Air Circuit Breaker: 2010-2011 Catalogue (EN)
Air Circuit Breaker: 2010-2011 Catalogue (EN)
Catalogue (EN)
EN B03
CHINT Electrics
CHINT Electric
CHINT Low-voltage Electrical Products
Zhejiang CHINT Electrics Co., Ltd, the business unit of CHINT for Low-voltage
Electrical Products, is a nationwide leader in power distribution and industrial
control industry and is one of the core businesses of CHINT Group. The product
lines cover low-voltage electrical products of circuit breakers, contactors,
pushbuttons, switches, transformers, relays, capacitors, motor starters, etc.
The company adopts an ERP system by SAP and automatic warehouse guarantee
just-in-time operations and lead-time. Many of CHINT Low-voltage electrical
products have been certified under important international certificates such as
CE, DNV, AENOR, KEMA, ASTA, VDE, TÜV, SEMKO, FIMKO, CCC, EK, ESC, SNI,
UKrSEPRO, GOST, RCC, SLSI, SAA, UL, CSA, etc. Exquisitely manufactured and
strictly tested, CHINT Low-voltage Electrical Products will meet your various
demands for industrial, commercial, and residential applications on reliable
operations and considerate before & after-sale services.
Chint products are certified
by the following
international certificates:
EU
Norway
DNV
Spain
Netherlands
K
RTE
UK
TE
IN
A A
Germany
Germany
TUV
Sweden
Finland
China
Korea
Czech
Indonesia
Ukraine
Russia
South Africa
Sri Lanka
Australia
C R US LISTED USA
Canada
Air Circuit Breaker
NA1
Summary Page 01
Installation Page 25
connecting bus-bar
correction
Accessories Page 58
and solutions
NA1-2000
630A to 2000A
Summary
5 basic frame sizes
For your various requirements, the Air Circuit Breaker NA1
includes 5 basic frame sizes as followed.
NA1-3200, 4000
2000A to 4000A
NA1-6300
4000A to 6300A
EU
Netherlands
Ukraine
Russia
South Africa
> >> 01
Air Circuit Breaker
NA1
11
7
12 8
13
14
15
3
02 > >>
Air Circuit Breaker
NA1
1 Drawout type
2 Fixed type
3 Intelligent controller
4 Operating mechanism
5 Auxiliary contact
9
6 Locking-device
10 7 Arcing chamber
11 Shunt release
12 Closing electromagnet
13 Under-voltage release
15 Rotary handle
16 Fixed plate
2
16
6
> >> 03
Air Circuit Breaker
NA1
1. General 2.6 Type designation
1.1 Application scope NA1 - □-□□ / □-□-□-□-□
NA1 series air circuit breaker is suitable for the circuit of
AC 50Hz/60Hz with rated service voltage 400V, 690V and Voltage of secondary circuit
rated service current up to 6300A. It is mainly used to AC220V, AC380V
distribute electric energy and protect circuits and electric DC220V, DC110V
equipment against over-load, under-voltage, short-circuit
and single-phase earthing fault.
With intelligentized and selective protection functions, the Wiring of main circuit:
breaker can improve the reliability of power supply, and avoid H:Horizontal wiring of main circuit
unnecessary power failure. The breaker is applicable for power V:Vertical wiring of main circuit
stations, factories, mines (for 690V) and modern high-buildings,
especially for the distribution system of intelligentized building. Mode of installation:
1.2 Standard: IEC/EN 60947-2. F:Fixed type
D:Draweout type
Frame size
Rated current
rated current
200A
400A
1000A 630A
800A
1000A
630A
800A
1000A
2000A
1250A
1600A
2000A
2000A
3200A
2500A
4000A
3200A
4000A 4000A
4000A
6300A 5000A
6300A
ACB
Company code
04 > >>
Air Circuit Breaker
NA1
3. Structure
+ =
Body
Drawer seat
Drawout type breaker/switch-disconnector
Closing electromagnet
Breaking/making page 58
Name plate
indicator
Auxiliary contact
page 59
Motor-driven energy
Structure for in storage mechanism
and out Locking device page 59
Rotary handle page 60
> >> 05
Air Circuit Breaker
NA1
4. Main technical parameter
Type NA1-1000
Rated ultimate short circuit breaking capacity Icu=42kA 400V 25kA 690V
Rated service short circuit breaking capacity Ics=30kA 400V 20kA 690V
Rated short-time withstand current Icw=30kA 1s 400V 20kA 1s 690V
Rated current In (A) 200 400 630 800 1000
Number of poles 3, 4
Rated voltage Ue (V) 400
Rated insulation voltage Ui (V) 690
Rated current of N-pole In (A) 50%In
Fixed disconnection time (ms) 23~32
Intelligent Standard type (M)
controller Communication type (H)
Electric life 5000
Operation
Non-maintenance 10,000
performance Mechanical life
Maintenance 20,000
Connection pattern Horizontal, Vertical
Motor operational Drawout 3P/4P 38/55
standard configuration
weight (kg) Fixed 3P/4P 22/26.5
Standard configuration: M type intelligent controller; Under-voltage release; Shunt release; Motor-driven energy-storage mechanism
Type NA1-2000
Rated ultimate short circuit breaking capacity Icu=80kA 400V 50kA 690V
Rated service short circuit breaking capacity Ics=50kA 400V 40kA 690V
Rated short-time withstand current Icw=50kA 1s 400V 40kA 1s 690V
Rated current In (A) 630 800 1000 1250 1600 2000
Number of poles 3, 4
Rated voltage Ue (V) 400, 690
Rated insulation voltage Ui (V) 1000
Rated current of N-pole In (A) 50%In
Fixed disconnection time (ms) 23~32
06 > >>
Air Circuit Breaker
NA1
Rated ultimate short circuit breaking capacity Icu=80kA 400V 65kA 690V
Rated service short circuit breaking capacity Ics=65kA 400V 65kA 690V
Rated short-time withstand current Icw=65kA 1s 400V 50kA 1s 690V
Rated current In (A) 2000 2500 3200 4000
Number of poles 3, 4 3
Rated voltage Ue (V) 400, 690
Rated insulation voltage Ui (V) 1000
Rated current of N-pole In (A) 100%In
Fixed disconnection time (ms) 23~32
Standard configuration: M type intelligent controller; Under-voltage release; Shunt release; Motor-driven energy-storage mechanism
Type NA1-6300
Rated ultimate short circuit breaking capacity Icu=120kA 400V 85kA 690V
Rated service short circuit breaking capacity Ics=100kA 400V 75kA 690V
Rated short-time withstand current Icw=100kA 1s 400V 75kA 1s 690V
rated current In (A) 4000 5000 6300
Number of poles 3, 4 3
Rated voltage Ue (V) 400, 690
Rated insulation voltage Ui (V) 1000
Rated current of N-pole In (A) 100%In
Fixed disconnection time (ms) 23~32
> >> 07
Air Circuit Breaker
NA1
5. Dimensions and connection
NA1-1000 Drawout-type
268
N 226
H
362
8×φ5
101.5
316
304
358
Installation panel
5
91.5
16
Disconnected
L1 45 position Installation hole on right side
105 158
L 65
A 323
N 27 Connected position
70 70 70
12
200,400A n×φ13
35
NA1-1000 L1 L
12
15
35
3P 194 284
18
630 50 6/8 8
2-11.5×8.5
800, 1000 50 6/8 10
L1(3P)
L1(4P)
NA1-1000 Fixed-type
268
H
N 226
315
259
101.5
8×φ5
312
270
Installation panel
46.5
216 15 A 9
N 239
3
15
35 53
n×φ10.5
12
18
630,800,
1000A NA1-1000 L1 L In(A) A(mm) n(3P/4P) H(mm)
12
4-9×13
800, 1000 50 6/8 10
L1
08 > >>
Air Circuit Breaker
NA1
NA1-2000 Drawout-type
45(Disconnected position)
448(4P)
8-Φ13
a 353(3P) 60
N pole 28
37.5
a
14
95 95 95 92.5
112
258
439
horizontal connection
42.5
37
92
In A a mm
70
630 10
23
10 97 175
187.5 800~1600 15
421
2000 20
292
465
375(3P)
470(4P)
21.5
155
Φ11
302
268
302
360(4P)
265(3P)
378
N pole
47 20
115
2-11×17
40
Φ14
17
172 32-Φ13 28
55
4-φ13
28
60
258
439
122.5
42.5
95.5
70
10
37
10 97 175 187.5
14
292
55 375(3P)
438.5
470(4P)
21.5
In A a mm
155
Φ11 630 10
302
268
302 800~1600 15
378
360(4P)
2000 20
265(3P)
47 20
2-11×17
Φ14
C Direction
172 N pole a
55
> >> 09
Air Circuit Breaker
NA1
448(4P)
45(Disconnected position) 353(3P)
C Direction
258
439
122.5
42.5
95.5
37
70
187.5
10 97 175 292
375(3P)
438.5 470(4P)
In A a mm
21.5
630 10
800~1600 15
155
2000 20
Φ11
302
268
360(4P)
302
378
265(3P)
C Direction
47 20
2-11×17
60
Φ14
14
N pole 28 8-φ13
172
55
55
11-Φ5 Installation panel
175
10
33 344 Right & outer
187.5 side of breaker 95 95 95 92.5
Right & outer side of breaker
NA1-2000 Fixed-type
18min 413(4P)
Zero arcing covering
ferreous material 318(3P)
292
In A a mm
a 630 10
115
800 ~1600 15
402
2000 20
a
112
258
8-Φ13
60
N pole 28
55
21
42
60
17
50 150 69.5
11 11
13
290 181
359 345(3P) 95 95 95 86
435(4P)
Horizontal
N Pole
311.2
269
115
4-Φ12
40
300
17
28.5
150
32-Φ13 28
Installation
Installation hole
panel 60
8-φ5 on Right & outer side 2
of breaker
340(3P) Installation hole 342.2 95 95 95
435(4P) on Right & outer side Vertical
of breaker Opening hole on panel
10 > >>
Air Circuit Breaker
NA1
NA1-3200 Drawout-type
528(4P)
45(Disconnected position)
413(3P) In A a mm
a 2000~2500 20
3200 30
a
16-Φ13
258
439
100
25
N pole 50
112
42.5
37
100
92
70
50
217.5
23
10 97 175 92.5
115 125 125
352
491
435(3P)
536 Horizontal
550(4P)
21.5
155
302
268
Φ11
362
378
N pole
440(4P)
115
325(3P)
47 20
40
2-11×17
17
Φ14
32-Φ13 40
202
55
528(4P)
45(Disconnected position)
413(3P)
C Direction
8-φ13
50
258
439
126
42.5
100
100
70
37
10 97 175 20 217.5
40 352
435(3P)
94
495 550(4P)
21.5
In A a mm
2000~2500 20
155
3200 30
302
268
Φ11
362
440(4P)
378
C Direction
325(3P)
N pole
47 20
2-11×17 a
Φ14
202
55
> >> 11
Air Circuit Breaker
NA1
528(4P)
45(Disconnected position)
413(3P)
C Direction
258
439
112
42.5
107.5
70
37
10 97 175
217.5
352
495 435(3P)
550(4P)
21.5
In A a mm
155 2000~2500 20
3200 30
302
268
Φ11
362
440(4P)
378
325(3P)
47 20
2-11×17 C Direction
Φ14
20
100
40
N pole 50
202
55
94
175
33 404 Right & outer
Right & outer side of breaker 217.5 side of breaker 16-Φ13
NA1-3200 Fixed-type
a In A a mm
2000~2500 20
115
3200 30
402
a
112
258
16-Φ13
55
86
15
N pole 40
21
72
60
50 150 69.5
11 11
40
13
290 211
389 400(3P)
115 115 115 96
515(4P)
Horizontal
N pole
311
269
115
4-Φ12
40
362
15
28.5
150
32-Φ13 40
Installation hole on 86
8-φ5 Right & outer side of breaker 2 Installation panel
400(3P) 115 115 115
Installation hole on 404
515(4P) Right & outer side of breaker
Opening hole on panel Vertical
12 > >>
Air Circuit Breaker
NA1
15
Zero arcing covering 40
ferreous material 10
134
15
40
130
30
189.5 189.5 79
Horizontal
402
258
112
21
55
130
11 11
150 69.5
13
50
290 515
424
479
175
40
17
311
269
4-Φ12
362 50
24-Φ15
150
28.5
140
8-φ5 2 Installation panel
207.5 207.5
404 Installation hole on
Installation hole on Right & outer side of breaker
515
Right & outer side of breaker Vertical
Opening hole on panel
45(Disconnected position)
528
30
258
439
112
42.5
92
70
37
10 97 175
217.5
494 352
550
21.5
20
155
Φ11
40
302
268
103
362
378
440
20
12-Φ13
2-11×17
50
47
Φ14
140
202
55
> >> 13
Air Circuit Breaker
NA1
756
45(Disconnected position)
C Direction
20
439
258
112
42.5
70
92
10 97 175
37
187.5
292
490
788
21.5
155
Φ11
302
268
C Direction
302
378
678
16-φ13
20
N Pole 155
40
20
2-11×17
47
Φ14
103
172
55
813(3P)
30
258
439
42.5
112
37
70
92
217.5
10 97 175 352
835(3P)
494
928(4P)
21.5
155
302
268
Φ11 362
378
818(4P)
N Pole 28-Φ15
703(3P)
20
2-11×17
47
Φ14
40
103
202
11-Φ5 Opening hole on panel
55
175 404
33 Right & outer
217.5 side of breaker
Right & outer side of breaker 55
199.5 247 247 170.5
Opening hole on panel
14 > >>
Air Circuit Breaker
NA1
45(Disconnected position)
903
30
258
439
112
42.5
37
92
70
10 97 175
217.5
494 352
928
21.5
155
Φ11
180 260
302
268
20
362
378
818
40
103
20
2-11×17
47
Φ14
24-Φ15
202 80
55
> >> 15
Air Circuit Breaker
NA1
6. Secondary circuit wiring
6.1 NA1-1000 Standard type, type (M)
▲
3 5 7 9 14 15 17 19 21 23 25 27 29 31 33 35 37 39 XT
FU
Intelligent Q F X M
controller
Power of
DF1 DF2 DF3 control circuit
SA DF4
TA
FU
1 2 4 6 8 10 11 12 13 16 18 20 22 24 26 28 30 32 34 36 38 40 XT
DC24V
+ -
Power
module
# #
Hl1: Failure indicator 8 ,9 : Making indicator (capacity AC400V,1A)
HL2: Close indicator 10#: Over-current pre-alarm signal output (selective)
HL3: Energy storage indicator 11#: Short current trip signal output (selective)
SB1: Under-voltage button 12#: Earthing trip alarm output (selective)
SB2: Shunt button 13#: Self-checking alarm signal output (selective)
SB3: Close button 14#: Common line of different contacts
Q: Under-voltage release 15#: Earthing protection line
F: Shunt release # #
16 ,17 : Normal contact of the controller
X: Close electromagnet (contact capacity AC400V 1A)
M: Energy storage motor 27#,28#: Under-voltage release
DF1-F4: Auxiliary switch 29#,30#: Shunt release
1#, 2#: Auxiliary power input(DC24V) 31#,32#: Closing electromagnet
3#,4#,5#: Fault trip contact output(4# common terminal, 33#,34#,35#: Energy storage motor
contact capacity AC230V,5A 18#~26#, 36#~38#: Auxiliary contact
6#,7#: To be connected with current transformer(selective) (auxiliary contact capacity: AC230V,5A)
Note:
Dashed is to be connected by users.
16 > >>
Air Circuit Breaker
NA1
L1 FU
N
PE
Profibus-DP L N PE
Fault indicator 1 2 3 4 5 6 7 8 9 10 11
+ + D11D12 D13
DC24V COM
Green ST201 SB1 SB2 SB3
D01 D02 D03
HL1 HL2 12 13 14 15 16 17
▲
Red
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 XT
Intelligent Q F X M
controller
SA
TA
1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 XT
DC24V
+ -
Power
module
Note:
Dashed is to be connected by users.
> >> 17
Air Circuit Breaker
NA1
▲
3 5 7 9 14 15 17 19 21 23 25 27 29 31 33 35 37 39 XT
FU
Q F X M
Intelligent Power of
controller control circuit
DF5 DF6 DF1 DF2 DF3
SA DF4
TA
FU
1 2 4 6 8 10 11 12 13 16 18 20 22 24 26 28 30 32 34 36 38 40 XT
+ -
DC24V Power
module
Note:
6NO(normal open) 6NC(normal close), without any additional function.
Dashed is to be connected by users.
18 > >>
Air Circuit Breaker
NA1
6.2 NA1-2000~3600
The secondary circuit wiring for NA1-2000~3600 with standard type (M) intelligent controller and instantaneous under-voltage release
Emergency
Main circuit Over-current release break
Motor-driven Motor-driven
make
Auxiliary contact
break
SB2
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 36 38 40 42 44 46 48 50
FU
Q F X M
SA
AX
Power
Processing
unit
Intelligent Controller
FU
1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 37 39 41 43 45 47 49 51
Open Close
_ 110V
~
_ 220V Intelligent release power ("1" connect positive pole, and "2" connect negative pole for direct current)
~
~380V
> >> 19
Air Circuit Breaker
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3M) intelligent controller and instantaneous under-voltage release
1 2
L1
N
PE
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
Q F X
AX
M
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Energy-
Fault storage Open Close
The auxiliary contact modes for customer use SB1: Shunt button
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence) Ⅱ Five switch contact
SB3: Making button
# #
36 38 40 42 44 46 36 38 40 42 44 46 48 50 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
# #
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
# #
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
# #
of the DC power supply module, and the 1 ~2 connect to
37 39 41 43 45 47 37 39 41 43 45 4 7 49 the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.
# #
12 ~19 : The programmable output terminal. The normal products without these terminals,
but if the customer special ordered, the cost extra added.
# # # #
16 ,17 : Self-diagnose alarm; 18 ,19 : Fault trip
# # #
20 : PE line; 21 ~24 : Display the voltage of the signal input.
The normal products without these terminals,
if the customer special ordered the function meter, the cost extra added.
#
21 : N phase input terminal
22 # ,23 # ,24 # : A, B, C three phase power input terminal (note the sequence)
25 # ,26 # : Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
( If the voltage exceeds 400V, special explanation when ordered)
20 > >>
Air Circuit Breaker
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3H) intelligent controller and instantaneous under-voltage release
1 2
L1
N
PE
To TO3 busbar 1 2 3 4 5
ST Power Supply
L N L N PE Modular IV
Profibus-DP - + - + -+ - +
ST-DP 12 13 14 15 16 17 18 19
Device + - + -
1 2 3 4 5 6 7 8 9 10 11
Special connecting wire
D11D12D13
To the inconnecting-line side DO24VDO24VCOM
Modbus-RTV PE Un U1 U2 U3 SB2 SB1 SB3 ST201
DO1 DO3
Transformer 12 13 14 15 16 17 18 19
connected
Red Green
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
Q F X
AX
M
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Energy
Fault
storage Open Close
The auxiliary contact modes for customer use SB1: Shunt button
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence) Ⅱ Five switch contact
SB3: Making button
# #
36 38 40 42 44 46 36 38 40 42 44 46 48 5 0 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
is AC power, the 1#~2# connects to the AC power directly.
When the power supply is DC power, forbid connecting the
1#~2# to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
37 39 4 1 43 45 47 37 39 41 4 3 4 5 47 49
of the DC power supply module, and the 1#~2# connect to
the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.
# #
12 ,13 : Signal alarm of load 1 output
# #
14 ,15 : Signal alarm of load2 output
# #
16 ,17 :Breaking signal output
# #
18 ,19 :Making signal output
# #
20 : PE line; 21 : N phase input terminal
# # #
22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence)
25#26#: Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
ST~DP: DP protocol module. There is no need for the ST-DP protocol module,
if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP,
the ST-DP protocol module is necessary, but the cost extra added.
ST power module IV: power converter (optional components)
ST201: Magnify the signal capacity of the controller. ( optional components) If the customer special ordered,
the cost extra added.
Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
(If the voltage exceeds 400V, special explanation when ordered)
> >> 21
Air Circuit Breaker
NA1
The secondary circuit wiring for NA1-2000~6300 with standard type (M) intelligent controller and time-delay under-voltage release
Failure Under-voltage
time-delay controller
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 36 38 40 42 44 46 48 50
FU
AX
Power
Processing
unit
Intelligent controller
FU
1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 37 39 41 43 45 47 49 51
Open Close
~_ 110V
Intelligent release power(”1” connect positive pole, and “2” connect negative pole for direct current)
~_ 220V
~380V
38 40 4 2 44 46 4 8 50
39 4 1 43 45 47 49
22 > >>
Air Circuit Breaker
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3M) intelligent controller and time-delay under-voltage release
1 2
L1
N
PE
Transformer
Under-voltage
connected time-delay controller
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
F X Q
AX
M
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Energy
Fault storage Open Close
Energy- Energy-
Main Shunt Closing Under-voltage
circuit
Intelligent controller Emergency release electromagnet
storage storage time-delay
release
Auxiliary switch
break indication motor
12#~19# are the programmable output terminal. The normal products without these terminals,
but if the customer special ordered, the cost extra added.
Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2. (If the voltage exceeds 400V,
special explanation when ordered)
> >> 23
Air Circuit Breaker
NA1
The secondary circuit wiring for NA1-2000~6300 with type (3H) intelligent controller and time-delay under-voltage release
1 2
L1
N
PE
To TO3 busbar 1 2 3 4 5
STPower Supply
L N L N PE Modular IV
Profibus-DP - + - + - + - +
ST-DP 12 13 14 15 16 17 18 19
+ -
1 2 3 4 5 6 7 8 9 10 11
Device D11D12D13
SB2 SB1 SB3 DO24VDO24VCOM
Special connecting wire
ST201
To the inconnecting-line side DO1 DO3
Modbus-RTV PE Un U1 U2 U3 12 13 14 15 16 17 18 19
Transformer
Under-voltage
connected
Red Green time-delay controller
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
F X Q
AX
M
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Fault Energy
storage Open Close
The auxiliary contact modes for customer use SB1: Shunt button
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence)
SB3: Making button
# #
38 40 42 44 46 48 50 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
# #
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
# #
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
# #
of the DC power supply module, and the 1 ~2 connect to
39 41 43 45 47 49
the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.
12#,13#: Signal alarm of load 1 output
14#,15# : Signal alarm of load 2 output
16#,17#: Breaking signal output; 18#,19#: Closing signal output
20#: PE line; 21#: N phase input terminal
22#,23#,24#: A, B, C three phase power input terminal (note the sequence)
25#,26# Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
ST~DP: DP protocol module. There is no need for the ST-DP protocol module,
if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP,
the ST-DP protocol module is necessary, but the cost extra added.
ST power module IV: power converter (optional components)
ST201: Magnify the signal capacity of the controller. ( optional components)
If the customer special ordered, the cost extra added.
Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
(If the voltage exceeds 400V, special explanation when ordered)
24 > >>
Air Circuit Breaker
NA1
7. Installation
7.1 Installation
7.1.1 Unload the breaker from the soleplate of package. When the guide rod points to separated position and handle
If it is drawout type, firstly pull out the handle under can't be rotated any longer, pull out the handle and firmly
the drawer-base of breaker, and plug it into the hole grasp the aluminum handle on drawer-base, pull out the
on central part of plastic cover under the drawer-base breaker body and remove it form the base, then move the
crossbeam, anticlockwise turns the handle, the body base from the sole plate and clean up the dirty things inside
will slowly slide along the outside of drawer-base. the drawer-base.
Possible positions
7.1.2 Check the insulation resistance with a 500V megger, 7.1.3 Power supply
resistance should not be less than 20M Ω when NA1 devices can be supplied either from the top or
ambient temperature is 20 ℃± 5 ℃ and relative from the bottom without reduction in performance,
humidity is 50%~70%. Otherwise dry it. in order to facilitate connection when installed in a
switchboard.
> >> 25
Air Circuit Breaker
NA1
7.1.4 Put the breaker (fixed-type) or drawer-base (drawout-type) Mounting the circuit-breaker
into the installation-bracket, and make it fixed, directly It is important to distribute the weight of the device
connect the cable wire of main circuit to the bus wire of uniformily over a rigid mounting surface such as rails
fixed-type circuit breaker. Alternatively put breaker body or a base plate.
onto the slideway of drawer-base. Plug the handle into This mounting plane should be perfectly flat (tolerance
installation hole, clockwise turns it until the under-part of on support flatness: 2 mm).This eliminates any risk of
drawer-base points at the connection position and ”click” deformation which could interfere with correct
sound is heard. It indicates that breaker body has been operation of the circuit breaker.
connected to its place, then connect the cable of main NA1 devices can also be mounted on a vertical plane
circuit to drawer-base. using the special brackets.
7.1.5 Partitions
A:non magnetic material
Sufficient openings must be provided in partitions to ensure
good air circulation around the circuit breaker;
Any partition between upstream and downstream connections
of the device must be made of nonmagnetic material.
For high-currents, of 2500 A and upwards, the metal supports
or barriers in the immediate vicinity of a conductor must
be made of non-magnetic material A;Metal barriers through
which a conductor passes must not form a magnetic loop.
A
Busbars
The mechanical connection must be exclude the possibility non magnetic material
of formation of a magnetic loop around a conductor.
26 > >>
Air Circuit Breaker
NA1
7.1.6 Busbar connections
The busbars should be suitably adjusted to ensure the
connection points are positioned on the terminals before
the bolts are inserted B The connections are held by the
supporter which is fixed to the framework of the
switchboard, in this way the circuit breaker terminals
do not have to support its weight C.
(This support should be placed close to the terminals).
B C B
18min 18min
> >> 27
Air Circuit Breaker
NA1
7.1.8 Clamping 1 2 3 4
Correct clamping of busbars depends on the tightening
torques used for the nuts and bolts,etc. Over-tightening
may have the same consequences as under-tightening.
Examples
28 > >>
Air Circuit Breaker
NA1
7.2 Wiring the secondary circuit according to electric principle
diagram.
Note: Bolts, nuts, gaskets shouldn't be left inside the drawer
seat to avoid being blocked. Secondary connecting part
Arcing chamber
7.3 Operation
Check the rated voltage of the following components
Main body
whether conforms to the power voltage . Such as under
voltage release, shunt release, closing electromagnet,
motor-driven mechanism and intelligent controller. Drawer seat
7.4 Maintenance
Check the technical parameters in time or add some
lubricating oil, etc.
This breaker structure is arranged vertically and modularized
composition with each functioncell separated, which make
the maintenance easy.
It has compact structure, reliable operation and strong free Handle Slideway
Note: the specifications in the table is obtained as the ambient temperature of air circuit breaker is 40℃, with open installation; this is in
compliance with the specification of copper busbars adopted under the heating conditions regulated in IEC/EN60947-2.
9. Power loss
Inm(A) NA1-1000 NA1-2000 NA1-3200 NA1-4000 NA1-6300
In(A) 200 400 630 800 1000 630 800 1000 1250 1600 2000 2000 2500 3200 4000/3P 4000/4P 4000 5000 6300
Power Drawer type 40 101 123 110 177 70 110 172 268 440 530 384 600 737 921 900 575 898 1426
loss (W) Fixed type 33 85 107 94 476 34.4 50 78 122 200 262 200 312 307 - - - - -
> >> 29
Air Circuit Breaker
NA1
10. A2S curve
I2t(A2s×106)
741
341
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
20 40 60 80 100 120 Is(kA)
Note: The ACB is to calibrated at 40℃, special application please refer to the table above and the curve below.
30 > >>
Air Circuit Breaker
NA1
1200 5000
4800
1100
4600
1000 In=1000A 4400
900
4200
4000 In=4000A
Rated current (A)
Ambient temperature(℃)
Ambient temperature(℃) NA1-3200, NA1-4000
NA1-1000
2000 7000
In=2000A
1900 6800
1800 6600
1700 6400
In=1600A
1600 6200
1500 6000
Rated current (A)
In=6300A
5800
Rated current (A)
1400
In=1250A
1300 5600
1200 5400
1100 5200 In=5000A
In=1000A
1000 5000
900 4800
In=800A
800 4600
700 In=630A 4400
600 4200
In=4000A
500 4000
400 3800
40 45 50 55 60 65 70 40 45 50 55 60 65 70
> >> 31
Air Circuit Breaker
NA1
12. Coordination recommendations
1×250 360 9 9
2×250 360 9 9
3×250 360 9 18.5
1×315 455 11.4 11.4
2×315 455 11.4 11.4
3×315 455 11.4 22.7
1×400 578 14.4 14.4
2×400 578 14.4 14.4
3×400 578 14.4 28.8
1×500 722 18 18
2×500 722 18 18
3×500 722 18 36.1
1×630 910 22.7 22.7
2×630 910 22.7 22.7
3×630 910 22.7 44.5
1×800 1154 19.3 19.3
2×800 1154 19.3 19.3
3×800 1154 19.3 38.5
1×1000 1444 24 24
2×1000 1444 24 24
3×1000 1444 24 48.1
1×1250 1805 30 30
2×1250 1805 30 30
3×1250 1805 30 60.1
1×1600 2310 36.5 36.5
2×1600 2310 36.5 36.5
3×1600 2310 36.5 73
1×2000 2887 48.2 48.2
2×2000 2887 48.2 48.2
3×2000 2887 48.2 96.3
1×2500 3608 60 60
2×2500 3608 60 60
1×3150 4550 75.8 75.8
2×3150 4550 75.8 75.8
32 > >>
Air Circuit Breaker
NA1
NA1-1000-400 9
NA1-1000-400 2×(5×30) 18.5 NA1, NM8
NA1-1000-400 27.5
NA1-1000-630 11.4
NA1-1000-630 2×(5×40) 22.7 NA1, NM8
NA1-1000-630 34.1
NA1-1000-630 14.4
NA1-1000-630 2×(5×40) 28.8 NA1, NM8
NA1-1000-630 43.2
NA1-1000-800 18
NA1-1000-800 2×(6×50) 36.1 NA1, NM8
NA1-1000-800 54.1
NA1-1000-1000 22.7
NA1-1000-1000 2×(8×50) 44.5 NA1, NM8
NA1-2000-1000 67.2
NA1-2000-1250 19.3
NA1-2000-1250 2×(10×60) 38.5 NA1, NM8
NA1-2000-1250 57.8
NA1-2000-1600 24
NA1-2000-1600 2×(12×60) 48.1 NA1, NM8
NA1-2000-1600 72.1
NA1-2000-2000 30
NA1-2000-2000 3×(10×60) 60.1 NA1, NM8
NA1-2000-2000 90.1
NA1-3200-2500 36.5
NA1-3200-2500 2×(10×100) 73 NA1, NM8
NA1-3200-2500 109.5
NA1-3200-3200 48.2
NA1-3200-3200 4×(10×100) 96.3 NA1, NM8
NA1-3200-3200 144.5
NA1-6300-4000 60
4×(10×120) NA1, NM8
NA1-6300-4000 120
NA1-6300-5000 75.8
7×(10×100) NA1, NM8
NA1-6300-5000 151.6
> >> 33
Air Circuit Breaker
NA1
13. Selectivity protection
13.1 Selective protection between NM8 and NA1
Rated
400 630 800 1000 1250
current (A)
Default setting ratings
3.2 5.04 6.4 8 10
of short time-delay 8In (kA)
Delayed tripping
0.1, 0.2, 0.3, 0.4
time (s)
Returnable time 0.06, 0.14, 0.23, 0.35
Frame size Rated Instantaneous
rated current current (A) setting ratings (kA)
34 > >>
Air Circuit Breaker
NA1
1600 2000 2000 2500 3200 3200 4000 4000 5000 6300
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.656~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.725~24 1.725~30 1.725~30 1.725~37.7 1.725~48 1.725~48 1.725~60 1.725~60 1.725~75 1.725~94.5
2.07~24 2.07~30 2.07~30 2.07~37.7 2.07~48 2.07~48 2.07~60 2.07~60 2.07~75 2.07~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.656~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
2.208~24 2.208~30 2.208~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
2.65~24 2.65~30 2.65~30 2.65~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
2.76~24 2.76~30 2.76~30 2.76~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
3.312~24 3.312~30 3.312~30 3.312~37.7 3.312~48 3.312~48 4~60 4~60 5~75 6.3~94.5
3.45~24 3.45~30 3.45~30 3.45~37.7 3.45~48 3.45~48 4~60 4~60 5~75 6.3~94.5
4.14~24 4.14~30 4.14~30 4.14~37.7 4.14~48 4.14~48 4.14~60 4.14~60 5~75 6.3~94.5
> >> 35
Air Circuit Breaker
NA1
Rated
400 630 800 1000 1250
current (A)
Default setting ratings
3.2 5.04 6.4 8 10
of short time-delay 8In (kA)
Setting
Downstream Upstream 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75
range (kA)
Delayed tripping
0.1, 0.2, 0.3, 0.4
time (s)
Returnable time 0.06, 0.14, 0.23, 0.35
Frame size Rated Instantaneous
rated current current (A) setting ratings (kA)
10 13.8~15 13.8~18.75
1000
12(motor) 16.56~18.75
12.5 17.25~18.75
1250
15.0(motor)
36 > >>
Air Circuit Breaker
NA1
1600 2000 2000 2500 3200 3200 4000 4000 5000 6300
3.45~24 3.45~30 3.45~30 3.45~37.7 3.45~48 3.45~48 4~60 4~60 5~75 6.3~94.5
4.14~24 4.14~30 4.14~30 4.14~37.7 4.14~48 4.14~48 4.14~60 4.14~60 5~75 6.3~94.5
4.347~24 4.347~30 4.347~30 4.347~37.7 4.347~48 4.347~48 4.347~60 4.347~60 5~75 6.3~94.5
5.216~24 5.216~30 5.216~30 5.216~37.7 5.216~48 5.216~48 5.216~60 5.216~60 5.216~75 6.3~94.5
4.83~24 4.83~30 4.83~30 4.83~37.7 4.83~48 4.83~48 4.83~60 4.83~60 5~75 6.3~94.5
5.796~24 5.796~30 5.796~30 5.796~37.7 5.796~48 5.796~48 5.796~60 5.796~60 5.796~75 6.3~94.5
5.52~24 5.52~30 5.52~30 5.52~37.7 5.52~48 5.52~48 5.52~60 5.52~60 5.52~75 6.3~94.5
6.624~24 6.624~30 6.624~30 6.624~37.7 6.624~48 6.624~48 6.624~60 6.624~60 6.624~75 6.624~94.5
6.9~24 6.9~30 6.9~30 6.9~37.7 6.9~48 6.9~48 6.9~60 6.9~60 6.9~75 6.9~94.5
8.28~24 8.28~30 8.28~30 8.28~37.7 8.28~48 8.28~48 8.28~60 8.28~60 8.28~75 8.28~94.5
8.694~24 8.694~30 8.694~30 8.694~37.7 8.694~48 8.694~48 8.694~60 8.694~60 8.694~75 8.694~94.5
10.44~24 10.44~30 10.44~30 10.44~37.7 10.44~48 10.44~48 10.44~60 10.44~60 10.44~75 10.44~94.5
8.694~24 8.694~30 8.694~30 8.694~37.7 8.694~48 8.694~48 8.694~60 8.694~60 8.694~75 8.694~94.5
10.44~24 10.44~30 10.44~30 10.44~37.7 10.44~48 10.44~48 10.44~60 10.44~60 10.44~75 10.44~94.5
9.66~24 9.66~30 9.66~30 9.66~37.7 9.66~48 9.66~48 9.66~60 9.66~60 9.66~75 9.66~94.5
11.59~24 11.59~30 11.59~30 11.59~37.7 11.59~48 11.59~48 11.59~60 11.59~60 11.59~75 11.59~94.5
11.04~24 11.04~30 11.04~30 11.04~37.7 11.04~48 11.04~48 11.04~60 11.04~60 11.04~75 11.04~94.5
13.25~24 13.25~30 13.25~30 13.25~37.7 13.25~48 13.25~48 13.25~60 13.25~60 13.25~75 13.25~94.5
13.8~24 13.8~30 13.8~30 13.8~37.7 13.8~48 13.8~48 13.8~60 13.8~60 13.8~75 13.8~94.5
16.56~24 16.56~30 16.56~30 16.56~37.7 16.56~48 16.56~48 16.56~60 16.56~60 16.56~75 16.56~94.5
17.25~24 17.25~30 17.25~30 17.25~37.7 17.25~48 17.25~48 17.25~60 17.25~60 17.25~75 17.25~94.5
20.7~24 20.7~30 20.7~30 20.7~37.7 20.7~48 20.7~48 20.7~60 20.7~60 20.7~75 20.7~94.5
> >> 37
Air Circuit Breaker
NA1
13.2 Selective protection in NA1
Rated
400 630 800 1000 1250
current (A)
Default setting ratings
3.2 5.04 6.4 8 10
of short time-delay 8In (kA)
Setting
Downstream Upstream 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75
range (kA)
Delayed tripping
0.1, 0.2, 0.3, 0.4
time (s)
Returnable time 0.06, 0.14, 0.23, 0.35
Frame size Rated Default instantaneous
rated current current (A) setting ratings 12In (kA)
400 4.8 6.348~9.45 6.348~12 6.348~15 6.348~18.75
630 7.56 9.998~12 9.998~15 9.998~18.75
800 9.6 12.696~15 12.696~18.75
NA1-2000 1000 12 15.87~18.75
1250 15
1600 19.2
2000 24
2000 24
NA1-3200 2500 30
3200 38.4
3200 38.4
NA1-4000
4000 48
4000 48
NA1-6300 5000 60
6300 75
Note: It can satisfy the selective protection if only the short time-delay setting value of the superior breaker 1.32 times more than the
subordinate breaker, when the instantaneous setting value is adjustive.
38 > >>
Air Circuit Breaker
NA1
1600 2000 2000 2500 3200 3200 4000 4000 5000 6300
6.348~24 6.348~30 6.348~30 6.348~37.7 6.348~48 6.348~48 6.348~60 6.348~60 6.348~75 6.348~94.5
9.998~24 9.998~30 9.998~30 9.998~37.7 9.998~48 9.998~48 9.998~60 9.998~60 9.998~75 9.998~94.5
12.696~24 12.696~30 12.696~30 12.696~37.7 12.696~48 12.696~48 12.696~60 12.696~60 12.696~75 12.696~94.5
15.87~24 15.87~30 15.87~30 15.87~37.7 15.87~48 15.87~48 15.87~60 15.87~60 15.87~75 15.87~94.5
19.837~24 19.837~30 19.837~30 19.837~37.7 19.837~48 19.837~48 19.837~60 19.837~60 19.837~75 19.837~94.5
25.392~30 25.392~30 25.392~37.7 25.392~48 25.392~48 25.392~60 25.392~60 25.392~75 25.392~94.5
31.74~37.7 31.74~48 31.74~48 31.74~60 31.74~60 31.74~75 31.74~94.5
31.74~37.7 31.74~48 31.74~48 31.74~60 31.74~60 31.74~75 31.74~94.5
39.675~48 39.675~48 39.675~60 39.675~60 39.675~75 39.675~94.5
50.784~60 50.784~60 50.784~75 50.784~94.5
50.784~60 50.784~60 50.784~75 50.784~94.5
63.48~75 63.48~94.5
63.48~75 63.48~94.5
79.35~94.5
> >> 39
Air Circuit Breaker
NA1
14. Intelligent controller
14.1 The intelligent controller of NA1-1000
a. The standard M type intelligent controller (NA1-1000)
1: Reset key
1 2: Rated current
3: MCU indicator( normal operation indicator)
4: Current indicator 5-Earthing fault indicator
2 3
6: Short circuit instantaneous fault indicator
4
7 7: Short circuit short time-delay fault indicator
5 8 8: Overload fault indicator
6 9: Time setting table
10: Current setting table
9 11: Overload long time-delay time setting key
12: Overload long time-delay current setting key
10 13: Fault cheking key
14: Short circuit short time-delay time setting key
15: Short circuit short time-delay current setting key
16: Test key
17: Short circuit instantaneous current setting key
18: Clear LED key
19: Earthing current setting key
11
12 20: Earthing time setting key
13
14
15 16
The function of keys show as followed:
17 18 “Fault checking“ key: After the breaker tripping,
press this key to indicate the kind of fault.
19 20
“Test key” key: used for checking the controller and the action of
the breaker.
“Clear LED” key: After the setting,testing and fault checking of the
controller, make the circuit breaker at normal operation.
2 1: Reset key
2: LCD display window
3: Fault and alarm reset key
4: Curve LED indication
3 5: ”Fault/alarm” LED
6: ”Normal” LED
4 5
7: ”Communication” indicator
6
7 8: Test key
9: Setting key
10: Message key
10 11: Protection key
12: Increasing key
8 11 13: Decreasing key
9 14: Choosing key
12 14
15: Exit key
15
13 16: Testing port
16
40 > >>
Air Circuit Breaker
NA1
c. Basic functions
● stands for definite setting ■ stands for optional setting — stands for no funcion
Standard (M type) Communication (H type)
Controller type Three cascades Four cascades Three cascades Four cascades
protection protection protection protection
Long time-delay protection ● ● ● ●
Short time-delay protection ● ● ● ●
Instantaneous protection ● ● ● ●
Earthing fault protection — ● ● ●
Load current display ● ● — —
Load current digital display (Ampere Meter) — — ● ●
Test function ● ● ● ●
Basic Fault recall ● ● ● ●
function Self-diagnose function ● ● ● ●
MCR making and breaking function ● ● ● ●
Fault alarm ● ● ● ●
Fault breaking indication ● ● ● ●
Customer setting, testing ● ● ● ●
Load monitor — — — —
RS485 port MODBUS protocol — — — —
Voltage measuring — — — —
Frequency display — — — —
Active power measuring — — — —
Power factor measuring — — — —
Electric energy measuring — — — —
Over voltage protection — — — —
Under voltage protection — — — —
Optional Phase protection — — ● ●
auxiliary
Current transformer earthing protection ■ (3P+N model) ■ (3P+N model) ■ ■
function
Exceed breaking function ■ ■ ■ ■
Thermal recall fuction ■ ■ ■ ■
Four output contacts ■ ■ ■ ■
LED display, code switch and LCD display, LED indication,
Man-machine interface instruction
toggle switch setting keyboard operation
d. Operation instructions
Standard intelligent controller setting
According to the panel number 9 showed, dial the switch 11,14,20 to set the time you need.
According to the panel number 10 showed, dial the switch 12,15,17,19 to set the current you need.
Example 1: means that overload long time-delay current is 0.9In, overload long time-delay time is 60s.
Example 2: means that short circuit short time-delay current is 4In, short circuit short time-delay time is 0.4s.
> >> 41
Air Circuit Breaker
NA1
Example 1 Example 2
tr tsd
Ir Isd
Press or key to return default interface. Press or key to return default interface.
On other non-fault interface, press to skip to testing On other non-fault interface, press to skip to
menu. system data setting menu.
Without action for several minutes, Without action for several minutes,
it returns to the default interface. it returns to the default interface.
Press or key to return default interface. Press or key to return default interface..
On other non-fault interface, press to skip to On other non-fault interface, press to skip to
protection data setting menu. testing menu.
Without action for several minutes, Without action for several minutes,
it returns to the default interface. it returns to the default interface.
42 > >>
Air Circuit Breaker
NA1
5. Submenu operation show:
overload longtime-delay protection setting
= SI = SI = SI
▲
+
-
▲
then ▲
+
-
▲
Setting definite value Save definite value
10000
5000
I R =(0.4~1)In
2000
tl=(30~240)s
(M type)
1000
500
200
100
50
20
10
5
t(a)
1
Isd=(3~10)IR(M type)
0.4s or(1.5~15)In(H type)
0.5
0.3s
0.2
0.2s
0.1
0.1s
0.05
0.01
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 70 80 100
xIn kA
> >> 43
Air Circuit Breaker
NA1
Long time-delay overcurrent protection, inverse time characteristic.
Setting current
Error Current Tripping time (s) time error
(IR)
1.05IR <2h Non-trip
1.3IR <1h trip
1.5IR(M) 30 60 120 240 ±10%
(0.4~1)In+OFF ±10%
2.0IR(M) 16.9 33.8 67.5 135 ±10%
1.5IR(H) 0.61~86 ±10%
6.0IR(H) 0.14~19.2 ±10%
Setting current
Error Setting delay time (s) Time error
(IR)
Isd ts(s)
M (3~10)IR+OFF ±10% 0.2 0.4 ±15%
H OFF+(1.5~15)IR ±10% 0.1 0.2 0.3 0.4 ±15%
Instantaneous characteristic.
Type Setting current (Ii) Tripping Error
M (3~15)In+OFF ≤0.85Ii 30ms Non-trip;>1.15Ii trip ±15%
H (1~20)In+OFF ≤0.85Ii 40ms Non-trip;>1.15Ii trip ±15%
Type Rated current (Ig) Error Rated delay time (Tg) Time error
M (0.2~0.8)In+OFF,min 100A ±10% 0.1, 0.2, 0.3, 0.4 ±15%
H (0.2~1.0)In+OFF,min 100A ±10% (0.1~1.0)s ±15%
Ig=(0.2~0.8)In(M type)
min 100A
T(s)
0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8
XIn
44 > >>
Air Circuit Breaker
NA1
Wiring diagram of the earthing fault protection.
Intelligent Intelligent
controller controller
N
N
Intelligent
Intelligent
controller
controller
PE
10
×In ×In
> >> 45
Air Circuit Breaker
NA1
14.2 The intelligent controller of NA1-2000, 3200, 4000, 6300
14.2.1 The standard M type intelligent controller (NA1-2000 3P 4P; NA1-3200 3P 4P; NA1 4000 3P)
The M type intelligent controller is the core part of the NA1 Air Circuit Breaker to protect the electric circuit and the power supply
against the dangers such as overload, short circuit and single-phase earthing fault. The controller adopts highly-integrated and high-
performance digital signal processor that featuring power functions and reliable performance to perform real-time processing to the
signal so as to achieve various protection function and numerous auxiliary functions.
Reset button
Rated current
Select key
Clear key
Fault indicator
Protection indicator
Function key
Program interface
t t
IL IS II I IG I
46 > >>
Air Circuit Breaker
NA1
a. Symbol designation table
[Link] power supply Step 6: Repeat step 3 ~ step 5 in case requiring changing
The operating power supply input to the intelligent controller: other parameters. If not, press “reset” key till the characteristic
AC 400V/380V, 230V/220V, AC 110V, 50Hz; curve indicator is off.
DC220V, 110V, 24V. Note: In case of occurrence of malfunction under setup status,
c. Basic functions of intelligent controller it will automatically exit the setup status and enter into
Main protection function malfunction status.
Query function During the adjustment of the parameters, the longer the time of
Parameter setting function pressing or holding the “+” or “-” key is, the faster the up or
Test function down speed is.
Load monitor function (optional)
Making current release (MCR) and High-Set Instantaneous Failure inquiry operation
Short Circuit (HSISC) function (optional) Query operation method
Signal alarm function (optional) Step 1: Make sure the controller is under reset status.
d. Operation instructions Step 2: Press “fault display” key till the ammeter display window
Parameter setting operation indicates the failure action value and the action time alternately.
Step 1: Setting right confirmation. The key must be switched Press “select” to inquiry relevant parameters.
to ”setting” position for type H. Step 3: Press “reset” key to exit the inquiry status.
This step is no necessary for type M.
Step 2: Make sure the controller is under reset status. If the Test operation method
controller isn't under reset status, press ”reset” key till the Step 1: Make sure the controller is under reset status.
ammeter displays operation current. Step 2: Press “set” key till the indicator of the short time-delay
Note: When the controller is under malfunction alarm status, characteristic curve current is on. Press “+””-” to adjust the
then the setup function is locked and the setup operation required current.
can't be conducted. Press “trip” key, then the breaker will trip. The ammeter display
Step 3: Press “set” key till the ammeter display window window will display the action current and action time in turn.
displays required action current or time setting. Step 3: Press “reset” key to exit the test status.
Step 4: Press ”+” and ”-” to set the items to be changed.
Step 5: Press “save” key. At that time, the “save“ indicator
will flash once to indicate that the parameters are saved.
If not desiring to save, then directly press “reset” key.
Then the parameters won't be changed and will remain the
original values.
> >> 47
Air Circuit Breaker
NA1
e. Characteristic
10000
5000
Ir1=(0.4~1)In
2000
Tr=(15~480)s
1000
500
200
100
50
20
10
5
t(a)
1
Ir2=(1.0~15)Ir1
0.5 0.4s
0.3s
0.2
I 2t 0.2s
OFF
0.1
0.1s
0.05
Ir3=1.0In~50kA/75kA/100kA
0.02
0.01
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 70 80 100
xIn kA
Current Ratings
Error Current Action Time Time Error
Range(lr1)
Current Ratings
Error Current Action Time Time Error
Range(lr2)
≤0.9Ir2 Non-trip
NA1-2000 1.3Ir1~15Ir1+OFF (OFF Position)
>1.10Ir2 Delayed-trip
NA1-3200 1.3Ir1~15Ir1+OFF (OFF Position), Ir2≤40KA ±10%
Time setting (ts) 0.1 0.2 0.3 0.4 ±25%
NA1-6300 1.3Ir1~15Ir1+OFF (OFF Position), Ir2≤50KA
Returnable Time 0.06 014 0.19 0.25 ±25%
48 > >>
Air Circuit Breaker
NA1
f. Earth fault protection
The earth fault protection has definite time-delay characteristic
with the failure delayed time no less than the definite time-delay time setting.
1000
500
100
50
20
10 Ir4=(0.2~0.8)In
t(s) 5
2
1
0.05
0.02
0.01
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
xIn
Current Ratings
Error Current Action Time Time Error
Range(lr4)
≤0.8 lr4 Non-tripping
(0.2~0.8)ln
>1.0 lr4 Tripping
+OFF (OFF position) ±10%
Setting time (Tg) 0.1 0.2 0.3 0.4 ±25%
(NA1-2000, min160A)
Returnable time 0.06 014 0.19 0.25 ±25%
> >> 49
Air Circuit Breaker
NA1
14.3 NA1 Multifunctional Intelligent Controller
a. Menu Operation Explanation
Display operation kneading board
7 7
1 1
2
3 2
4 3
4
5
6 6
16 16
50 > >>
Air Circuit Breaker
NA1
t t
0 I 0 I
NA1-2000 630 800 1000 1250 1600 2000 Yes Yes Yes
> >> 51
Air Circuit Breaker
NA1
c. NA1 Multifunctional Intelligent Controller subject menu
NA1 Multifunctional Intelligent controller has provided
4 subject menu and 1 default interface
452 A 3H
150
A B C N current I
100 voltage U
50 frequency F
3H
energy E
power P
·The controller displays the default interface harmonic H
when on electiicity.
·Under each subject menu, press or the
corresponding subject key can return to default
interface.
·press to enter into measure main menu
·If don't press any keys in 5 minutes and then the
·press or to return to default interface
pane cursor will show the maximum phase
automatically. ·In other non-fault interface, press to jump to
·In the non-activated fault interface, measure menu
if don't press any key in 30 minutes
and then will automatically return to the
default interface.
3H 3H
clock set current protection
measurement meter set load monitor
test & clock voltage protection
3H 3H
communication set other protection
I/O set
52 > >>
Air Circuit Breaker
NA1
5. “history and maintenance”menu
3H 3H 3H
current warning production information Variable-record
operating time release record
contact wearout warning record
Ir Ir Ir
=10 00 A =40.4 %In 1200 A =48.0 %In =1200 A =48.0 %In
curve type curve type curve type
=VI =VI =VI
▲
+
-
▲
then adjust ▲
+
-
▲
fixed value save fixed value
5000
2000
1000
500
Express inverse-time 1
(Ordinary use)
200
Express inverse-time 2
(Motor protection)
100
Express inverse-time
50
Standard
inverse-time
20
10
t(s)
5 High-voltage fuse
compatibility
0.5
0.2
0.1
0.05
0.02
0.01
0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20
Xin1
> >> 53
Air Circuit Breaker
NA1
Function of intelligent controller
● stands for definite setting ■ stands for optional setting — stands for no funcion
Type
Function configuration
M 3M 3H
Inquiry function ● ● ●
Self-diagnose function — ● ●
Programing interface function — — —
Communication function — — ●
Alarm record — ● ●
54 > >>
Air Circuit Breaker
NA1
e. Overload long time-delay protection
Note: When N-phase is 50%, protective settings are treated as 50% for N-phase. If long delay setting is 2000A, long delay setting for
phase A, B and C is 2000A, and 1000A for phase N.
Note: When controller is frame I (Inm=2000A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1;
when controller is frame II (Inm=3200A, 4000A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1 and max is 40kA;
When controller is frame III (Inm=6300A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1 and max is 50kA.
Note: When controller is frame I (Inm=2000A), rectified value of instantaneous protection is 1.0In~50kA+OFF;
when controller is frameII (Inm=3200A), rectified value of instantaneous protection is 1.0In~65kA+OFF;
When controller is frame III (Inm=6300A), rectified value of instantaneous protection is 1.01n~75kA+OFF.
> >> 55
Air Circuit Breaker
NA1
Wiring diagram of earth fault protection
CT CT L1 CT L1
L1
L2 L2
L2
L3 L3
L3
N
PEN intelligent
PE
intelligent controller
intelligent
controller
controller N
PE
externally connected zero sequence current externally connected zero sequence current externally connected zero sequence current
inductor type 1 applied(ZCT) inductor type 2 applied(ZCT) inductor type 3 applied(ZCT)
ZCT ZCT
CT CT CT
L1 L1 L1
L2 L2 L2
L3 L3 L3
N N
PEN
PE intelligent
intelligent ZT100
intelligent controller
controller
controller
PE or PEN
load type method 1 property curve load monitor type 2 property curve
10000
10000
5000
5000
Ir1=(0.4~1)In
Ir1=(0.4~1)In
Ic1=(0.2~1)In
2000 Ic1=(0.2~1)In
2000
Ic2=(0.2~1)In Ic2=(0.2~1)In
1000
1000
500 500
200 200
100 100
50 50
t1=(15~480)S tr2=60s t1=(15~480)S
20 20
Tr1=(1/2)tL
10 Tr2=(1/4)tL 10 tr2=1/4tL
5 5
t(a) t(a)
2 2
tr1=1/2tL
1 1
0.5 0.5
0.2
0.2
0.05
0.05
0.02
0.02
0.01
0.01 30
0.010.02 0.03.1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
0.01 0.02 0.03 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 xIn
xIn
56 > >>
Air Circuit Breaker
NA1
Technical parameter:
k. Communication networking
Make key-lock at “communication” position, connect to
secondary terminals “10#” and “11#” through cable to
achiveve the communication function.
Rt
Rt
ST-DP ST-DP ST-DP
CP5×11Main
RS232 RS485 station card r
Converter RS485
NA1 NA1 NA1
> >> 57
Air Circuit Breaker
NA1
15. Accessories
15.1 Under-voltage release
Without power supply, under-voltage release can't close.
It is classified into instantaneous and time-delay type.
Delay time 0, 1s, 2s, 3s, 4s, 5s, 6s, 7s are fixed for NA1-1000; 1s, 3s, 5s are fixed for NA1-2000, 3200, 4000, 6300.
Within 1/2 time-delay range, circuit breaker does not trip when power voltage recovers and exceeds 85%Ue.
Characteristic
Make sure there is power supply on the under-voltage release, before making the circuit breaker.
Forbid making the power for long time to avoid the shunt release being damaged.
Forbid making the power for long time to avoid the closing release being damaged.
58 > >>
Air Circuit Breaker
NA1
Characteristic
Characteristic
15.6 Doorcase
Installed on the door of the distribution cubicle, for sealing 15.7 Phases barrier
the distribution cubicle and making the Installed between the busbars to increase the creepage
protection class to IP40( fixed type and drawout type). distance.
> >> 59
Air Circuit Breaker
NA1
15.10 Off position locking mechanism
When the circuit breaker is disconnected, padlock can be used to lock it after pulling out the lock lever, then the circuit breaker
can't be “Test” or “connected” position.( Padlock is prepared by users)
15.11 Key lock
Lock the circuit breaker on the OFF position, then the circuit breaker can't be closed.
Locks and keys will be provided by us.
Separate lock and key is matched with one set of the circuit breaker.
Three same locks and two same keys are matched with three circuit breaker.
Note: Before pulling out the key, the break pushbutton should be pressed first, rotate the key anticlockwise, then pull it out.
2. Installation sequence:
1. Boring here, and 2. Put the into 3. Install the 4. Push the red button “ON”, and take the
polish the hole hole
make the hole lock here key out, then install the cover.
it smooth
2m(max)
1QF 2QF
1QF 2QF
0 0
0 1
1 0
Notes: a. when the steel cable needs to be bent, enough transition arc should be reserved to guarantee flexible movement of steel cable;
b. check the steel cable and make sure there is enough lubricant in the steel cable to guarantee flexible movement of steel cable.
60 > >>
Air Circuit Breaker
NA1
15.13 Connecting-rod type mechanical interlock
Three vertical-installed three-poles or four-poles, drawout-type or fixed type circuit breakers realize the interlock between one
breaker with another two different-state breakers.
Bracket 2
Nameplate
Bracket 1
Body
Drawout base
> >> 61
Air Circuit Breaker
NA1
16. Regular malfunction and solutions
Fault description Reasons analysis Maintenance method
1. Check the breaking current value and operation time of intelligent release.
Over load tripping 2. Analyze the load and electric network, exclude the overload if it happens.
(IL indicator flashing) 3. Match the actual operating current with long time-delay current setting value.
4. Press the reset button to reclose the breaker
1. Check the breaking current value and operation time of intelligent release.
2. Exclude the short circuit fault if it happens
Short circuit tripping
3. Check the setting value of intelligent release
(“Is”or“Ii”indicator flashing)
4. Check the normal state of breaker
5. Press the reset button to reclose the breaker
Tripping of
circuit breaker
1. Check the breaking current value and acting time of intelligent release.
Earthing fault tripping 2. Exclude the earthing fault if that happens.
(IG indicator flashing) 3. Match the fault current setting value with the actual protection.
4. Press the reset button to reclose the breaker.
Mechanical interlock acting Check the working state of two circuit breakers fixed with mechanical interlock
Intelligent release don't reset
Press the reset button to reclose the breaker
(panel is raised)
The breaker Secondary circuit of drawerout- Make the breaker to "making" position
can't be type breaker isn't connected ("click" sound will be heard)
closed
Check the secondary circuit:
Breaker hasn't stored energy 1. Power voltage of motor shouldn't less than 85%Ue.
2. Check the storage mechanism, replace it if necessary.
Mechanical interlock acting Check the working state of two circuit breakers
leads to locking of breaker fixed with mechanical interlock
Tripping immediately: 1. Check the breaking current value and operation time of intelligent release;
Tripping after
1. Short circuit current is closed 2. Exclude the short circuit fault if it happens;
closing the
[Link] tripping because of 3. Exclude overload fault
circuit breaker
(Fault indicator transient current is high 4. Check the normal state of breaker
flashing) when closing; 5. Modify the current setting value of intelligent release
3. Overload current is closed 6. Press the reset button to reclose the breaker
62 > >>
Air Circuit Breaker
NA1
Fault description Reasons analysis Maintenance method
Manual storage can't be realized Mechanical fault with the energy-storage device
Drawerout-type breaker
[Link] isn't pulled out
can't be drawn out [Link] out the handle
[Link] is not totally at the
at the "opening" [Link] the circuit breaker totally at “opening” position
“opening" position
position
Fault indicator still Fault happened with Cut off the power, then connect again. Otherwise contact
flashing after pressing
intelligent release with manufacturer
the clear button
> >> 63
Air Circuit Breaker
NA1
NA1-1000 Orde sheet
Customer: Tel: Date:
Quantity:
Model NA1-1000
Rated current In ( A ) □ 200 □ 4 00 □ 63 0 □ 8 00 □ 10 00
Installation mode □ Drawerout type □ Fixed type
Number of poles □ Three poles □ Four poles
Conventional setting before delivery: IR=1In, 30s, Isd=8In, Tsd 0.4s; Ii=12In; Ig=OFF tg=0.4s
Long time-delay Current setting: In (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, OFF)
protection IR(Ir1) Time setting: s (30, 60, 120, 240)
Short circuit short time- Current setting: IR (3, 4, 5, 6, 7, 8, 10,OFF)
□Standard delay protection Isd(Ir2) Time setting: s (0.2, 0.4)
M type Short circuit instantaneous
Current setting: In (3, 4, 6, 8, 10, 12, 15, OFF)
protection Ii(Ir3)
Earthing Current setting: In (0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, OFF Min100A)
protection Ig Time setting: s (0.2, 0.4, 0.6, 0.8)
Protection data setting: LED display; Test function; Fault recall; Self-diagnose function;
MCR and HSISC function; Fault breaking indication
Intelligent Optional □ Exceed skipping function □ Self-diagnose alarm □ Fault breaking alarm
controller function □ Overload alarm □ Earthing fault alarm
Conventional setting before delivery: IR=1In, 17.2s,; Is=6IR, Isd=8IR; Tsd 0.4s; Ii=12In; Ig=OFF tg=0.4s
Current setting:(0.4~1)In
Long time-delay
Time setting(1.5In): 0.61, 0.98, 1.47, 2.46, 3.68, 4.91, 6.14, 8.29,
protection IR(Ir1)
11.1, 17.2, 24.6, 36.8, 49.1, 61.4, 73.7, 86s
Short circuit short time- Current setting: (1.5~15)IR + OFF
delay protection Isd(Ir2)
□Comm- Time setting: (0.1~0.4)s
Note: 1) Please mark “√” or fill figure in the relative ”□” if no mark, we will provide according to conventional.
NA1-1000
64 > >>
Air Circuit Breaker
NA1
NA1-2000~6300 Orde sheet
Customer: Tel: Date:
Quantity:
Installation mode □Drawerout type □Fixed type (note: =In 4000A fixed type is not available)
Number of poles □Three poles □Four poles
Protection function Others functions Optional function
□M-typ e
1. □Ir1 protection for overload long time-delay, Ir2 inverse-time protection
sta ndard + definite time-delay protection for short-circuit short time-delay, Ir3 □ Display of voltage
typ e (default instantaneous protection for short-circuit, Ir4 4-section protection for □ Display of frequency
single-phrase earthing. 1. Function of current □ Display of power factor
configuration)
2. □Ir1 protection for overload long time-delay, Ir2 definite time-delay meter □ Display of power
protection for short-circuit short time-delay, Ir3 instantaneous protection 2. Function of □ Function of monitoring
for short-circuit, Ir4 4-section protection for single-phrase earthing. self-diagnosis load
3. Function of setting
Intelligent controller
1. Ir1 protection for overload long time-delay, Ir2 definite time-delay protection ! Not items to be selected
□H-type for short-circuit short-delay, Ir3 instantaneous protection for short-circuit, 4. Function of test necessarily, cost of the
Communication- 4-section protection for single-phrase earthing. 5. Function of display increased will be calculated
type (optional) 2. Ir1 protection for overload long time-delay, Ir2 inverse-time protection + additionally
definite time-delay protection for short-circuit short time-delay, Ir3 instantaneous
protection for short-circuit, 4-section protection for single-phrase earthing.
Available set range of Ir1 long-delay current:(0.4~1)In !Conventional setting before delivery: overload long time-delay: 1.0In
Explanation:
Available set range of operating time with overload 1.5In: 15, 30, 60......480s !Conventional setting before delivery: overload 1.5In, operating 15s
Available set
range of ! Conventional setting before delivery: short time-delay current 8Ir1
protection Available set range of current of Ir2 short-delay; Operating time of short-delay: 0.1~0.4s ! Conventional setting before delivery: operating time of short time-delay: 0.4s 0.1~0.4s
function and
conventional Available set range of Ir3 instantaneous current : 1.0 In~50kA/75kA/100kA
setting before ! Conventional setting before delivery: 12In
delivery Available set scope of Ir4 earthing protection current: 0.2~0.8 In; Available set scope of operating time of earthing protection: 0.1~0.4s
! Conventional setting before ex-factory: 0.5 In;OFF
Power supply of controller □AC380V, □AC220V, □DC220V, □DC110V (Optional)
Under-voltage □AC380V, □AC220V, □DC220V, □customize V (Optional)
Electrical accessories
release (default
configuration) □Instantaneous □Delay s; □ Time delay of R-C (Resistance-Capacity) type Undser-voltage release: (1~5)s (Optional)
Shunt release
(default □AC380V, □AC220V, □DC220V, □DC110V (Optional)
configuration)
Motor (default
□AC380V, □AC220V, □DC220V, □DC110V (Optional)
configuration)
device (cost will □ Steel cable interlocking :( for both types of drawer-type and fixed-type) □ Button lock (Optional)
be calculated □ Key lock: ( for both types of drawer-type and fixed-type) □ Door interlock (open or closed position)
Special
Connection of main circuit □ Explanation of vertical connection (prepared with vertical bus-bar): conventional supply is horizontal connection
□ Revolving bus-bar (Drawerout type In≤3200) (cost of the increased will be burden by the user)
Remark: Current of frame size, rated current, and auxiliary control voltage must be indicated when ordering
Note: 1) Please mark “√”or fill figure in the relative“□”if no mark, we will provide according to conventional factory settings.
2) For ordering products with optional function or special requirements, please contact with us.
> >> 65
Air Circuit Breaker
NA1
Configurations explanation 2. NA1-1000 fundamental configurations
a. Motor-driven:
1. NA1-2000~6300 fundamental configurations Under-voltage instantaneous release;
a. Motor-driven: Shunt release;
Under-voltage instantaneous release; Closing electromagnet;
Shunt release; Motor driven operating mechanism;
Closing electromagnet; 4 normal open and 4 normal close auxiliary contacts;
Motor driven operating mechanism; M-type Intelligent Controller;
4 suits of transform contact; Closing and breaking push button lock;
M-type Intelligent Controller; Horizontal wiring of main circuit;
Horizontal wiring of main circuit; Doorcase;
Doorcase; Element of main circuit;
Element of main circiut; Operating instructions of Air Circuit Breaker;
Operating instructions of Air Circuit Breaker; Packing box;
Packing box; Drawer seat(Drawout type)
Drawer seat (Drawout type)
b. Manual:
b. Manual: Under-voltage instantaneous release;
Under-voltage instantaneous release; 4 normal open and 4 normal close auxiliary contacts;
4 suits of transform contact; M-type Intelligent Controller;
M-type Intelligent Controller; Horizontal wiring of main circuit;
Horizontal wiring of main circuit; Closing and breaking push button lock;
Doorcase; Doorcase;
Element of main circuit; Element of main circuit;
Operating instructions of Air Circuit Breaker; Operating instructions of Air Circuit Breaker;
Packing box; Packing box;
Drawer seat(Drawout type) Drawer seat(Drawout type)
3. Additional selective configurations(need extra cost) 4. Additional selective configurations(need extra cost)
NA1-2000~6300 selective configurations explanation: NA1-1000 selective configurations explanation:
66 > >>
Air Circuit Breaker
NA1
Detailed certificate
Model Voltage Frame size Rated current Poles EU Netherlands Ukraine Russia South Africa
4000 3P _ _ _ _ _
4000
■
4000 5000 3P 4P ■ ■ ■ Except 5000 ■
6300
6300 3P ■ ■ ■ ■ ■
4000 3P _ _ ■ _ _
4000
■ _
4000 5000 3P 4P ■ ■ ■ Except 5000
6300
3P ■ ■ ■ ■ _
6300
> >> 67
Air Circuit Breaker