface or terminal, measure the contact point
voltage and ensure that there is no risk of electric shock.
● Ensure that all slots are installed with boards or filler panels. Avoid hazards
caused by hazardous voltages or energy on boards. Ensure that the air
channel is normal, control electromagnetic interference, and prevent dust and
other sundries on the backplane, baseplate, and boards.
● After installing the equipment, remove idle packing materials such as cartons,
foam, plastics, and cable ties from the equipment area.
● In the case of a fire, immediately leave the building or the equipment area,
and turn on the fire alarm bell or make an emergency call. Do not enter the
building on fire in any case.
● Do not stop using protective devices. Pay attention to the warnings, cautions,
and related precautionary measures in this document and on the equipment.
Promptly replace warning labels that have worn out.
● Keep irrelevant people away from the equipment. Only operators are allowed
to access the equipment.
● All cable holes should be sealed. Seal the used cable holes with firestop putty.
Seal the unused cable holes with the caps delivered with the cabinet. The
following figure shows the criteria for correct sealing with firestop putty.

● Do not use solvents such as water, alcohol, or oil to clean electrical


components inside or outside of a cabinet.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 3


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

Personal Safety
● If there is a probability of personal injury or equipment damage during
operations on the equipment, immediately stop the operations, report the
case to the supervisor, and take feasible protective measures.
● To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits
to telecommunication network voltage (TNV) circuits.
● Do not power on the equipment before it is installed or confirmed by
professionals.

Symbol Conventions
To ensure personal and equipment safety, observe all the safety instructions
marked on the equipment when installing, operating, and maintaining the
equipment.

Symbol Description

Indicates a part exposed to high voltage. This symbol


warns operators that both direct and indirect contact with
the power grid voltage is fatal. This symbol is attached to
a position with dangerous voltages or a power protective
cover which may be removed during maintenance.

Warns users of overheating. This symbol is attached to a


device surface that may overheat and cause scalding. It
warns users not to touch the surface during operations or
maintenance. Users should wear heat insulation gloves
before operations to prevent scalding.

Indicates protection earthing. This symbol is attached next


or to a protection ground terminal next to grounded
equipment and an external ground system. An equipment
ground cable is connected to an external ground bar
through the protection ground terminal.

Indicates equipotential bonding. This symbol is found with


equipotential terminals inside equipment.

Indicates electrostatic discharge (ESD). This symbol is used


in all electrostatic sensitive areas. Before operating
equipment in these areas, wear ESD gloves or an ESD
wrist strap.

Capacitors store hazardous energy. Open the chassis one


minute after all power supplies are disconnected.
or

Indicates that the equipment is safe to use at altitudes


below 2000 m.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 4


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

Symbol Description

Indicates that the equipment is not safe to use in tropical


climates.

Indicates a fan assembly or moving part. This symbol is


silkscreened on or attached to the panel of a fan assembly,
or warning operators to keep away. Do not touch the blades
when the fan is rotating.

This symbol is used when the usage of a device port


cannot be clearly described. It prompts users to refer to
or the instruction. This symbol can be used in but not limited
to the following scenarios:
1. For a multi-power device, use it near the power supply
to replace the multi-power supply identifier. The
symbol indicates that the device has multiple power
inputs. Therefore, when powering off the device, you
must disconnect all power inputs.
or
2. If there are multiple output interfaces, use the symbol
near the output interfaces. Connect cables according to
the rated power output and configuration parameter
information in the instruction.
3. If there are multiple slots, use the symbol near the slot
information. For details, see the description of slot
information, restrictions on boards, and usage
conditions in the instruction.

1.2 Personnel Requirements


● Personnel who plan to install or maintain the equipment must receive
thorough training, understand all necessary safety precautions, and be able to
correctly perform all operations.
● Only qualified professionals or trained personnel are allowed to install,
operate, and maintain the equipment.
● Only qualified professionals are allowed to remove safety facilities and inspect
the equipment.
● Personnel who will operate the equipment, including operators, trained
personnel, and professionals, should possess the local national required
qualifications in special operations such as high-voltage operations, working
at heights, and operations of special equipment.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 5


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

NOTE

● Professionals: personnel who are trained or experienced in equipment operations and


are clear of the sources and degree of various potential hazards in equipment
installation, operation, maintenance
● Trained personnel: personnel who are technically trained, have required experience, are
aware of possible hazards on themselves in certain operations, and are able to take
protective measures to minimize the hazards on themselves and other people
● Operators: operation personnel who may come in contact with the equipment, except
trained personnel and professionals

1.3 Electrical Safety


Grounding
● The protective ground of the equipment should be reliably connected to the
ground screw on the metal enclosure (grounding resistance ≤ 0.1 ohm).
● For the equipment that needs to be grounded, install the ground cable first
when installing the equipment and remove the ground cable last when
removing the equipment.
● Do not damage the ground conductor.
● Do not operate the equipment in the absence of a properly installed ground
conductor.
● For the equipment that uses a three-pin socket, ensure that the ground
terminal in the socket is connected to the protection ground.

AC and DC Power

DANGER

● The power system is energized by power sources with hazardous voltage. Direct
or indirect contact (through damp objects) with the power sources may result
in electric shock.
● Non-standard and improper operations may result in fire or electric shock.
● Do not connect or disconnect power cables with power on. Transient contact
between the core of the power cable and the conductor will generate electric
arcs or sparks, which may cause fire or personal injury.

● If the power supply to the equipment is permanently connected, install an


easily accessible disconnector at the exterior of the device.
● Before making electrical connections, switch off the disconnector on the
upstream device to cut off the power supply if people may contact energized
components.
● If a "high electricity leakage" tag is attached on the equipment, ground the
protective ground terminal on the equipment enclosure before connecting the
AC power supply; otherwise, electric shock as a result of electricity leakage
may occur.
● Before installing or removing a power cable, turn off the power switch.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 6


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

● Before connecting a power cable, check that the label on the power cable is
correct.
● Before connecting the power supply, ensure that cable connections are
correct.
● If the equipment has multiple inputs, disconnect all the inputs before
operating the equipment.

Cabling
● When routing cables, ensure that a distance of at least 30 mm exists between
the cables and heat-generating components or areas. This prevents damage
to the insulation layer of the cables.
● Do not route cables behind the air intake and exhaust vents of the
equipment.
● Ensure that cables meet the VW-1 flame spread rating requirements.
● Bind cables of the same type together. When routing cables of different types,
ensure that they are at least 30 mm away from each other.
● Ensure that all cables are securely bound. Route and bind cables so that they
appear neat and tidy and their cable sheaths are intact.
● If an AC input power cable is connected to the cabinet from the top, bend the
cable in a U shape outside the cabinet and then route it into the cabinet.
● Ensure that the bending radius of each cable is at least five times the
diameter of the cable.
● When routing power cables, ensure that there is no coiling or twisting. Do not
join or weld power cables. If necessary, use a longer cable.

ESD
● When installing, operating, and maintaining the equipment, comply with the
ESD protection regulations and wear the ESD clothing, gloves, and wrist strap.
● When holding a board, hold its edge without touching any components. Do
not touch the components with your bare hands.
● Package boards with ESD packaging materials before storing or transporting
them.

1.4 Installation Environment Requirements


● To prevent fire due to high temperature, ensure that the ventilation vents or
heat dissipation system are not blocked when the equipment is running.
● Ensure that there are no acid, alkaline, or other corrosive gases in the
installation place.
● Do not place the equipment near heat sources or exposed fire sources, such
as electric heaters, microwave ovens, roasters, water heaters, furnace fire,
candles, or other places where high temperature may occur. Otherwise, the
enclosure will melt or the equipment will heat up, which can cause a fire.
● Install the equipment in an area far away from liquids. Do not install it under
areas prone to condensation, such as under water pipes and air exhaust vents,
or areas prone to water leakage, such as air conditioner vents, ventilation

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 7


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

vents, or feeder windows of the equipment room. Ensure that no liquid enters
the equipment to prevent faults or short circuits.
● Before installing the equipment into a cabinet, ensure that the cabinet is
secured and will not tilt or fall down due to loss of balance, which can cause
personal injury or equipment damage.
● Do not expose the equipment to flammable or explosive gas or smoke. Do
not perform any operation on the equipment in such environments.

Installation at Heights
Working at heights refers to operations that are performed at least 2 meters
above the ground.
Do not at heights in any of the following situations:
● Rainwater remains on steel pipes or other risky conditions exist. After the
preceding conditions no longer exist, the safety director and relevant technical
personnel need to check the involved equipment. Operators can begin
working only after obtaining consent.
● When working at heights, comply with local relevant laws and regulations.
● Only trained and qualified personnel are allowed to work at heights.
● Before working at heights, check the climbing tools and safety gears such as
safety helmets, safety belts, ladders, springboards, scaffolding, and lifting
equipment. If they do not meet the requirements, take corrective measures or
disallow working at heights.
● Wear personal protective equipment such as the safety helmet and safety belt
or waist rope and fasten it to a solid structure. Do not mount it on an
insecure moveable object or metal object with sharp edges. Make sure that
the hooks will not slide off.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 8


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

DANGER

● Set a restricted area and eye-catching signs for working at heights to warn
away irrelevant personnel.
● Carry the operation machinery and tools properly to prevent them from falling
off and causing injuries.
● Personnel involving working at heights are not allowed to throw objects from
the height to the ground, or vice versa. Objects should be transported by tough
slings, hanging baskets, highline trolleys, or cranes.
● Do not perform operations on the upper and lower layers at the same time. If
unavoidable, install a dedicated protective shelter between the upper and lower
layers or take other protective measures. Do not pile up tools or materials on
the upper layer.
● Ensure that guard rails and warning signs are set at the edges and openings of
the area involving working at heights to prevent falls.
● Do not pile up scaffolding, springboards, or other sundries on the ground under
the area involving working at heights. Do not allow people to stay or pass
under the area involving working at heights.
● Inspect the scaffolding, springboards, and workbenches used for working at
heights in advance to ensure that their structures are solid and not overloaded.
● Dismantle the scaffolding from top down after finishing the job. Do not
dismantle the upper and lower layers at the same time. When removing a part,
ensure that other parts will not collapse.
● Do not loiter when working at heights. Do not sleep at heights.

● Any violations must be promptly pointed out by the site manager or safety
supervisor and the involved personnel should be prompted for correction.
Personnel who fail to stop violations will be forbidden from working.
● Operators who violate the safety regulations are responsible for accidents
caused. The supervisor has to bear the responsibility accordingly.

1.5 Mechanical Safety


Hoisting Devices

DANGER

Do not walk under hoisted objects.

● Only trained and qualified personnel are allowed to perform hoisting


operations.
● Check that hoisting tools are available and in good condition.
● Before hoisting objects, ensure that hoisting tools are firmly secured onto a
load-bearing object or wall.
● Ensure that the angle formed by two hoisting cables is no more than 90
degrees, as shown in the following figure.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 9


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

● Do not drag steel ropes and hoisting tools or bump hoisted objects against
hard objects during hoisting.

Using Ladders
● Use wooden or fiberglass ladders when you need to perform live working at
heights.
● When a step ladder is used, ensure that the pull ropes are secured and the
ladder is held firm.
● Before using a ladder, check that it is intact and confirm its load bearing
capacity. Do not overload it.
● Ensure that the wider end of the ladder is at the bottom, or protective
measures have been taken at the bottom to prevent the ladder from sliding.
● Ensure that the ladder is securely positioned. The recommended angle for a
ladder against the floor is 75 degrees, as shown in the following figure. An
angle ruler can be used to measure the angle.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 10


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

When climbing a ladder, take the following precautions to reduce risks and ensure
safety:
● Keep your body steady.
● Do not climb higher than the fourth rung of the ladder from the top.
● To climb onto a roof, ensure that the ladder top is at least one meter higher
than the roof line, as shown in the following figure.

● Ensure that your body's center of gravity does not shift outside the legs of the
ladder.

Drilling Holes
When drilling holes into a wall or floor, observe the following safety precautions:

NOTICE

Do not drill holes into the equipment. Doing so may affect the electromagnetic
shielding of the equipment and damage components or cables inside. Metal
shavings from drilling may short-circuit boards inside the equipment.

● Wear goggles and protective gloves when drilling holes.


● When drilling holes, protect the equipment from shavings. After drilling, clean
up any shavings that have accumulated inside or outside the equipment.

Moving Heavy Objects


● Be cautious to avoid injury when moving heavy objects.

● When moving the equipment by hand, wear protective gloves to prevent


injuries.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 11


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

● Move or lift the equipment by holding its handles or lower edges. Do not hold
the handles of modules (such as power supply units, fans, and boards) that
are installed in the equipment because they cannot support the weight of the
equipment.

1.6 Battery Safety


If no battery is involved, skip this section.
Before installing, operating, or maintaining batteries, read the battery
manufacturer's instructions. Observe the safety precautions provided in this
document which are supplemental to the safety instructions provided by the
battery manufacturer.

Basic Requirements
Before operating batteries, carefully read the safety precautions for battery
handling and master the correct battery connection methods.

DANGER

● Do not expose batteries at high temperatures or around heat-generating


sources, such as sunlight, fire sources, transformers, and heaters. Overheating
may cause battery explosion.
● Do not burn batteries. Otherwise, the batteries may explode.
● To avoid leakage, overheating, fire, or explosions, do not disassemble, alter, or
damage batteries, for example, insert sundries into batteries or immerse
batteries in water or other liquids.
● When replacing a battery, use a battery of the same model or type. Improper
replacement may cause the battery to explode.
● Do not connect a metal conductor to the battery poles or touch the battery
terminals. Otherwise, the battery may be short-circuited and heat up, which
can cause injuries such as burning.

To ensure safety during battery installation, operation, and maintenance, pay


attention to the following:
● Do not wear conductive articles such as watches, bracelets, bangles, and rings.
● Wear goggles, rubber gloves, and protective clothing to avoid damage caused
by electrolyte in the case of electrolyte overflow. If a battery overflows,
protect the skin or eyes from the leaking liquid. If the skin or eyes come in
contact with the leaking liquid, wash it immediately with clean water and go
to the hospital for medical treatment.
● Use dedicated insulated tools.
● Move batteries in the required direction. Do not place a battery upside down
or tilt it.
● Keep the battery loop disconnected during installation and maintenance.
● Do not drop, squeeze, or puncture a battery. Protect batteries from external
high pressure to prevent internal short circuits and overheating.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 12


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

● Dispose of waste batteries in accordance with local laws and regulations. Do


not dispose of batteries as household waste. If a battery is disposed of
improperly, it may explode.
● Do not use a damaged battery.
● To prevent injuries or explosion, do not allow children or pets to swallow or
bite a battery.
● If batteries experience discoloration, deformation, abnormal heating, or other
abnormalities during working, charging, or storage, stop using the batteries
and replace them with new ones.
● Batteries can work properly with the allowed charge and discharge
parameters when the temperature is within the specified range. If the
temperature is outside the specified range, the battery charge and discharge
performance and safety are affected.

Battery Installation
Before installing batteries, observe the following safety precautions:

● Install batteries in a dry and cool environment with good ventilation, which is
away from high temperature and flammable materials, and take precautions
against fire.
● Place and secure batteries horizontally.
● Note the polarities when installing batteries. Do not short-circuit the positive
and negative poles of the same battery or battery string. Otherwise, the
battery may be short-circuited.
● When installing a battery string, retain at least one breakpoint to prevent a
loop being formed. After checking that the installation is correct, close the
breakpoints to finish the installation.
● During the installation, insulate the terminals of cables connecting batteries.
Ensure that the terminals do not come into contact with metal components
such as the cabinet.
● Secure battery cables or copper bars by tightening bolts to the required
torque. Loose connections will result in excessive voltage drop or cause
batteries to burn out in the case of excessive current.
● Check battery connections periodically, ensuring that all screws are securely
tightened.

Battery Short Circuit

DANGER

Battery short circuits can generate high instantaneous current and release a great
amount of energy, which may cause equipment damage or personal injury.

● If permitted, disconnect the batteries in use before performing any other


operations on them.
● To avoid battery short circuit, do not maintain batteries with power on.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 13


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

Flammable Gas

NOTICE

● Do not use unsealed lead-acid batteries.


● To prevent fire or corrosion, ensure that flammable gas (such as hydrogen) is
properly exhausted for lead-acid batteries.

Lead-acid batteries emit flammable gas when used. Ensure that batteries are kept
in a well-ventilated area and take preventive measures against fire.

Battery Leakage

NOTICE

Battery overheating causes deformation, damage, and electrolyte overflow.

If the battery temperature is higher than 60°C, check the battery for electrolyte
overflow. If the electrolyte overflows, handle the leakage immediately.
Electrolyte overflow may damage the equipment. It will corrode metal parts and
boards, and ultimately damage the boards.

WARNING

When the electrolyte overflows, absorb and neutralize the electrolyte immediately.
When moving or handling a battery whose electrolyte leaks, note that the leaking
electrolyte may cause damage.

If the electrolyte overflows, follow the instructions of the battery manufacturer or


neutralize the electrolyte by using sodium bicarbonate (NaHCO3) or sodium
carbonate (Na2CO3).

Lithium Battery
The safety precautions for lithium batteries are similar to those for lead-acid
batteries except that you also need to observe the following precautions.

WARNING

There is a risk of explosion if the model of the replaced battery is incorrect.

● A battery can be replaced only with a battery of the same or similar model
recommended by the manufacturer.
● When handling a lithium battery, do not place it upside down, tilt it, or bump
it with other objects.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 14


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 1 Safety Precautions

● Keep the lithium battery loop disconnected during installation and


maintenance.
● When the ambient temperature is lower than the lower limit of the operating
temperature (charge is forbidden at 0°C), do not charge the lithium battery.
Otherwise, a short circuit would occur inside the battery.
● Do not throw a lithium battery in fire.
● When maintenance is complete, return the waste lithium battery to the
maintenance office.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 15


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 2 Product Overview

2 Product Overview

2.1 Product Overview


The ETP48400-C3B1 and ETP48400-C3B2 are embedded power systems that
convert AC power into DC power. They supply –48 V or –57 V constant voltage to
load equipment. The maximum capacity of the ETP48400-C3B1 is 24 kW, and the
maximum capacity of the ETP48400-C3B2 is 18 kW. They apply to newly built sites
as well as capacity expansion and reconstruction of existing sites. The intelligent
power distribution unit DCDB48-200-16B/DCDB48-200-16B-XXX and lead-acid
battery box DCDB48-400-4C are optional components.

2.2 Product Introduction


ETP48400-C3B1/ETP48400-C3B2

Figure 2-1 ETP48400-C3B1 appearance

(1) Ground screw (2) AC input module (3) LLVD power distribution

(4) SMU02C (5) BLVD power distribution (6) Battery wiring ports

(7) Reserved slot for CIM02C/ (8) UIM05B1 (9) Space for rectifiers
NIM01C3

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 16


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 2 Product Overview

Figure 2-2 ETP48400-C3B2 appearance

(1) Ground screw (2) AC input module (3) LLVD power distribution

(4) SMU02C (5) BLVD power distribution (6) Battery wiring ports

(7) Reserved slot for CIM02C/ (8) UIM05B1 (9) Space for rectifiers
NIM01C3

Table 2-1 System specifications


Item ETP48400-C3B1 ETP48400-C3B2

AC input system 220/380 V AC three-phase four- 120/240 V AC dual–live wire


wire, compatible with 220 V AC
single-phase

DC power distribution ● LLVD: two 125 A and three 63 A circuit breakers


● BLVD: two 63 A, two 32 A, and two 16 A circuit breakers

Surge protection ● AC surge protection: nominal surge discharge current: 30 kA (8/20


µs), five times respectively in the positive and negative directions
● DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA
(8/20 µs) in common mode

(Optional) Intelligent Power Distribution Unit

Figure 2-3 DCDB48-200-16B appearance

(1) Ground screw (2) LLVD power distribution (3) BLVD power distribution

(4) DMU02C1 (5) DC input ports

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 17


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 2 Product Overview

Figure 2-4 DCDB48-200-16B-XXX appearance

(1) Ground screw (2) LLVD power distribution (3) BLVD power distribution

(4) DMU02C1 (5) DC input ports

Figure 2-5 DMU02C1 panel

(1) Run indicator (2) Alarm indicator (3) RS485 communications


ports

Table 2-2 Indicator description

Name Color Status Description

Run Green Off The DMU is faulty or has no DC


indicator input.

Blinking The communications is normal.


slowly (0.5
Hz)

Blinking fast The communications fails.


(4 Hz)

Alarm Red Off No alarm is generated.


indicator
Steady on An alarm is generated.

Table 2-3 Communication port description

Communications Communications Communications


Port Parameter Protocol

COM1/COM2 Baud rate: 9600 bit/s Modbus protocol


NOTE
All these ports are protected by a security mechanism.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 18


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 2 Product Overview

Figure 2-6 Communication port pins

Table 2-4 Pin definitions for the RS485 port


Pin Signal Description

1 TX+ Transmits data over RS485

2 TX-

4 RX+ Receives data over RS485

5 RX-

3, 6, 7, 8 NA –

Figure 2-7 DIP switch

NOTE

● When multiple DCDB48-200-16Bs are cascaded, you need to set the address DIP switch
for the DMU02C1.
● If one DCDB48-200-16B is installed, you do not need to set the address DIP switch for
the DMU02C1.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 19


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 2 Product Overview

Table 2-5 DIP switch description


Address of Intelligent Pin 1 Pin 2
Power Distribution Unit

1 OFF OFF

2 OFF ON

3 ON OFF

4 ON ON
NOTE
● If one contactor and one shunt are installed, for example, in a DCDB48-200-16B-4731,
set pin3 to OFF and pin4 to OFF.
● If two contactors and one shunt are installed, for example, in a
DCDB48-200-16B-4731-008, set pin3 to OFF and pin4 to ON.

Table 2-6 DCDB specifications


Item DCDB48-200-16B DCDB48-200-16B-XXX

Input voltage 40–60 V DC

Total input Maximum: 200 A


current

DC power ● BLVD power Supports a maximum of 16 circuit breakers.


distribution distribution: two 1- ● BLVD configuration: A maximum of six 16 A, 20
pole 16 A, two 1-pole A, 32 A, 40 A, or 63 A circuit breakers can be
20 A, and two 1-pole installed.
32 A circuit breakers
● LLVD configuration 1: A maximum of ten 16 A,
● LLVD power 20 A, 32 A, 40 A, or 63 A circuit breakers can be
distribution: four 1- installed.
pole 32 A and six 1-
pole 63 A circuit ● LLVD configuration 2: A maximum of seven 16
breakers A, 20 A, 32 A, 40 A, or 63 A circuit breakers and
two 80 A, 100 A, or 125 A circuit breakers can
be installed.

Dimensions (H 43.6 mm x 482.6 mm x 255 mm


x W x D)

Weight ≤ 10 kg

Installation Installed in a 19-inch rack


mode

Cabling mode Routed in and out from the front

Maintenance Maintained from the front


mode

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 20


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 2 Product Overview

(Optional) DCDB48-400-4C

Figure 2-8 DCDB48-400-4C appearance

(1) Ground screw (2) Battery circuit breaker (3) Battery power distribution
status detection ports

(4) Space reserved for battery (5) DC input ports


power distribution

Table 2-7 DCDB48-400-4C specifications


Item Specifications

Input voltage 40–60 V DC

Total input current Maximum: 400 A

DC power distribution Four 1-pole 125 A circuit breakers

Dimensions (H x W x D) 43.6 mm x 482.6 mm x 180 mm

Weight ≤ 4 kg

Installation mode Installed in a 19-inch rack

Cabling mode Routed in and out from the front

Maintenance mode Maintained from the front

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 21


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

3 Components

3.1 Monitoring Module SMU02C


Figure 3-1 SMU02C

(1) SD card slot (2) Running indicator (3) Minor alarm indicator

(4) Major alarm indicator (5) Buttons (6) USB ports (protected by a
security protection mechanism)

(7) RS485/RS232 (8) FE communications port (9) CAN communications port


communications port

(10) LCD

Indicators

Table 3-1 Indicator description

Item Color Status Description

Running Green Off The SMU is faulty or has no DC


indicator input.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 22


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Item Color Status Description

Blinking slowly The SMU is running properly and


(0.5 Hz) communicating with the host
properly.

Blinking fast (4 The SMU is running properly but fails


Hz) to communicate with the host.

Minor Yellow Off No minor or warning alarm is


alarm generated.
indicator
Steady on A minor or warning alarm is
generated.

Major Red Off No critical or major alarm is


alarm generated.
indicator
Steady on A critical or major alarm is
generated.

Buttons

Table 3-2 Button description

Button Name Description

Up
Press or to browse menus or select
parameters.
Down

Back Returns to the previous menu without saving the


settings.

OK ● Enters the main menu from the standby screen.


● Enters a submenu from the main menu.
● Saves the submenu settings.

Note:
● The LCD screen becomes dark if no button is pressed within 30s.
● You need to log in again if no button is pressed within 1 minute.

● To increase or decrease a parameter value quickly, press and hold or

● Hold down and for 10s to restart the SMU.

● Hold down and (or ) for 2s to increase (or decrease) the LCD
contrast.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 23


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

SD Card Slot
An SD card is used to store up to 32 GB photos shot by the camera.

USB Port
You can quickly deploy a site, import and export configuration files, export run
logs, and upgrade software by inserting the USB flash drive that is specially used
for site deployment into the USB port.

After installing a dedicated WiFi module on the USB port, you can access the
WebUI locally.

NOTICE

Using a WiFi module not provided by the Company may cause function
abnormalities or data loss. The Company will not be liable for any loss caused
thereby.

Communications Ports

Table 3-3 Communication port description

Communications Port Communications Communications Function


Parameter Protocol

FE 10M/100M SNMP protocol Connects to a third-


autonegotiation party NMS.

BIN protocol Connects to a Huawei


NMS.

HTTPS protocol Connects to a PC and


manages the SMU
over the WebUI.

TCP-Modbus protocol Adapts to Huawei


TCP-Modbus and
connects to a third-
party NMS.

RS485/RS232 Baud rate: 1200 bit/s, Master/Slave protocol Connects to a Huawei


2400 bit/s, 4800 bit/s, NMS.
9600 bit/s, 14400 bit/s,
19200 bit/s, 115200 YDN protocol Connects to a third-
bit/s party NMS.

CAN Baud rate: 125 kbit/s CAN protocol Connects to Huawei


southbound devices.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 24


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Communications Port Communications Communications Function


Parameter Protocol
NOTE
All the preceding ports are protected by security mechanisms.

Figure 3-2 Communications port pin definitions

Table 3-4 Pin definitions for the FE port


Pin Signal Description

1 TX+ Transmit data over FE.

2 TX-

3 RX+ Receive data over FE.

6 RX-

4, 5, 7, 8 Null -

Table 3-5 RS485/RS232 port pin definitions


Pin Signal Description

1 TX+ Transmit data over RS485.

2 TX-

4 RX+ Receive data over RS485.

5 RX-

3 RX232 Receives data over RS232.

7 TX232 Transmits data over RS232.

6 PGND Protective earthing (PE)

8 Null -

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 25


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Table 3-6 Pin definitions for the CAN port


Pin Signal Description

1 RX+ Receive data over RS485.

2 RX-

3 Null -

4 TX+ Transmit data over RS485.

5 TX-

6 Null -

7 CANH CAN bus high level

8 CANL CAN bus low level

3.2 User Interface Module UIM05B1


Figure 3-3 Panel

(1) Dry contact and sensor (2) COM communications port (3) Battery temperature sensor
ports port

(4) Door status sensor port (5) Battery switch (6) Cable hole for fan cables

(7) Handle

NOTE

The battery switch is used only when the mains is unavailable.

Figure 3-4 Dry contacts

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 26


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Figure 3-5 Pins in a COM port

Table 3-7 Pin definitions for a COM port


Pin Signal Description

1 RS485_RX+ RS485 data +

2 RS485_RX– RS485 data –

3 12 V Power supply

4 RS485_TX+ RS485 data +

5 RS485_TX– RS485 data –

6 GND Grounding

7 N/A -

8 GND Grounding

3.3 Communications Expansion Module NIM01C3


The communications expansion module is used for 4G communication. It provides
extra RS485/CAN ports for the SMU to connect to southbound communications
equipment.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 27


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Figure 3-6 Panel

(1) SIM card slots (2 PCS) (2) 4G indicator (3) Alarm indicator

(4) Running indicator (5) ANT antenna port (6) COM1 port

(7) COM2 port (8) COM3/CAN port (9) COM4 port

(10) Handle

Indicators

Table 3-8 Indicator description


Item Color Status Description

4G Green Steady on The dial-up connection is in


indicator the data service state.

Blinking at intervals of 2s A network has been


(on for 0.1s and then off registered.
for 1.9s)

Blinking at intervals of 2s Network search is in progress


(on for 0.1s, off for 0.1s, or no available network is
on for 0.1s, and then off found.
for 1.7s)

Alarm Red Off No alarm is generated.


indicator
Steady on An alarm is generated.

Running Green Off The board is not running


indicator because it is faulty or has no
DC input.

Blinking slowly (0.5 Hz) The board is running and


communicating with the host
properly.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 28


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Item Color Status Description

Blinking fast (4 Hz) The board is running properly,


but fails to communicate with
the host.

Communications Ports

Table 3-9 Communications port description

Communications Communications Description


Port Parameter

COM1 Baud rate: 9600 bit/s, Supports master/slave and


19200 bit/s, or 115200 Modbus protocols.
bit/s Supplies 12 V power.

COM2 Baud rate: 9600 bit/s, Supports master/slave and


19200 bit/s, or 115200 Modbus protocols.
bit/s Supplies 12 V power.

COM3/CAN Baud rate: 9600 bit/s COM3: Supports master/slave and


Modbus protocols.
CAN: Supports the CAN protocol.

COM4 Baud rate: 9600 bit/s, Supports the Modbus protocol.


19200 bit/s, or 115200
bit/s

Figure 3-7 Pins in the COM1, COM2, or COM3 port

Table 3-10 Pin definitions for the COM1 and COM2 ports

Pin Signal Description

1 RS485_RX+ Receive data over RS485.

2 RS485_RX-

3 12V Power supply

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 29


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Pin Signal Description

4 RS485_TX+ Transmit data over RS485.

5 RS485_TX-

6 Null -

7 Null -

8 GND Grounding

Table 3-11 Pin definitions for the COM3/CAN port


Pin Signal Description

1 RS485_RX+ Receive data over RS485.

2 RS485_RX-

3 Null -

4 RS485_TX+ Transmit data over RS485.

5 RS485_TX-

6 GND Grounding

7 CANH CAN bus high level

8 CANL CAN bus low level

Table 3-12 Pin definitions for the COM4 port


Pin Signal Description

R+ RS485+ RS485 data, positive

R- RS485- RS485 data, negative

3.4 Communications Expansion Module CIM02C


The module is used to provide extra RS485/CAN ports for the SMU and supply 12
V power to southbound devices.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 30


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Figure 3-8 Panel

(1) COM1 port (2) COM2 port (3) COM3 or COM4 port

(4) 12 V power port (5) COM5 port (6) Handle

Table 3-13 Communications port description


Communications Description Communications
Port Parameter

COM1 ● Supports RS485. Baud rate: 9600


● Supplies 12 V power. bit/s by default
● Connects to a smart device. Options: 9600
bit/s, 1200 bit/s,
COM2 ● Supports RS485. 2400 bit/s, 4800
● Supplies 12 V power. bit/s, 14400 bit/s,
19200 bit/s,
● Connects to a smart device. 115200 bit/s
COM3/COM4 COM3 supports RS485 and connects
to a smart device. When COM3 is
used to connect to outdoor devices,
reserve only the wires corresponding
to pins 1, 2, 4, and 5 to avoid surge
risks.
COM4 supports RS232 and CAN.
RS232 is used by default, which can
be changed to CAN by using a jumper.
For the operation method, see the
appendix. COM4 mainly connects
indoor smart devices. If it is connected
to outdoor smart devices, surge risks
may occur.

COM5 ● Supports RS485 and RS232. RS485


is used by default, which can be
changed to RS232 by using a
jumper. For the operation method,
see the appendix.
● Connects to an air conditioner.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 31


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Figure 3-9 Pin definitions for the COM1, COM2, COM3, or COM4 communication
port

Table 3-14 Pin definitions for the COM1 and COM2 ports
Pin Signal Description

1 RS485_RX+ Receive data over RS485.

2 RS485_RX-

3 12V Power supply

4 RS485_TX+ Transmit data over RS485.

5 RS485_TX-

6 Null -

7 Null -

8 GND Grounding

Table 3-15 Pin definitions for the COM3 and COM4 ports
Pin Signal Description

1 RS485_RX+ Receive data over RS485.

2 RS485_RX-

3 RS232_RXD Receives data over RS232.

4 RS485_TX+ Transmit data over RS485.

5 RS485_TX-

6 GND Grounding

7 CANH/RS232_TXD CAN data, positive/Transmits data over


RS232.

8 CANL CAN data, negative

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 32


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Table 3-16 COM5 communications port pin definitions

Silk Screen Signal Description

R+/TX RS485+/ RS485 data, positive/Transmits data


RS232_TXD over RS232.

R-/RX RS485-/ RS485 data, negative/Receives data


RS232_RXD over RS232.

GND GND Grounding

3.5 Rectifier
A rectifier converts AC input power into stable DC power.

Figure 3-10 Appearance

(1) Power indicator (2) Alarm indicator (3) Fault indicator

(4) Locking latch (5) Handle

Table 3-17 Indicator description

Indicator Color Status Description

Power Green Steady The rectifier has an AC input.


indicator on

Off The rectifier has no AC input.

The rectifier is faulty.

Blinking The rectifier is being queried.


at 0.5
Hz

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 33


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Indicator Color Status Description

Blinking The rectifier is loading an application


at 4 Hz program.

Alarm Yellow Off No alarm is generated.


indicator
Steady ● A warning is generated due to
on ambient overtemperature.
● The rectifier has generated a
protection shutdown alarm due to
ambient overtemperature or
undertemperature.

AC input overvoltage or undervoltage


protection has been triggered.

The rectifier is in hibernation state.

Blinking The communication between the


at 0.5 rectifier and the external device is
Hz interrupted.

Fault indicator Red Off The rectifier is normal.

Steady The rectifier locks out due to output


on overvoltage.

The rectifier has no output due to an


internal fault.

3.6 Digital Temperature and Humidity Sensor


A digital temperature and humidity sensor detects the indoor ambient
temperature and humidity in real time.

Figure 3-11 Appearance 1

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 34


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 3 Components

Figure 3-12 Appearance 2

DIP Switch
The following figure shows the DIP switch on a digital T/H sensor. The following
table describes the DIP switch settings.

Figure 3-13 DIP switch 1

Figure 3-14 DIP switch 2

Table 3-18 DIP switch settings


Toggle Toggle Toggle Toggle Toggle Toggle T/H
Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Switch 6 Sensor
Address

ON ON OFF OFF ON ON 51

OFF OFF ON OFF ON ON 52

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 35


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4 System Installation

4.1 Preparing for the Installation

4.1.1 Preparing Cables


The cross-sectional area of a power cable depends on the current that will flow
through the cable and the voltage drop allowed for the cable.

The cable cross-sectional areas listed are for reference only.

Table 4-1 Preparing cables for the ETP48400-C3B1 and ETP48400-C3B2

Cable Type Maximum Minimum Cross- Maximum Cross-


Current (A) Sectional Area Sectional Area
(mm2) (mm2)

AIU03B (three- Live wire 63 10 (cord end terminal 16 (bare wire)


phase with the with an insertion
neutral wire depth of 18 mm)
connected)
Neutral 63 16 (M6 OT terminal) 25 (bare wire)
wire

PE wire 63 16 (M6 OT terminal) 35 (bare wire)

AIU03C (three- Live wire 63 10 (cord end terminal 16 (bare wire)


phase with the L1 with an insertion
neutral wire depth of 18 mm)
connected or
disconnected) Live wire 63 10 (cord end terminal 16 (bare wire)
L2 with an insertion
depth of 18 mm)

Live wire 63 10 (cord end terminal 16 (bare wire)


L3 with an insertion
depth of 18 mm)

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 36


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Cable Type Maximum Minimum Cross- Maximum Cross-


Current (A) Sectional Area Sectional Area
(mm2) (mm2)

Neutral 63 10 (cord end terminal 16 (bare wire)


wire with an insertion
depth of 18 mm)

PE wire 63 16 (M6 OT terminal) 35 (M6 OT terminal)

AIU02 (single- Live wire 144 25 (M6 OT terminal) 35 (M6 OT terminal)


phase)
Neutral 144 25 (M6 OT terminal) 35 (M6 OT terminal)
wire

PE wire 90 16 (M6 OT terminal) 35 (M6 OT terminal)

AIU02 (dual-live Live wire 125 25 (cord end terminal 35 (cord end terminal
wire) L1 with an insertion with an insertion
depth of 18 mm) depth of 18 mm)

Live wire 125 25 (cord end terminal 35 (cord end terminal


L2 with an insertion with an insertion
depth of 18 mm) depth of 18 mm)

PE wire 90 16 (M6 OT terminal) 35 (M6 OT terminal)

DC output power - 16 1.5 16 (bare wire)


cable
- 32 4 16 (bare wire)

- 63 10 16 (bare wire)

- 80 10 35

- 100 16 35

- 125 25 35

Battery cable 350 35 (M6 OT terminal); 50 (M6 terminal with


2 PCS a width less than 16
mm); 2 PCS
NOTE
● The size data in the table is applicable when the ambient temperature is 30°C (in air) and only cables in a
single loop are involved.
● When the ambient temperature is not 30°C or cables in multiple loops are routed together, use cables with
larger cross-sectional areas if the cabling distance is long.
● Battery cables should be able to withstand a temperature of at least 90°C.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 37


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.1.2 Tools

NOTICE

Use tools with insulated handles. The following table is for reference only.

Table 4-2 Installation tools and instruments

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 38


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.1.3 Installation Dimensions


Figure 4-1 Installation dimensions for the ETP48400-C3B1 and ETP48400-C3B2

NOTE

48.3 mm indicates that the distance between a power subrack mounting ear and the front
of the subrack is about 48.3 mm.

Figure 4-2 Installation dimensions for an intelligent power distribution unit

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 39


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-3 Installation dimensions for a lead-acid battery box

4.2 Installing Devices


Procedure
Step 1 Install a subrack in a 19-inch rack.

Figure 4-4 Installing the ETP48400-C3B1 or ETP48400-C3B2 subrack

Step 2 Install an intelligent power distribution unit in the 19-inch rack.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 40


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-5 Installing an intelligent power distribution unit

Step 3 Install a lead-acid battery box in the 19-inch rack.

Figure 4-6 Installing a lead-acid battery box

----End

4.3 Installing Ground Cables

CAUTION

Ensure that the ground cables are installed securely. Inappropriate grounding may
cause device damage and personal injury.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 41


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-7 Installing a ground cable for the ETP48400-C3B1 or ETP48400-C3B2

(1) Ground bar

Figure 4-8 Installing a ground cable for the DCDB48-200-16B

(1) Ground bar

Figure 4-9 Installing a ground cable for the DCDB48-200-16B-XXX

(1) Ground bar

Figure 4-10 Installing a ground cable for the lead-acid battery box

(1) Ground bar

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 42


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.4 Installing a Rectifier


Prerequisites
● The rectifier is intact after being unpacked.
● The filler panel has been removed from the rectifier slot.

NOTICE

● If the rectifier is damaged, contact your local office.


● The rectifier slot presents a risk of electric shock. Do not touch the slot with
your hands.
● High temperature is generated around the air exhaust vent when the rectifier is
running. Do not touch the vent with your hands or cover the vent with cables
or other objects.
● In an outdoor scenario, you are advised to power on the module within 24
hours after unpacking. If the module cannot be powered on in time, place it in
a dry indoor environment without corrosive gas.
● In an indoor scenario, you are advised to power on the module within seven
days after unpacking. If the module cannot be powered on in time, place it in a
dry indoor environment without corrosive gas.

Procedure
Step 1 Push the locking latch towards the left.

Step 2 Draw the handle downwards.

Step 3 Gently push the rectifier into its slot along the guide rails.

Step 4 Push the handle upwards.

Step 5 Push the locking latch towards the right to secure the handle.

Figure 4-11 Installing a rectifier

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 43


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.5 Installing a Circuit Breaker


Prerequisites
If a circuit breaker is required, perform the following steps to install it.

Procedure
Step 1 Install a circuit breaker in the slot.
Step 2 Switch off the circuit breaker to be installed. (The view window turns green.)
Step 3 Push the circuit breaker so that it is aligned with the subrack.

Figure 4-12 Installing a circuit breaker

----End

4.6 Installing a Digital Temperature and Humidity


Sensor
Prerequisites
If a digital temperature and humidity sensor is required, perform the following
steps to install it.

Procedure
Step 1 Attach the digital temperature and humidity sensor to the side panel of the
cabinet.
NOTE

There is a magnet at the bottom of the digital temperature and humidity sensor, which can
be directly attached to the side panel of the cabinet.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 44


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-13 Installing a digital temperature and humidity sensor

Step 2 Connect the communications cable for the digital temperature and humidity
sensor to the COM port on the communications expansion module or UIM.
NOTE

The communications cables in the figures are connected to communications expansion


modules.

Figure 4-14 Installing a communications cable for a digital temperature and


humidity sensor

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 45


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-15 Installing communications cables for cascaded digital temperature


and humidity sensors

Step 3 Set the DIP address.

Table 4-3 DIP switch settings

Toggle Toggle Toggle Toggle Toggle Toggle Address of


Switch Switch Switch 3 Switch Switch Switch Digital
1 2 4 5 6 Temperature
and Humidity
Sensor

ON ON OFF OFF ON ON 51

OFF OFF ON OFF ON ON 52

----End

4.7 Installing a Communications Expansion Module


NIM01C3
Context
If an NIM01C3 is required, perform the following steps to install it.

Procedure
Step 1 Wear an ESD wrist strap or ESD gloves.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 46


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Step 2 Remove the filler panel from the slot for installing the communications expansion
module.
Step 3 (Optional) Install a SIM card in the communications expansion module.

NOTICE

This step is required if the NIM01C3 is used for 4G wireless networking.


The SIM card inserted into the communications expansion module (NIM01C3)
should support GSM, WCDMA, TD-SCDMA, TDD, and FDD standards, and have the
SMS and data service functions enabled.

Figure 4-16 Installing a SIM card

(1) SIM card

Step 4 Draw the handle rightwards.


Step 5 Gently insert the communications expansion module into its slot along the guide
rails.
Step 6 Push the handle leftwards and tighten the screws.

Figure 4-17 Installing a communications expansion module NIM01C3

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 47


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.8 Installing a Communications Expansion Module


CIM02C
Procedure
Step 1 Remove the filler panel from the slot for installing the communications expansion
module.
Step 2 Draw the handle rightwards.
Step 3 Gently insert the communications expansion module into its slot along the guide
rails.
Step 4 Push the handle leftwards and tighten the screws.

Figure 4-18 Installing a communications expansion module CIM02C

----End

4.9 (Optional) Installing Dry Contact Signal Cables


Procedure
Step 1 Press the contact plate using a flat-head screwdriver to flip the metal spring inside
each dry contact.
Step 2 Connect the signal cables to the corresponding dry contacts.
Step 3 Remove the flat-head screwdriver and check that the signal cables are connected
securely.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 48


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-19 Installing a dry contact signal cable

----End

4.10 (Optional) Installing Communications Cables

4.10.1 WebUI Management


Procedure
Step 1 Connect the FE port on the SMU by using a network cable.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 49


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-20 Connecting a communications cable (for WebUI management)

(1) WebUI terminal (2) FE port on the SMU

----End

4.10.2 Using the U2000-SPM for Management


Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end of the cable to the MON0 or MON1 port on Huawei BBU.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 50


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-21 Connecting a communications cable

(1) RS485/RS232 port on the SMU (2) MON1 port on Huawei BBU

----End

4.10.3 NetEco Management


Networking Mode 1: FE Port
Step 1 Connect the FE port on the SMU by using a network cable.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 51


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-22 Connecting a communications cable (over the FE port)

(1) NetEco terminal (2) FE port on the SMU

----End

Networking Mode 2: RS485 Port


Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end of the cable to the MON0 or MON1 port on Huawei BBU.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 52


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-23 Connecting a communications cable (over the RS485 port)

(1) RS485/RS232 port on the SMU (2) MON1 port on Huawei BBU

----End

4.10.4 Third-Party NMS Management (over SNMP)


Procedure
Step 1 Connect the FE port on the SMU by using a network cable.

Figure 4-24 Connecting a communications cable (for third-party NMS


management)

(1) SNMP-based NMS terminal (2) FE port on the SMU

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 53


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.11 Installing Sensor Cables

4.11.1 Installing Door Status Sensor Cables


Procedure
Step 1 Connect door status sensor cables to the GATE ports on the UIM.

Figure 4-25 Installing cables for a door status sensor

----End

4.11.2 Installing Battery Temperature Sensor Cables


Procedure
Step 1 Connect the battery temperature sensor cables to the BTEMP port on the UIM.

Figure 4-26 Installing battery temperature sensor cables

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 54


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.11.3 Installing Smoke Sensor Cables


Procedure
Step 1 ProcedureConnect smoke sensor cables to the SMOKE ports on the UIM.

Figure 4-27 Installing smoke sensor cables

----End

4.11.4 Installing a Water Sensor Cable


Procedure
Step 1 Connect the water sensor cable to the WATER ports on the UIM.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 55


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-28 Installing a water sensor cable

----End

4.12 Installing Cables

DANGER

● Ensure that the upstream AC input circuit breaker is in the OFF position, and
attach a warning label indicating "Do not operate."
● Switch all circuit breakers to OFF before installing cables.

NOTICE

● If cables are routed from the front of the power subrack, the minimum bending
radius of the cables is 80 mm.
● If cables are routed from the top of the power subrack, it is recommended that
2 U be reserved for cabling.
● If the preceding conditions are not met, you are advised to use super flexible
cables.

4.12.1 Installing DC Output Power Cables

Connecting DC Output Power Cables to 125 A Circuit Breakers


Step 1 Use cables (cross-sectional area: 10–35 mm2) and cord end terminals to prepare
DC output power cables.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 56


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Table 4-4 Preparing cables


Cross-Sectional Recommended Cord End Terminal Recommended Bare Wire
Area Specifications Specifications

10 mm2 Pre-insulated and with an insertion 25–35 mm2


depth of 18 mm NOTICE
Cord end terminals are recommended.
16 mm2 Pre-insulated and with an insertion When bare wires are used, you are
depth of 18 mm advised to add heat shrink tubing to
ensure that the wire ends are not split.
25 mm2 Pre-insulated and with an insertion
depth of 18 mm

35 mm2 Not pre-insulated; with an insertion


depth of 18 mm

Figure 4-29 Preparing a cord end terminal

(1) Cable (2) Cord end terminal (3) Crimping tool

Step 2 Install DC output power cables.


1. Loosen the screws for the DC output circuit breakers.
2. Connect DC output power cables to the corresponding DC output circuit
breakers.
3. Tighten the screws for the DC output circuit breakers.

NOTICE

Tighten the screws until they are flush with the thread, indicating that the
screws are fastened properly.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 57


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-30 Installing DC output power cables

(1) DC load

----End

Connecting DC Output Power Cables to 63 A Circuit Breakers


Step 1 Use cables (cross-sectional area: 1.5–16 mm2) and cord end terminals to prepare
DC output power cables.

Table 4-5 Preparing cables


Cross-Sectional Recommended Cord End Terminal Recommended Bare Wire
Area Specifications Specifications

1.5 mm2 Pre-insulated and with an insertion 16 mm2


depth of 18 mm NOTICE
Cord end terminals are
4 mm2 Pre-insulated and with an insertion recommended. When bare wires are
depth of 18 mm used, you are advised to add heat
shrink tubing to ensure that the wire
10 mm2 Pre-insulated and with an insertion ends are not split.
depth of 18 mm

16 mm2 Pre-insulated and with an insertion


depth of 18 mm (supports bare wire
installation)

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 58


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-31 Preparing a cord end terminal

(1) Cable (2) Cord end terminal (3) Crimping tool

Step 2 Install DC output power cables.


1. Insert a flat-head screwdriver (2 mm wide) into the holes for DC output
circuit breakers.
2. Connect DC output power cables to the corresponding DC output circuit
breakers.
3. Remove the flat-head screwdriver.

Figure 4-32 Installing DC output power cables

(1) DC load

----End

4.12.2 Installing a 220/380 V AC Three-Phase Four-Wire Input


Power Cable

Procedure
Step 1 Use cables (cross-sectional area: 10–16 mm2), cord end terminals, and OT
terminals to prepare an AC input power cable.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 59


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-33 Preparing a cord end terminal

(1) Cable (2) Cord end terminal (3) Crimping tool

Figure 4-34 Preparing an OT terminal

(1) Cable (2) OT terminal (3) Heat shrink tubing

(4) Hydraulic pliers (5) Heat gun

Step 2 Remove the protective cover from the N wiring position.


Step 3 Connect the AC input power cable to corresponding AC input circuit breakers.
Step 4 Reinstall the protective cover on the N wiring position.

Figure 4-35 Installing a 220/380 V AC three-phase four-wire input power cable

(1) Alternating current distribution box (ACDB)

----End

4.12.3 Installing 220 V AC Single-Phase Input Power Cables


Procedure
Step 1 Install a short-circuit copper bar and remove the protective cover from the short-
circuit copper bar.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 60


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-36 Installing a short-circuit copper bar

Step 2 Use cables (cross-sectional area: 10–35 mm2), cord end terminals, and OT
terminals to prepare AC input power cables.

Figure 4-37 Preparing an OT terminal

(1) Cable (2) OT terminal (3) Heat shrink tubing

(4) Hydraulic pliers (5) Heat gun

Step 3 Install AC input power cables.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 61


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-38 Installing 220 V AC single-phase input power cables

(1) AC distribution box

Step 4 Reinstall the protective cover for the short-circuit copper bar.

----End

4.12.4 Installing 120/240 V AC Dual–Live Wire Input Power


Cables
Procedure
Step 1 Use cables (cross-sectional area: 10–35 mm2) and cord end terminals to prepare
AC input power cables.

Figure 4-39 Preparing a cord end terminal

(1) Cable (2) Cord end terminal (3) Crimping tool

Step 2 Install AC input power cables.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 62


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-40 Installing AC input power cables

(1) ACDB

----End

4.12.5 Installing Cables for an Intelligent Power Distribution


Unit
NOTE

The methods for installing cables between the intelligent power distribution unit and other
power subracks are similar. The following uses one of them as an example.

Procedure
Step 1 Install power cables for the intelligent power distribution unit.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 63


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-41 Installing power cables for the DCDB48-200-16B intelligent power
distribution unit

Figure 4-42 Installing power cables for the DCDB48-200-16B-XXX intelligent


power distribution unit

Step 2 Install DC output power cables for the intelligent power distribution unit.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 64


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-43 Installing DC output power cables for the intelligent power
distribution unit

(1) DC load

Step 3 (Optional) Set the DIP address.


NOTE

When multiple intelligent power distribution units are cascaded, set the DIP address.

1. Remove the DMU02C1.

Figure 4-44 Removing the DMU02C1

2. Set the DIP address.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 65


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-45 DIP switch

Table 4-6 DIP switch description


Address of Intelligent Power Pin 1 Pin 2
Distribution Unit

1 OFF OFF

2 OFF ON

3 ON OFF

4 ON ON
NOTE
– If one contactor and one shunt are installed, for example, in a
DCDB48-200-16B-4731, set pin3 to OFF and pin4 to OFF.
– If two contactors and one shunt are installed, for example, in a
DCDB48-200-16B-4731-008, set pin3 to OFF and pin4 to ON.

3. Reinstall the DMU02C1.


Step 4 Install communications cables for the intelligent power distribution unit.

Figure 4-46 Installing a communications cable for one intelligent power


distribution unit

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 66


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-47 Installing communications cables for multiple intelligent power


distribution units

----End

4.12.6 Installing Cables for a Lead-Acid Battery Box


Prerequisites

DANGER

● Smoking and sources of ignition are prohibited near batteries.


● Switch off the battery circuit breakers before installing batteries.
● Comply with regulations and warnings issued by manufacturers.
● Use tools with insulated handles. Otherwise, batteries may burn out and cause
personal injury.
● Before handling batteries, wear goggles, rubber gloves, and protective clothes.
Remove all conductive objects, such as watches, bracelets, bangles, and rings.
● If battery acid gets in the eyes, rinse with cold water for more than 15 minutes
and seek medical advice immediately. If battery acid comes into contact with
skin or clothing, wash with soap and water immediately.
● Do not use metal or conductors to simultaneously touch two or more battery
terminals or touch battery terminals and grounded objects (for example, a
battery compartment); otherwise, transient short circuits occur, which may
produce sparks or explosions.
● During battery installation, ensure that the positive and negative battery
terminals are correctly connected to prevent reverse polarity. Connect the
negative battery cable and then the positive battery cable.
● Secure battery cables with a torque specified in battery documentation. Loose
connections will result in excessive voltage drops or cause batteries to burn out
when the current is high.
● The methods for installing cables between the lead-acid battery box and other
power subracks are similar. The following uses one type of cable as an example.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 67


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Procedure
Step 1 Install power cables for the lead-acid battery box.
NOTE

You can only connect one DCDB48-400-4C to the power subrack.

Figure 4-48 Installing power cables for the lead-acid battery box

Step 2 Switch off the battery circuit breakers.


Step 3 Install battery cables for the lead-acid battery box.
NOTE

You can only connect one battery string (or one battery cell) to a circuit breaker.

Figure 4-49 Installing battery cables for the lead-acid battery box

(1) Battery string

Step 4 Install a fuse detection cable for the lead-acid battery box.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 68


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-50 Installing a fuse detection cable for the lead-acid battery box

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 69


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

4.12.7 Installing Lithium Batteries and Cables

Prerequisites

DANGER

● Smoking and sources of ignition are prohibited near batteries.


● Switch off the battery circuit breakers before installing batteries.
● Comply with regulations and warnings issued by manufacturers.
● Use tools with insulated handles. Otherwise, batteries may burn out and cause
personal injury.
● Before handling batteries, wear goggles, rubber gloves, and protective clothes.
Remove all conductive objects, such as watches, bracelets, bangles, and rings.
● Do not use metal or conductors to simultaneously touch two or more battery
terminals or touch battery terminals and grounded objects (for example, a
battery compartment); otherwise, transient short circuits occur, which may
produce sparks or explosions.
● During battery installation, ensure that the positive and negative battery
terminals are correctly connected to prevent reverse polarity. Connect the
negative battery cable and then the positive battery cable.
● Secure battery cables with a torque specified in the battery documentation.
Loose connections will result in excessive voltage drops or cause batteries to
burn out when the current is high.
● Low temperature charging may cause short circuits inside the electrochemical
cell and explosion.
● Install lithium batteries in a dry, clean, and well-ventilated environment that is
free from sources of strong infrared radiation, organic solvents, and corrosive
gases. Do not expose lithium batteries to sunlight or water and keep them far
away from sources of ignition.
● Do not immerse battery cables in water. Do not place battery cables in places
that can be directly exposed to rain.
● Ambient humidity: ≤ 95% RH The IP rating of the outdoor cabinet is IPX4 or
higher.

NOTICE

● Before installing lithium batteries, ensure that the running indicator is off. Use
a multimeter to check that the lithium battery power port has no voltage.
● Install lithium batteries at the lower layer and then the upper layer.
● At least two persons are required to move a lithium battery.
● The following uses one battery as an example.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 70


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Procedure
Step 1 Install a lithium battery in a 19-inch rack.

Figure 4-51 Installing a lithium battery

Step 2 Install a ground cable for each lithium battery.

Figure 4-52 Installing a ground cable for a lithium battery

(1) Ground bar

Step 3 Install communications cables and a build-out resistor for lithium batteries.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 71


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 4 System Installation

Figure 4-53 Installing communications cables for lithium batteries

Step 4 Install lithium battery power cables.

Figure 4-54 Installing lithium battery power cables

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 72


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 5 Verifying the Installation

5 Verifying the Installation

5.1 Checking Hardware Installation


● Check that all screws, especially those used for electrical connections, are
secured. Check that flat washers and spring washers are installed properly.
● Check that rectifiers are completely inserted into their respective slots and
properly locked.

5.2 Checking Electrical Connections


● Check that all circuit breakers are OFF or all fuses are disconnected.
● Check that flat washers and spring washers are securely installed for all OT
terminals and that all the OT terminals are intact and properly connected.
● Check that batteries are correctly installed and that battery cables are
correctly connected, and not short circuits exist.
● Check that input and output power cables and ground cables are correctly
connected, and not short circuits exist.

5.3 Checking Cable Installation


● Check that all cables are securely connected.
● Check that all cables are arranged neatly and bound properly to their nearest
cable ties, and are not twisted or overly bent.
● Check that cable labels are properly and securely attached in the same
direction.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 73


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

6 Commissioning

NOTICE

● Performing commissioning procedure provided in this chapter may result in


power failure or alarms. Inform the alarm center before commencing the
procedure and after completing the procedure.
● Commissioning should be performed by trained personnel according to the
commissioning instructions provided in this chapter.
● Commissioning is performed with the power on. Before you perform
commissioning, remove any conductors such as jewelry or watches, stand on
dry insulating material, and use insulated tools.
● During commissioning, do not establish contact between electrical points that
have different electric currents.
● Check that the status of a unit or component meets requirements before
turning on its switch.
● If you are maintaining or servicing equipment and do not want others to
perform any operation, attach the label "Currently being serviced. Do not
switch on." to the equipment.
● During commissioning, shut down the power system immediately if any fault is
detected. Rectify the fault, start the power system, and proceed with the
commissioning.

6.1 Powering on Lead-Acid Batteries


Procedure
Step 1 Measure the voltage between battery strings. The value should range from –42 V
DC to –58 V DC.

Step 2 Switch the battery circuit breaker on the lead-acid battery box to ON.

Step 3 Press the battery switch for 2s to 5s. When you hear a sound from the contactor,
power-on is complete.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 74


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Step 4 Measure the voltage between the –48 V busbar and the RTN+ busbar. The value
should range from –42 V DC to –58 V DC.

----End

6.2 Connecting the Lithium Battery Supply

NOTICE

● After the monitoring module identifies the lithium battery, the monitoring
module restarts.
● After power-on, turn off the output of the lithium battery if the site is not in
use temporarily.

Procedure
Step 1 Switch on the lithium battery circuit breaker.
Step 2 Press the Manual ON/OFF button on the lithium battery to activate the lithium
battery.
Step 3 Press the switch for 2–5 seconds. The system is powered on when you hear a
sound from the contactor.
Step 4 Check whether the lithium batteries communicate properly. If the run indicator on
a lithium battery is steady on, the battery communicates properly with the
monitoring device. If it blinks fast (4 Hz), the communication between them is
interrupted. If so, check whether the communications cable is properly connected.
Step 5 Observe the lithium batteries for 15 minutes. The lithium batteries are running
properly if the alarm indicators are off.
Step 6 Set all circuit breakers to the appropriate status based on site requirements.
Step 7 Observe the power system for 15 minutes. If no alarm (except the door status
alarm) is generated on the SMU during this period, the current and voltage for
batteries and loads are normal.

----End

6.3 Setting the Display Language


After powering on the SMU, press or on the LCD to select a display

language. Then press to enter the standby screen.

NOTE

● If an undesired language is selected, reseat and restart the SMU and then select the
desired language.
● The preset password is 000001.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 75


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

6.4 Setting Deployment Wizard


After Setup Wizard Init is displayed on the LCD, set the following parameters.

Table 6-1 Parameter settings

Item Setting Value

Setting the time Set this parameter to the local time zone.
zone.

Set the date and Set this parameter to the local date and time.
time

Battery Set the parameters based on site conditions.


manufacturer NOTE

Battery model ● If the battery model is set to ESM-A, you do not need to set battery parameters
after the SMU restarts.
● If the battery model is set to lead-acid battery, perform the following steps to set
battery parameters after the SMU restarts:

The SMU may Yes


restart.

Battery 1 Yes/No
Connected NOTE
● If battery routes 1 and 2 are respectively connected to a battery string (a battery
Battery 2 string consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected
Connected and Battery 2 Connected to Yes and others to No, and set Single-String Cap. to
150 Ah.
Battery 3
● If battery route 1 is connected to two parallel battery strings (one battery string
Connected consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected to Yes
and others to No, and set Single-String Cap. to 300 Ah.
Battery 4
Connected

Single-String Cap. Rated capacity of each battery string


NOTE
A battery string includes a set of batteries controlled by one circuit breaker or fuse.

The SMU may Yes


restart.

6.5 Setting the Date and Time


NOTE

● The LCD screen becomes dark if no button is pressed within 30s.


● You need to log in again if no button is pressed within 1 minute.
● The preset password is 000001.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 76


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Set the date and time as required. Skip the setting if they have been correctly set
in the setup wizard.

Table 6-2 Setting the date and time

Main Menu Second-Level Third-Level Default Value Setting


Menu Menu

Setting Wizard Date and Time Zone UTC +08:00 Beijing Set this parameter to the
Time local time zone.
NOTE
Date and - Set this parameter to the
The date and
time vary Time local date and time.
with time
zones. Set the NTP Enable No Yes/No
time zone, NOTE
date, and Set the parameter to Yes if
time based you need to synchronize the
on the local SMU time and the site
situation. network server time.

6.6 Setting the AC Input System


Set the AC input system based on site requirements.

Table 6-3 Setting the AC input system

Main Menu Second-Level Third-Level Setting Value


Menu Menu

Parameters Mains AC Mode Set to the ● 2-Phase


Settings local power 2-Wire
supply ● 1-Phase
system.
● 3-Phase
4-Wire

6.7 Setting the 57 V Constant Voltage Parameter


Set the 57 V constant voltage parameter based on site requirements.

Table 6-4 Setting the 57 V constant voltage parameter

Main Menu Second-Level Third-Level Fourth-Level Setting Value


Menu Menu Menu

Parameters Li Battery Basic Work Mode 57V Mode ● 57V Mode


Settings Parameters ● 48V Mode

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 77


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

6.8 Setting DCDB Parameters


Set DCDB parameters based on site requirements.

Table 6-5 Setting DCDB parameters

Main Menu Second-Level Third-Level Fourth-Level Menu Value


Menu Menu

Parameters DC Power DMU LLVD n Enabled Enable/ Disable


Settings
LLVD n Mode Voltage Mode/ Time
Mode

LLVD n Voltage 36.0-56.0 V

LLVD n Recon Volt 37.0-58.0 V

LLVD n Time 0–6000 min

LLVD Delay Time 5-90s

6.9 Setting AC Peak Clipping Parameters


Set peak shaving parameters based on site requirements.

Table 6-6 Setting peak shaving parameters

Main Second Third- Fourth-Level Menu Setting Description


Menu -Level Level
Menu Menu

Parameters AC Peak AC Mains Peak Shave Enable or disable the peaking


Settings Shaving parameters Enb shaving function. When the mains
capacity or circuit breaker capacity is
insufficient, you are advised to
enable the peak shaving function.

Cap for Peak Shave ● If the input transformer power is


insufficient, set this parameter to
the transformer power (unit: kW).
● If the input transformer power is
sufficient, keep the default value.

Breaker Rated Curr ● If the circuit breaker capacity is


insufficient, set this parameter to
the circuit breaker capacity (unit:
A).
● If the circuit breaker capacity is
sufficient, keep the default value.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 78


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Main Second Third- Fourth-Level Menu Setting Description


Menu -Level Level
Menu Menu

Derating Coef Indicates the high temperature


derating coefficient of the circuit
breaker. Keep the default value (0.8)
unless otherwise specified.

Peak Rated Phase Volt Set the parameter based on the


Shaving rated voltage of the power grid.
Para Default value: 220 V.

Peak Shaving SOC If power failure occurs, reserve the


battery capacity for peak shaving.
Peak Shaving SOC
(Mix.)

Power-On By default, this parameter does not


Hysteresis for LLVD need to be set.
in Peak Shaving

Batt Backup Enable Indicates whether the peak shaving


battery is used as the backup battery
in the case of power failure. Default
value: No.

Allow A/C Indicates whether the air conditioner


Shutdown in Peak can be turned off during peak
Shaving shaving. You are advised to disable
this function.

Allow LLVD n Indicates whether to power off the


Disconnection in minor loads when the battery
Peak Shaving capacity reserved for peak shaving is
fully discharged.

6.10 Setting Sensor Parameters


Set sensor parameters based on site requirements.

Table 6-7 Setting sensor parameters


Main Menu Second-Level Third-Level Fourth-Level Settings
Menu Menu Menu

Parameters Setup Parameter Sensor Config Door Sensor Yes, No


Settings NOTE
Water Sensor Set these parameters to
Yes or No as required.
Smoke Sensor

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 79


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Main Menu Second-Level Third-Level Fourth-Level Settings


Menu Menu Menu

Batt. Temp.
Sensor

Temp1 Sensor

6.11 Setting the Mains Collection Channel


Procedure
Step 1 On the WebUI, set the mains collection channel.

Figure 6-1 Setting the mains collection channel

----End

6.12 Setting Communications Parameters

6.12.1 (Optional) Setting Parameters for WebUI Management

Operating Environment
Operating system: Windows XP or later

Browser: Internet Explorer 8.0 or later, Firefox 13 or later, or Chrome 20

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 80


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

NOTE

Internet Explorer is used as an example to illustrate all WebUI operations mentioned in this
document.

Configuring the LAN

NOTICE

● If the SMU is connected to a local area network (LAN) and a proxy server has
been selected, cancel the proxy server settings.
● If the SMU is connected to the Internet but your computer is connected to a
LAN, do not cancel the proxy server settings. Otherwise, you cannot access the
SMU.

To cancel the proxy server settings on the PC, perform the following steps:

Step 1 Open Internet Explorer.


Step 2 Choose Tools > Internet Options.
Step 3 Click the Connections tab and click LAN settings.
Step 4 Deselect Use a proxy server for your LAN.

Figure 6-2 Canceling proxy server settings 1

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 81


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Figure 6-3 Canceling proxy server settings 2

Step 5 Click OK.

----End

Configuring Internet Explorer Security Settings

NOTICE

Configure Internet Explorer security setting before you perform the following
operations.
● Export historical logs, historical data, statistics, and battery test records.
● Upload system configuration files.
● Download system configuration files.
● Upgrade the software.

To modify Internet Explorer security settings, perform the following steps:

Step 1 Open Internet Explorer.


Step 2 Choose Tools > Internet Options.
Step 3 Click the Security tab.
Step 4 Click Internet and then Custom level. After you specify Internet security settings,
click Local intranet and then Custom level.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 82


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Figure 6-4 Internet Explorer security

Step 5 Specify the security settings.


Enable the following functions:
● Initialize and script ActiveX controls not marked as safe for scripting.
● Allow previously unused ActiveX controls to run without prompt.
● Include local directory path when uploading files to a server.
● Enable automatic prompting for file downloads.

Figure 6-5 Internet Explorer security setting 1

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 83


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Figure 6-6 Internet Explorer security setting 2

Figure 6-7 Internet Explorer security setting 3

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 84


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Figure 6-8 Internet Explorer security setting 4

Step 6 Click OK.

Step 7 Click the Advanced tab and select Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2.

Figure 6-9 Internet Explorer security setting 5

Step 8 Click OK.

----End

Setting SMU Parameters


Step 1 Apply for a fixed IP address to the site or equipment room network administrator.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 85


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Step 2 Set the IP address, subnet mask, and gateway address on the SMU LCD.

Table 6-8 IP parameters


Main Second-Level Third-Level Default Value Setting
Menu Menu Menu

Setting Network IP Address [Link] Set this parameter according to


Wizard Parameters the address information
provided by the network
administrator.

Subnet Mask [Link] Set this parameter according to


the address information
provided by the network
administrator.

Default Gateway [Link] Set this parameter according to


the address information
provided by the network
administrator.

----End

Logging In to the WebUI


Step 1 Set the laptop IP address to be in the same network segment as the SMU IP
address.
For example, if the SMU has an IP address of [Link], a subnet mask of
[Link], and a default gateway of [Link], set the IP address to
[Link], subnet mask to [Link], and default gateway to [Link]
on the PC.
Step 2 Enter [Link] IP address (such as [Link] in the address
box of the browser, and then press Enter to enter the WebUI login page.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 86


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Figure 6-10 WebUI login page

NOTE

The preset user names include admin, engineer, and operator, and the preset password is
Changeme. The user names are respectively used by administrators, engineers, and
operators.
Change the preset password upon your first login to ensure the system security.

----End

6.12.2 (Optional) Setting Parameters Before Using U2000-


SPM
Context

NOTICE

If a Huawei BBU is deployed, set the Northbound and M/S Protocol parameters.

Procedure
Step 1 Set the port mode, communications protocol type, baud rate, and communications
address on the SMU's LCD.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 87


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Table 6-9 Communications parameters

Main Second- Third- Fourth-Level Fifth-Level Default Settings


Menu Level Menu Level Menu Menu Value
Menu

Parameters Comm. Serial Port Northbound Port Mode Manual Manual


Settings Parameters
Protocol Type M/S M/S
NOTE Protocol Protocol
Protocol Type is
displayed only
when Port
Mode is set to
Manual.

M/S Baud Rate - 9600 9600


Protocol
Comm. - 3 3
Address

----End

6.12.3 (Optional) Setting Parameters Before Using NetEco

Networking Mode 1: FE Port


Step 1 Apply to the site or equipment room network administrator for a fixed IP address.

Step 2 Set the IP address, subnet mask, and gateway on the SMU's LCD.

Table 6-10 IP parameters

Main Second-Level Third-Level Default Value Settings


Menu Menu Menu

Setting Network IP Address [Link] Set this parameter


Wizard Parameters according to the IP address
assigned by the network
administrator.

Subnet Mask [Link] Set this parameter


according to the subnet
mask provided by the
network administrator.

Default [Link] Set this parameter


Gateway according to the gateway
address provided by the
network administrator.

Step 3 Set the IP Addresses and Ports for the active servers of the NetEco on the SMU's
LCD.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 88


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Table 6-11 NetEco parameters


Main Menu Second-Level Third-Level Fourth-Level Default Settings
Menu Menu Menu Value

Parameters Comm. Network NetEco [Link] Set an IP


Settings Parameters Parameters Primary IP address for the
active NetEco
server.

NetEco Port 31220 Set a port for


Number the NetEco.

----End

Networking Mode 2: RS485 Port


Step 1 Set Port Mode to Manual, Protocol Type to M/S Protocol, Baud Rate to 9600,
and Comm. Address to 3.

Table 6-12 Communications parameters


Main Second- Third- Fourth-Level Fifth-Level Default Settings
Menu Level Level Menu Menu Value
Menu Menu

Parameters Comm. Serial Northbound Port Mode Automatic Manual


Settings Parameters Port
Protocol Type M/S M/S
NOTE Protocol Protocol
This parameter is
displayed only
when Port Mode
is set to Manual.

M/S Baud Rate - 9600 9600


Protocol
Comm. - 3 3
Address

----End

6.12.4 (Optional) Setting Parameters Before Using SNMP


Management
Prerequisites
NOTE

You can set SNMP parameters remotely or locally on the WebUI.

Before setting SNMP parameters, obtain the information listed in Table 6-13 from
the SNMP-based NMS.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 89


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Table 6-13 Information obtained from the NMS


Information Description

SNMP Version SNMP version and port number used for communication between the
SMU and NMS. The SNMP version can be SNMPv1, SNMPv2c, or
SNMP Port Number SNMPv3.

Read Community If you use SNMPv1 or SNMPv2c, enter the read and write community
Name names that comply with the NMS. Otherwise, the SMU will not connect
to the NMS.
Write Community
Name The read community name must be different from the write community
name.

User Name To enhance the security, you need a user name and password for
authentication if you use SNMPv3. After the authentication succeeds, the
MD5/SHA Password SMU can communicate with the NMS.
DES/AES Password

Trap Target Address IP address and port number used for reporting alarm trap packets.

Trap Port

Trap Community If you use SNMPv1 or SNMPv2c, this parameter is the community name
used for reporting alarm trap packets.

NOTE

● The standard protocols SNMPv1 and SNMPv2 have security risks. You are advised to use
the secure protocol SNMPv3.
● The standard encryption algorithms MD5 and DES have security risks. You are advised
to use the secure encryption algorithms SHA and AES.

Procedure
Step 1 Log in to the WebUI.
NOTE

The preset user name is admin, and the preset password is Changeme.

Step 2 Access the System Settings page and set SNMP.


● There are two NMSs and the SNMP versions are SNMPv1 or SNMPv2c and
SNMPv3: Set SNMP Version in SNMP to ALL, set SNMP Port, Read
Community Name, and Write Community Name, then click Add in
SNMPv3, set User Name, MD5/SHA Password, and DES/AES Password, and
click Confirm.
● SNMPv1 or SNMPv2c: Set SNMP Version in SNMP to SNMPv1&SNMPv2c,
set SNMP Port, Read Community Name, and Write Community Name, and
click Confirm.
● SNMPv3: Set SNMP Version in SNMP to SNMPv3, click Add in SNMPv3, set
User Name, MD5/SHA Password, and DES/AES Password, and click
Confirm.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 90


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 6 Commissioning

Step 3 Click Add in SNMP Trap.


● If SNMP Version is set to SNMPv1 or SNMPv2c, set Trap Target Address,
Trap Port, and Trap Community.
● If SNMP Version is set to SNMPv3, set Trap Target Address, Trap Port, and
SNMPv3 User Name.
NOTE

The SNMP version here can be different from the version in Step 2.

Step 4 In Mib files, click Export to export the Mib file and then import it into the NMS.
NOTE

If there is only one NMS, perform Step 4 once only.

----End

6.13 Connecting the AC Power Supply


Procedure
Step 1 Switch on the AC input circuit breaker and measure the output voltage of the AC
input circuit breaker. The value should range from 85 V AC to 300 V AC.
Step 2 Check that the RUN indicator on the rectifier is steady on.
Step 3 Set all circuit breakers to the appropriate status based on site requirements.
Step 4 Observe the power system for 15 minutes. If no alarm (except the door status
alarm) is generated on the SMU during this period, the current and voltage for
batteries and loads are normal.

----End

6.14 Subsequent Operations


Procedure
Step 1 Reinstall the removed panels (if any).
Step 2 The subrack surface paint should be intact. If paint peels off, repair the paint to
prevent corrosion.
Step 3 Clean the site and leave there.

----End

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 91


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

7 Maintenance

7.1 Routine Maintenance


Perform routine maintenance based on site requirements. The recommended
maintenance interval is six months. If any fault occurs, rectify it in a timely
manner.

NOTICE

Do not maintain devices on raining days, preventing water from entering and
damaging devices.

7.1.1 AC and DC Power Distribution


Table 7-1 AC and DC power distribution maintenance
No. Maintenance Item If... Then...

1 Check for AC input ● AC input power cables 1. Replace AC input power


undervoltage. have a large voltage cables with shorter or
drop. thicker cables.
● AC input power cables 2. Connect AC input power
are in poor contact. cables securely.
● The mains voltage is too 3. Provide the voltage data
low. to the power supplier.

2 Check for AC input The mains voltage is too Provide the voltage data to
overvoltage. high. the power supplier.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 92


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

No. Maintenance Item If... Then...

3 Check whether the AC input ● AC input power cables 1. Check and rectify the
voltage is open-phase. are in poor contact, cables.
short-circuited, or 2. Provide the open-phase
damaged. data to the power
● The mains supply has supplier.
failed.

4 Check whether a DC output ● Load overcurrent occurs. Rectify any overcurrent or


circuit breaker is OFF and a ● Load short-circuit short circuit. Turn on the
fuse is blown. occurs. circuit breaker or replace
the fuse.

5 Check for DC busbar A rectifier is abnormal. Replace the abnormal


overvoltage. rectifier.

6 Check for DC busbar ● The AC power supply 1. Resume the AC power


undervoltage. has failed. supply.
● The system is 2. Check the load status
overloaded. and rectify faults if any.
● A rectifier is abnormal. 3. Replace the abnormal
rectifier.

7.1.2 Rectifier
Table 7-2 Rectifier maintenance
No. Maintenance Item Possible Fault Cause Suggestion

1 Check the green indicator Off: 1. Check the rectifier AC


status (normal: steady on). ● There is no AC input. input.
● The rectifier is faulty. 2. Replace the rectifier.

2 Check the yellow indicator Steady on: 1. Check the ambient


status (normal: off). ● Because the ambient temperature status, and
temperature is high, the clean the cabinet air
rectifier power is limited. channel.
● Because the ambient 2. Rectify faults in the
temperature exceeds the indoor temperature
upper or lower threshold, control system.
the rectifier shuts down 3. Check the AC input
for protection. voltage.
● AC input over/ 4. The rectifier is in
undervoltage protection hibernation. No action is
is triggered. required.
● The rectifier is in
hibernation.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 93


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

No. Maintenance Item Possible Fault Cause Suggestion

Blinking: 1. Check that the rectifier


● The rectifier communications cable is
communication has failed securely connected.
● The rectifier is faulty. 2. Replace the rectifier.

3 Check the red indicator Steady on: 1. Check that the cabinet is
status (normal: off). ● The rectifier is latched off not connected to an
due to output external DC power source
overvoltage. that has a voltage of
greater than 58.5 V DC.
● The rectifier is faulty.
2. Check that the rectifier
output voltage is within
58.5 V DC.
3. Replace the rectifier.

7.1.3 Monitoring Unit


Table 7-3 SMU maintenance
No. Maintenance Possible Cause Suggestion
Item

1 Check the green ● Off: There is no DC 1. Check that the DC input power cable is
indicator status. input. securely connected.
● Off: The SMU is faulty. 2. Check that the communications cable
is securely connected.
3. Replace the SMU.

2 Check the yellow ● Steady on: A minor 1. Check related components based on
indicator status. alarm or warning is alarms.
generated. 2. Replace the SMU.
● Steady on: The SMU is
faulty.

3 Check the red ● Steady on: A critical or 1. Check related components based on
indicator status. major alarm is alarms.
generated. 2. Replace the SMU.
● Steady on: The SMU is
faulty.

4 Check the LCD ● The LCD cable is loose. 1. Check that the LCD cable is securely
display status. ● The SMU is faulty. connected.
2. Replace the SMU.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 94


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

No. Maintenance Possible Cause Suggestion


Item

5 Check that the ● The communications 1. Check that the communications cable
SMU can cable is loose. is securely connected.
communicate ● Networking parameters 2. Check that networking parameters are
with the NMS. are not correctly set. correctly set.

7.1.4 Parameters on the SMU


Table 7-4 SMU parameter maintenance
No. Maintenance Item Possible Fault Cause Suggestion

1 Check whether the ● Parameters are set Set battery parameters


displayed battery capacity incorrectly. again.
and number of battery ● The number of batteries
strings are the same as the is changed, or batteries
actual data. are replaced.

2 Check Charge Current N/A Change the value as


Limit Coefficient. The required. Otherwise, retain
value is typically 0.15C10 0.15C10.
and adjustable.

3 Check whether the ● The battery temperature 1. Replace the battery


displayed battery sensor is faulty. temperature sensor.
temperature is the same as ● The SMU is faulty. 2. Replace the SMU.
the actual temperature.

4 Check whether the ● Battery current detection 1. Check that the current
displayed total load current fault. monitoring cable is
is the same as the actual ● The SMU is faulty. securely connected.
current measured by a 2. Replace the SMU.
clamp meter.

5 Check whether the ● The current monitoring 1. Check that the current
displayed battery charge cable is loose. monitoring cable is
current is the same as the ● The SMU is faulty. securely connected.
actual current measured by 2. Replace the SMU.
a clamp meter.

6 Check whether the ● The cabinet busbar and 1. Check and secure the
difference between the cables are loose or in cabinet busbar and cable
displayed DC output poor contact. connections.
voltage and the measured ● The SMU is faulty. 2. Replace the SMU.
DC busbar voltage is less
than 0.5 V DC.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 95


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

7.1.5 Cables
Table 7-5 Cable maintenance
No. Maintenance Item Possible Fault Cause Suggestion

1 Check whether signal Cables are not properly Bind signal cables and
cables and power cables installed. power cables separately.
are separately bound.

2 Check whether all cables Cables are not properly Bind cables properly.
are bound properly. installed.

3 Check whether the cabinet Cables are not properly Connect the cabinet ground
ground bar is securely installed. bar to the site or equipment
connected to the site or room ground point.
equipment room ground
point.

4 Check whether ground Cables corrode after being Replace rusty cables.
cables are rusty. used for a long time.

5 Check whether cables have ● Cables are too thin. ● Replace the cables with
overheated and are ● Cables are not properly cables of the required
deteriorating. routed. thickness.
● Route the cables properly.

6 Check whether the cable ● Cables are too thin. ● Replace the cables.
near the output port of the ● Cables are not properly ● Reinstall the cables (strip
circuit breaker is installed. the cables for 18 mm)
overheated. and ensure that the
cables are securely
connected.

7 Check whether copper Cables are not properly ● Use standard terminals.
wires are exposed at the installed. ● Insulate exposed copper
circuit breaker wiring wires.
terminals.

8 Check whether cables are Cables are not properly Replace the cables and
misshapen by metal parts. installed. adjust the cable routing.

9 Check whether cables pass Cables are not properly Adjust the cable routing to
behind the air exhaust installed. prevent cable overheating.
vents of rectifiers.

10 Check whether cable Cable insulation is damaged. Reinsulate the cables with
insulation is damaged. insulation tape.

7.2 Identifying Component Faults

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 96


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

7.2.1 Identifying SMU Faults


The following lists the SMU faults:
● The DC output is normal but the green indicator on the SMU is off.
● The SMU breaks down or cannot be started. Its LCD has abnormal display or
buttons cannot be operated.
● With alarm reporting enabled, the SMU does not report alarms when the
power system is faulty.
● The SMU reports an alarm whereas the power system does not experience the
fault.
● The SMU fails to communicate with the connected lower-level devices even
though the communications cables are correctly connected.
● Communication between the SMU and all rectifiers fails even though the
rectifiers and the communications cables are normal.
● The SMU cannot monitor AC or DC power distribution when communications
cables are intact and AC and DC power distribution is normal.
● Parameters cannot be set or running information cannot be viewed on the
SMU.

7.2.2 Identifying Rectifier Faults


The following lists the rectifier faults
● The AC input and slot connector are normal, but the Fault indicator (red) is
steady on or all indicators are off.
● The slot connector and SMU are normal, but the Alarm indicator (yellow) still
blinks after the rectifier is reinstalled.
● The AC input and SMU are normal, but the SMU cannot control the rectifier.

7.2.3 Identifying Circuit Breaker Faults


If the load fuse is blown, it indicates that the circuit breaker trips. If the circuit
breaker is switched on and the downstream device is still not powered (the busbar
has power), the circuit breaker is faulty and needs to be replaced.

7.2.4 Locating AC Input Module Faults


The following lists the AC input module faults:
● The AC surge protector is faulty.
● Under normal AC power supply, if the rectifier has no output after the circuit
breaker is switched on (the upstream has power), the circuit breaker is faulty.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 97


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

7.3 Replacing Components

NOTICE

● Ensure that loads are supplied with power when replacing major components.
For example, keep the switches for primary loads in the ON position, and do
not turn off the battery switch and AC input switch at the same time.
● Seek the customer's prior consent if load disconnection is required.
● Rectifiers and the SMU are hot-swappable.

7.3.1 Replacing an SMU02C

Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new SMU is intact.

Procedure
Step 1 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and
ESD gloves.
NOTE

Record the software version of the old SMU. If the old SMU is damaged and version
information cannot be viewed, send the bar codes of the old SMU and cabinet to technical
support engineers.

Step 2 Disconnect the communications cable from the SMU02C panel and record the
cable information.

Step 3 Push the locking latch leftwards.

Step 4 Pull the handle outwards and remove the SMU02C from the subrack.

Figure 7-1 Removing the SMU02C

Step 5 Remove the SD card from the side of the SMU02C.


NOTE

If no SD card is installed, go to Step 7.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 98


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Step 6 Insert the SD card into the new SMU02C.

Step 7 Place the new SMU02C in the slot, push the locking latch leftwards, and pull out
the handle.

Step 8 Gently push the SMU02C along the guide rails until it is engaged. Close the
handle, and push the locking latch rightwards.

Figure 7-2 Installing the SMU02C

Step 9 Reconnect the communications cable to the SMU02C panel based on the recorded
information.

Step 10 Set SMU02C parameters.


NOTE

After installing the new SMU, power on the SMU and check the software version of the
new SMU. If the software version of the new SMU is earlier than that of the old SMU,
upgrade the software.

Step 11 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Put the removed component in an ESD box or bag and return it to the local
warehouse.

7.3.2 Replacing a UIM05B1

Prerequisites
● The ESD wrist strap, ESD gloves, ESD box or bag, and toolbox are available.
● The new UIM05B1 is intact.

Procedure
Step 1 Connect the ESD wrist strap ground cable, and wear the ESD wrist strap and ESD
gloves.

Step 2 Record the connection positions of cables on the UIM05B1 panel and remove the
cables.

Step 3 Loosen the screws on the UIM05B1 panel, pull the handle until it is engaged, and
take out the UIM05B1.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 99


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Figure 7-3 Removing the UIM05B1

Step 4 Install the new UIM05B1.


Step 5 Install the cables based on the recorded information.
Step 6 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Put the replaced component in an ESD box or bag and return it to the local
warehouse.

7.3.3 Replacing an NIM01C3


Prerequisites
● An ESD wrist strap, ESD gloves, an ESD box or bag, a cabinet door key, and
required tools are available.
● The new NIM01C3 is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.
Step 2 Record all cable connection positions on the communications expansion module
and disconnect the cables.
Step 3 Loosen the screws on both sides of the communications expansion module.
Step 4 Pull the handle rightwards and remove the communications expansion module.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 100


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Figure 7-4 Removing a communications expansion module

Step 5 Remove the SIM card from the SIM card slot, and insert the new communications
expansion module. Skip this step if no SIM card is installed.
Step 6 Place the new NIM01C3 in the corresponding slot of the monitoring unit subrack,
and push the NIM01C3 until its front panel is flush with the front panel of the
monitoring unit subrack.
Step 7 Push the handle inwards until it is engaged, and then tighten the screws.

Figure 7-5 Installing a communications expansion module

Step 8 Reconnect cables to the panel of the new communications expansion module
based on the recorded information.
Step 9 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Put the replaced component in an ESD box or bag and return it to the local
warehouse.

7.3.4 Replacing a CIM02C


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 101


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

● The new CIM02C is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.

Step 2 Note where cables are connected to the CIM02C panel. Record these positions and
disconnect the cables.

Step 3 Loosen the screws on both sides of the CIM02C panel.

Step 4 Pull the handle rightwards and take out the CIM02C.

Figure 7-6 Removing the CIM02C

Step 5 Place the new CIM02C into the correct slot in the subrack, and push the CIM02C
until its front panel is flush with the front panel of the subrack.

Step 6 Push the handle inwards until it is engaged, and then tighten the screws.

Figure 7-7 Installing the CIM02C

Step 7 Reconnect the cables to the new CIM02C panel based on the information you
recorded.

Step 8 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Put the replaced component in an ESD box or bag and return it to the local
warehouse.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 102


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

7.3.5 Replacing a DMU02C1


Prerequisites
● The protective gloves and cabinet door key are available.
● The new DMU02C1 is intact.

CAUTION

● Do not remove the DMU02C1 that is loaded. Otherwise, it may be


damaged.
● To prevent burns, exercise caution when removing a DMU02C1 because it
may be hot as a result of continuous operation.

Procedure
Step 1 Put on the protective gloves.
Step 2 Note where cables are connected to the DMU02C1 panel. Record these positions
and disconnect the cables.
Step 3 Remove the old DMU02C1.

Figure 7-8 Removing the old DMU02C1

Step 4 Record the DIP address on the old DMU02C1.

Figure 7-9 DIP switch

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 103


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Step 5 Install the new DMU02C1.


1. Set the DIP switch on the new DMU02C1 based on the DIP switch settings on
the old DMU02C1 to ensure consistency.
2. Install the DMU02C1.

Figure 7-10 Installing the new DMU02C1

Step 6 Reconnect the cables based on the information you recorded.


Step 7 Remove the protective gloves.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

7.3.6 Replacing a Rectifier


Prerequisites
● You have obtained a pair of protective gloves and the cabinet door key.
● The new rectifier is intact.

CAUTION

Protect yourself from being burnt when moving the rectifier because the rectifier
has a high temperature.

Procedure
Step 1 Put on protective gloves.
Step 2 Push the locking latch at the right side of the panel towards the left.
Step 3 Gently draw the handle outwards, and then remove the rectifier from the subrack.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 104


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Figure 7-11 Removing a rectifier

Step 4 Push the locking latch on the new rectifier towards the left, and pull out the
handle.
Step 5 Place the new rectifier at the entry to the correct slot.
Step 6 Gently slide the converter into the slot along guide rails until it is engaged. Close
the handle, and push the locking latch towards the right to lock the handle.

Figure 7-12 Installing a rectifier

Step 7 Take off protective gloves.

----End

Follow-up Procedure
Pack the removed component, and return it to local warehouse.

7.3.7 Replacing a Circuit Breaker


Prerequisites
● You have obtained the toolbox.
● The new circuit breaker is intact.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 105


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

NOTICE

● Power off the system before replacing a circuit breaker. Do not operate
with power on.
● Power-off will disconnect power supply to loads. Obtain prior consent from
customers before replacing a circuit breaker.

Procedure
Step 1 Switch off the circuit breaker to be replaced.

Step 2 Record the connection positions of cables, remove the cables, and insulate them.

Step 3 Push the faulty circuit breaker along the guide rails and pull it out horizontally.

Figure 7-13 Removing a circuit breaker

Step 4 Put the new circuit breaker to the slot and push it along the guide rails until it is
in position.

Step 5 Connect cables to the circuit breaker based on the recorded cable information.

Step 6 Switch on the circuit breaker.

----End

Follow-up Procedure
Pack the removed components and send them to the local Huawei warehouse.

7.3.8 Replacing an AC Input Module

Prerequisites
The required tools are available and the new AC input module is intact.

NOTICE

● Power off the AC input module before replacing it.


● Power-off will cause load devices to be shut down. Before replacing the AC
input module, obtain the customer's approval.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 106


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Procedure
Step 1 Switch off the circuit breaker on the AC input module.

Step 2 Record the installation positions of cables, remove the cables and insulate them.

Step 3 Remove the AC input module.

Figure 7-14 Removing the AC input module

Step 4 Install the new AC input module.

Step 5 Install the AC input power cables based on the recorded information.

Step 6 Switch on the AC input module.

----End

Follow-up Procedure
Pack the removed parts and send it to the local Huawei warehouse.

7.3.9 Replacing a Digital Temperature and Humidity Sensor

Prerequisites
● Tools and the key to the cabinet door are available.
● The new digital temperature and humidity sensor is intact.

Procedure
Step 1 Record cable information and installation positions.

Step 2 Record the DIP switch settings.

Step 3 Disconnect the cable from the communications port on the sensor.

Step 4 Remove the faulty sensor.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 107


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual 7 Maintenance

Figure 7-15 Removing a sensor

Step 5 Set the DIP switch of the new sensor based on the recorded information.
Step 6 Install a new sensor.
Step 7 Connect cables based on the recorded information.

----End

Follow-up Procedure
Pack the removed component and send it to the local warehouse.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 108


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual A How Do I Install a Hall Effect Sensor?

A How Do I Install a Hall Effect Sensor?

NOTICE

When installing the hall effect sensor, ensure that the direction of current is the
same as that of the arrow on the hall effect sensor.

Figure A-1 Installing a Hall effect sensor 1

Figure A-2 Installing a Hall effect sensor 2

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 109


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual B Technical Specifications

B Technical Specifications

Table B-1 Technical specifications


Category Item Specifications

Environment Operating temperature –40°C to +65°C (When the


conditions ambient temperature is between
–33°C and +55°C, the power
system works properly. When the
ambient temperature is greater
than 55°C and less than or equal
to 65°C, the output power is
linearly derated to 80%. When
the ambient temperature is –
40°C, the power system can start
properly after AC power is
applied.)

Transportation –40°C to +70°C


temperature

Storage temperature –40°C to +70°C

Operating humidity 5%–95% RH (non-condensing)

Storage humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m
When the altitude ranges from
2000 m to 4000 m, the operating
temperature decreases by 1°C for
each additional 200 m.

Noise System audible noise: ≤ 60 dBA


at 25°C, ≤ 72 dBA at 40°C; meets
class 3.1 requirements of ETSI
300753.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 110


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual B Technical Specifications

Category Item Specifications

Others There is no conductive dust,


corrosive gas, or explosion
hazard.
Dust, corrosive substances, pests,
molds, and other indicators
should be controlled in
accordance with class 3.1
requirements in ETSI EN 300
019-1-3 (V2.3.2 or a later
version).

AC input Input frequency 45–66 Hz; rated frequency: 50


Hz/60 Hz

Power factor ≥ 0.99 (rated input voltage, 50%–


100% load)

DC output Output voltage –53.5 V DC

Maximum output power ● ETP48400-C3B1: 24 kW


● ETP48400-C3B2: 18 kW

Regulated voltage ≤ ±1%


precision

Peak-to-peak noise ≤ 200 mV (0–20 MHz)


voltage

Psophometrically ≤ 2 mV
weighted noise voltage

Unbalance of load ≤ ±5% (50%–100% load)


sharing

AC input AC input overvoltage ≥ 300 V AC


protection protection threshold

AC input overvoltage 290–300 V AC


recovery threshold

AC input undervoltage ≤ 80 V AC
protection threshold

AC input undervoltage 80–90 V AC


recovery threshold

DC output DC output overvoltage –56 V DC to –60.5 V DC (default:


protection protection threshold 59.5 V DC)

EMC Conducted emission ● AC port: EN 55032, Class B


specifications ● DC port: EN 55032, Class A1
● Signal port: EN 55032, Class B

Radiated interference EN 55032, Class B

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 111


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual B Technical Specifications

Category Item Specifications

Harmonic current IEC 61000-3-12

Voltage flicker and IEC 61000-3-11


fluctuation

Electrostatic discharge IEC 61000-4-2


(ESD)

Electrical fast transient IEC 61000-4-4


(EFT)

Radiated susceptibility IEC 61000-4-3


(RS)

Conducted susceptibility IEC 61000-4-6


(CS)

Surge susceptibility IEC 61000-4-5

Voltage dip IEC 61000-4-11

Others MTBF 200,000 hours (at 25°C)

Structure Dimensions (H x W x D) ETP48400-C3B1/ETP48400-C3B2:


130 mm x 482 mm x 330 mm

Weight ≤ 20 kg (excluding rectifiers)

IP rating IP20

Installation mode Installed in a 19-inch rack

Cabling mode Routed in and out from the front

Maintenance mode Maintained from the front

Heat dissipation mode Free cooling

NOTE

1. This is a class A product and may cause radio interference in residential areas. Therefore,
you may need to take adequate safety measures to prevent radio interference.

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 112


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual C Electrical Conceptual Diagrams

C Electrical Conceptual Diagrams

Figure C-1 ETP48400-C3B1 electrical conceptual diagram

Figure C-2 ETP48400-C3B2 electrical conceptual diagram

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 113


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power D Associations Between UIM Dry Contacts and
User Manual Alarms

D Associations Between UIM Dry


Contacts and Alarms

Table D-1 Associations between dry contacts and alarms


Port Type Silk Screen Associated Alarm

Dry contact input DIN4 Dry contact input 4

Dry contact output DIN1/ALM1 AC failure


Default setting Long-time AC failure (disabled by
(closed: alarm; default)
open: normal). The
setting can be DIN2/ALM2 Busbar overvoltage
modified. Busbar ultra overvoltage
NOTE Busbar undervoltage
The DIN/ALM1-3 is a
multiplexing port. Busbar ultra undervoltage
Lithium battery discharge

DIN3/ALM3 Single-rectifier fault – redundancy


(disabled by default)
Single-rectifier fault – non-
redundancy (disabled by default)
Multi-rectifier fault
All-rectifier communication failure
Rectifier fault
Rectifier protection
Communication failure

ALM4 AC SPD fault


DC SPD fault

ALM5 Load fuse blown


Battery fuse blown

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 114


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power D Associations Between UIM Dry Contacts and
User Manual Alarms

Port Type Silk Screen Associated Alarm

ALM6 High battery temperature


Very high battery temperature
Low battery temperature
Very low battery temperature
High ambient temperature
Very high ambient temperature
Low ambient temperature

ALM7 Door status alarm

ALM8 Power cabinet temperature


control:
Fan 1 fault, fan 2 fault, fan 3
fault, high temperature of the
return air vent
When an external direct
ventilation battery cabinet or a
heat exchanger cabinet is used:
Air outlet overtemperature, air
outlet undertemperature, air inlet
overtemperature, air inlet
undertemperature, return air vent
overtemperature, return air vent
undertemperature, EXTFAN1 fault,
EXTFAN2 fault, INFAN1 fault,
INFAN2 fault, INFAN3 fault,
INFAN4 fault, TEC air conditioner
fault
When an external PC300D or air
conditioner is used:
High air conditioner temperature,
air conditioner internal fan fault,
air conditioner external fan fault,
air conditioner compressor fault,
communication failure

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 115


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power E How Do I Change the Communications Protocol
User Manual for COM4 and COM5?

E How Do I Change the Communications


Protocol for COM4 and COM5?

● To use CAN for communication through the COM4 port:


Take out the CIM02C, remove the jumper caps from pins 1 and 2 in the J18
position shown in Figure E-1, and insert the jumper caps into pins 2 and 3.
● To use RS232 for communication through the COM5 port:
Take out the CIM02C, remove the jumper caps from pins 1 and 2 in the J16
and J17 positions shown in Figure E-1, and insert the jumper caps into pins 2
and 3.

Figure E-1 COM4 and COM5 port jumper positions

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 116


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power E How Do I Change the Communications Protocol
User Manual for COM4 and COM5?

Figure E-2 Jumper connection rules for the COM4 and COM5 ports

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 117


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual F Acronyms and Abbreviations

F Acronyms and Abbreviations

E
EFT electrical fast transient
EMC electromagnetic compatibility
ESD electrostatic discharge

H
HTTPS Hypertext Transfer Protocol Secure

I
IP Internet Protocol

L
LCD liquid crystal display

M
MTBF mean time between failures

R
RS radiated susceptibility

S
SMU site monitoring unit
SNMP Simple Network Management
Protocol
SPD surge protection device

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 118


ETP48400-C3B1 and ETP48400-C3B2 Embedded
Power
User Manual F Acronyms and Abbreviations

THD total harmonic distortion

U
UIM user interface module

Issue 07 (2022-06-28) Copyright © Huawei Technologies Co., Ltd. 119