2010-2011

Catalogue (EN)

Air Circuit Breaker

EN B03
CHINT Electrics

CHINT Electric
CHINT Low-voltage Electrical Products
Zhejiang CHINT Electrics Co., Ltd, the business unit of CHINT for Low-voltage
Electrical Products, is a nationwide leader in power distribution and industrial
control industry and is one of the core businesses of CHINT Group. The product
lines cover low-voltage electrical products of circuit breakers, contactors,
pushbuttons, switches, transformers, relays, capacitors, motor starters, etc.
The company adopts an ERP system by SAP and automatic warehouse guarantee
just-in-time operations and lead-time. Many of CHINT Low-voltage electrical
products have been certified under important international certificates such as
CE, DNV, AENOR, KEMA, ASTA, VDE, TÜV, SEMKO, FIMKO, CCC, EK, ESC, SNI,
UKrSEPRO, GOST, RCC, SLSI, SAA, UL, CSA, etc. Exquisitely manufactured and
strictly tested, CHINT Low-voltage Electrical Products will meet your various
demands for industrial, commercial, and residential applications on reliable
operations and considerate before & after-sale services.
Chint products are certified
by the following
international certificates:

EU

Norway
DNV

Spain

Netherlands
K
RTE

UK
TE
IN

A A

Germany

Germany
TUV

Sweden

Finland

China

Korea

Czech

Indonesia

Ukraine

Russia

South Africa

Sri Lanka

Australia

C R US LISTED USA

Canada
Air Circuit Breaker
NA1

Summary Page 01

Main technical parameter Page 06

Dimensions and connection Page 08

Secondary circuit wiring Page 16

Installation Page 25

Recommendation for user’s Page 29

connecting bus-bar

Power loss Page 29

A2S curve Page 30

Temperature compensation Page 30

correction

Coordination recommendations Page 32

Selectivity protection Page 34

Intelligent controller Page 40

Accessories Page 58

Regular malfunction Page 62

and solutions

Order sheet Page 64


Air Circuit Breaker
NA1
NA1-1000
200A to 1000A

NA1-2000
630A to 2000A

Summary
5 basic frame sizes
For your various requirements, the Air Circuit Breaker NA1
includes 5 basic frame sizes as followed.

NA1-3200, 4000
2000A to 4000A

NA1-6300
4000A to 6300A

EU

Netherlands

Ukraine

Russia

South Africa

> >> 01
Air Circuit Breaker
NA1

11
7

12 8

13

14

15
3

02 > >>
Air Circuit Breaker
NA1

NA1 Air Circuit Breaker

1 Drawout type

2 Fixed type

3 Intelligent controller

4 Operating mechanism

5 Auxiliary contact
9
6 Locking-device

10 7 Arcing chamber

8 Secondary connecting part

9 Wire-cable mechanical interlock

10 Connecting-rod type mechanical interlock

11 Shunt release

12 Closing electromagnet

13 Under-voltage release

14 Motor-driven energy-storage mechanism

15 Rotary handle

16 Fixed plate

2
16
6

> >> 03
Air Circuit Breaker
NA1
1. General 2.6 Type designation
1.1 Application scope NA1 - □-□□ / □-□-□-□-□
NA1 series air circuit breaker is suitable for the circuit of
AC 50Hz/60Hz with rated service voltage 400V, 690V and Voltage of secondary circuit
rated service current up to 6300A. It is mainly used to AC220V, AC380V
distribute electric energy and protect circuits and electric DC220V, DC110V
equipment against over-load, under-voltage, short-circuit
and single-phase earthing fault.
With intelligentized and selective protection functions, the Wiring of main circuit:
breaker can improve the reliability of power supply, and avoid H:Horizontal wiring of main circuit
unnecessary power failure. The breaker is applicable for power V:Vertical wiring of main circuit
stations, factories, mines (for 690V) and modern high-buildings,
especially for the distribution system of intelligentized building. Mode of installation:
1.2 Standard: IEC/EN 60947-2. F:Fixed type
D:Draweout type

2. Operation conditions Mode of operation:


M:Manual
2.1 Temperature condition:
P: Power-driven
-5℃~40℃; the average value within 24h
shall not exceed +35℃ (special situation excluded);
2.2 Altitude:≤2000m; No. of poles:
2.3 Pollution grade: Grade 3; 3:3-pole
2.4 Air conditions: 4:4-pole
At mounting site, relative humidity not exceed 50%
at the max temperature of +40℃, higher relative Intelligent controller:
humidity is allowable under lower temperature, M: Standard type
RH could be 90% at +20℃, special measures 3M: Multifunctional type
should be taken to occurrence of dews; 3H: Communication type
2.5 Note: Without the intelligent controller,
the breaker functions as a switch-disconnector.
Rated current:

Frame size
Rated current
rated current
200A
400A
1000A 630A
800A
1000A
630A
800A
1000A
2000A
1250A
1600A
2000A
2000A
3200A
2500A
4000A
3200A
4000A 4000A
4000A
6300A 5000A
6300A

Frame size rated current:


1000A, 2000A, 3200A,4000A, 6300A

Design sequence number

ACB

Company code

04 > >>
Air Circuit Breaker
NA1
3. Structure

+ =

Body
Drawer seat
Drawout type breaker/switch-disconnector

Fixed plate for the fixed type breaker


Fixed type breaker/switch-disconnector

Fault-breaking indicator Under-voltage release


Enclosure
Making button page 58
reset button

Energy storage & Shunt release


Breaking button release indicator page 58

Closing electromagnet
Breaking/making page 58
Name plate
indicator
Auxiliary contact
page 59

Motor-driven energy
Structure for in storage mechanism
and out Locking device page 59
Rotary handle page 60

Rotate out Intelligent controller


Rotate in page 40

> >> 05
Air Circuit Breaker
NA1
4. Main technical parameter
Type NA1-1000

Rated ultimate short circuit breaking capacity Icu=42kA 400V 25kA 690V
Rated service short circuit breaking capacity Ics=30kA 400V 20kA 690V
Rated short-time withstand current Icw=30kA 1s 400V 20kA 1s 690V
Rated current In (A) 200 400 630 800 1000
Number of poles 3, 4
Rated voltage Ue (V) 400
Rated insulation voltage Ui (V) 690
Rated current of N-pole In (A) 50%In
Fixed disconnection time (ms) 23~32
Intelligent Standard type (M)
controller Communication type (H)
Electric life 5000
Operation
Non-maintenance 10,000
performance Mechanical life
Maintenance 20,000
Connection pattern Horizontal, Vertical
Motor operational Drawout 3P/4P 38/55
standard configuration
weight (kg) Fixed 3P/4P 22/26.5

Standard configuration: M type intelligent controller; Under-voltage release; Shunt release; Motor-driven energy-storage mechanism

Type NA1-2000

Rated ultimate short circuit breaking capacity Icu=80kA 400V 50kA 690V
Rated service short circuit breaking capacity Ics=50kA 400V 40kA 690V
Rated short-time withstand current Icw=50kA 1s 400V 40kA 1s 690V
Rated current In (A) 630 800 1000 1250 1600 2000
Number of poles 3, 4
Rated voltage Ue (V) 400, 690
Rated insulation voltage Ui (V) 1000
Rated current of N-pole In (A) 50%In
Fixed disconnection time (ms) 23~32

Intelligent Standard type (M)


controller Communication type (H)
Electric life 5000
Operation
Non-maintenance 10,000
performance Mechanical life
Maintenance 20,000
Connection pattern Horizontal, Vertical
Motor operational Drawout 3P/4P 67.5 / 79.8 69.6 / 83.65 78.6 / 90.5
standard configuration
weight (kg) Fixed 3P/4P 42.4 / 52 44 / 54 45 / 56

06 > >>
Air Circuit Breaker
NA1

Type NA1-3200, NA1-4000

Rated ultimate short circuit breaking capacity Icu=80kA 400V 65kA 690V
Rated service short circuit breaking capacity Ics=65kA 400V 65kA 690V
Rated short-time withstand current Icw=65kA 1s 400V 50kA 1s 690V
Rated current In (A) 2000 2500 3200 4000
Number of poles 3, 4 3
Rated voltage Ue (V) 400, 690
Rated insulation voltage Ui (V) 1000
Rated current of N-pole In (A) 100%In
Fixed disconnection time (ms) 23~32

Intelligent Standard type (M)


controller Communication type (H)
Electric life 5000
Operation
Non-maintenance 10,000
performance Mechanical life
Maintenance 20,000
Connection pattern Horizontal, Vertical
Motor operational Drawout 3P/4P 90.5 / 116 90.5 / 116 102.8 / 131 132 / 172
standard configuration
weight (kg) Fixed 3P/4P 54.8 / 68 54.8 / 68 56.5 / 86 85 / -

Standard configuration: M type intelligent controller; Under-voltage release; Shunt release; Motor-driven energy-storage mechanism

Type NA1-6300

Rated ultimate short circuit breaking capacity Icu=120kA 400V 85kA 690V
Rated service short circuit breaking capacity Ics=100kA 400V 75kA 690V
Rated short-time withstand current Icw=100kA 1s 400V 75kA 1s 690V
rated current In (A) 4000 5000 6300
Number of poles 3, 4 3
Rated voltage Ue (V) 400, 690
Rated insulation voltage Ui (V) 1000
Rated current of N-pole In (A) 100%In
Fixed disconnection time (ms) 23~32

Intelligent Standard type (M)


controller Communication type (H)
Electric life 2500
Operation
Non-maintenance 5000
performance Mechanical life
Maintenance 10,000
Connection pattern Horizontal, Vertical
Motor operational Drawout 3P/4P 202 / 236 202 / 236 236 / -
standard configuration
weight (kg) Fixed 3P/4P -/- -/- -/-

> >> 07
Air Circuit Breaker
NA1
5. Dimensions and connection
NA1-1000 Drawout-type

216 34 Boring dimension of doorcase

268
N 226

H
362

8×φ5

101.5

316
304

358
Installation panel

5
91.5
16
Disconnected
L1 45 position Installation hole on right side
105 158
L 65
A 323

N 27 Connected position
70 70 70
12

200,400A n×φ13
35
NA1-1000 L1 L
12

15
35
3P 194 284
18

n×φ10.5 4P 264 354


630,800,
1000A
In(A) A(mm) n(3P/4P) H(mm)
2×φ8.5 200, 400 32 3/4 6
158

630 50 6/8 8
2-11.5×8.5
800, 1000 50 6/8 10
L1(3P)

L1(4P)

NA1-1000 Fixed-type

Boring dimension of doorcase

268
H

N 226
315

259
101.5

8×φ5
312
270

Installation panel
46.5

216 15 A 9
N 239
3

70 70 70 Installation hole on right side


12
n×φ13
200,400A 35

15
35 53
n×φ10.5
12
18

630,800,
1000A NA1-1000 L1 L In(A) A(mm) n(3P/4P) H(mm)
12

3P 246 274 200, 400 32 3/4 6


4P 316 344 630 50 6/8 8
144

4-9×13
800, 1000 50 6/8 10

L1

08 > >>
Air Circuit Breaker
NA1

NA1-2000 Drawout-type

45(Disconnected position)
448(4P)
8-Φ13
a 353(3P) 60
N pole 28

37.5
a

14
95 95 95 92.5

112

258
439
horizontal connection

42.5
37
92
In A a mm

70
630 10
23
10 97 175
187.5 800~1600 15
421
2000 20
292
465
375(3P)

470(4P)
21.5

155
Φ11

302
268

302
360(4P)

265(3P)

378
N pole
47 20

115
2-11×17

40
Φ14

17
172 32-Φ13 28
55

11-Φ5 Installation panel 60


175 344
33 Right & outer 95 95 95
187.5 side of breaker
Right & outer side of breaker
Opening hole on panel

NA1-2000 Drawout-type, vertical, rear connection

45(Disconnected position) 448(4P)


353(3P)
C Direction

4-φ13
28

60

258
439
122.5

42.5
95.5

70

10
37

10 97 175 187.5
14
292
55 375(3P)
438.5
470(4P)
21.5

In A a mm
155

Φ11 630 10
302
268

302 800~1600 15
378
360(4P)

2000 20
265(3P)

47 20

2-11×17
Φ14
C Direction
172 N pole a
55

11-Φ5 Installation panel


175 344 Right & outer
33
187.5 side of breaker
Right & outer side of breaker
Opening hole on panel
95 95 95 92.5

> >> 09
Air Circuit Breaker
NA1

NA1-2000 Drawout-type, horizontal, rear connection

448(4P)
45(Disconnected position) 353(3P)
C Direction

258
439
122.5

42.5
95.5

37

70
187.5

10 97 175 292
375(3P)
438.5 470(4P)

In A a mm
21.5

630 10
800~1600 15

155
2000 20
Φ11

302
268
360(4P)

302

378
265(3P)

C Direction
47 20

2-11×17
60
Φ14

14
N pole 28 8-φ13
172
55

55
11-Φ5 Installation panel
175

10
33 344 Right & outer
187.5 side of breaker 95 95 95 92.5
Right & outer side of breaker

Opening hole on panel

NA1-2000 Fixed-type

18min 413(4P)
Zero arcing covering
ferreous material 318(3P)
292
In A a mm
a 630 10
115

800 ~1600 15
402

2000 20
a
112

258

8-Φ13
60
N pole 28
55

21

42
60

17

50 150 69.5
11 11
13

290 181

359 345(3P) 95 95 95 86
435(4P)
Horizontal

N Pole
311.2
269

115

4-Φ12
40

300
17
28.5
150

32-Φ13 28
Installation
Installation hole
panel 60
8-φ5 on Right & outer side 2
of breaker
340(3P) Installation hole 342.2 95 95 95
435(4P) on Right & outer side Vertical
of breaker Opening hole on panel

10 > >>
Air Circuit Breaker
NA1

NA1-3200 Drawout-type

528(4P)
45(Disconnected position)
413(3P) In A a mm

a 2000~2500 20
3200 30

a
16-Φ13

258
439
100

25
N pole 50

112

42.5
37

100
92

70

50
217.5
23
10 97 175 92.5
115 125 125
352
491
435(3P)
536 Horizontal
550(4P)
21.5

155

302
268

Φ11
362

378
N pole
440(4P)

115
325(3P)

47 20

40
2-11×17

17
Φ14

32-Φ13 40
202
55

11-Φ5 Installation panel 100


175
33 404
Right & outer 115 125 125
Right & outer side of breaker 217.5 side of breaker
Vertical

Opening hole on panel

NA1-3200 Drawout-type, horizontal, rear connection

528(4P)
45(Disconnected position)
413(3P)
C Direction

8-φ13
50

258

439
126

42.5
100

100

70
37

10 97 175 20 217.5
40 352
435(3P)
94
495 550(4P)
21.5

In A a mm
2000~2500 20
155

3200 30
302
268

Φ11
362
440(4P)

378

C Direction
325(3P)

N pole
47 20

2-11×17 a
Φ14

202
55

11-Φ5 Installation panel


175
33 404 Right & outer
Right & outer side of breaker 217.5 side of breaker
115 115 115 102.5
Opening hole on panel

> >> 11
Air Circuit Breaker
NA1

NA1-3200 Drawout-type, horizontal, rear connection

528(4P)
45(Disconnected position)
413(3P)
C Direction

258
439
112

42.5
107.5

70
37
10 97 175
217.5
352
495 435(3P)
550(4P)
21.5

In A a mm
155 2000~2500 20
3200 30
302
268

Φ11
362
440(4P)

378
325(3P)

47 20

2-11×17 C Direction
Φ14

20
100

40
N pole 50
202
55

11-Φ5 Installation panel

94
175
33 404 Right & outer
Right & outer side of breaker 217.5 side of breaker 16-Φ13

115 125 125 92.5


Opening hole on panel

NA1-3200 Fixed-type

Zero arcing covering 493(4P)


18min
ferreous material 378(3P)
352

a In A a mm
2000~2500 20
115

3200 30
402
a
112

258

16-Φ13
55

86
15

N pole 40
21

72
60

50 150 69.5
11 11
40
13

290 211

389 400(3P)
115 115 115 96
515(4P)
Horizontal

N pole
311
269

115

4-Φ12
40

362
15
28.5
150

32-Φ13 40
Installation hole on 86
8-φ5 Right & outer side of breaker 2 Installation panel
400(3P) 115 115 115
Installation hole on 404
515(4P) Right & outer side of breaker
Opening hole on panel Vertical

12 > >>
Air Circuit Breaker
NA1

NA1-4000 Fixed-type (3P)

18min 493 120 16-Φ13


15

15
Zero arcing covering 40
ferreous material 10

134
15

40
130
30
189.5 189.5 79

Horizontal

402

258
112

21
55
130

11 11
150 69.5

13
50
290 515
424
479

175

40
17
311
269

4-Φ12
362 50
24-Φ15
150

28.5

140
8-φ5 2 Installation panel
207.5 207.5
404 Installation hole on
Installation hole on Right & outer side of breaker
515
Right & outer side of breaker Vertical
Opening hole on panel

NA1-4000 Drawout-type (3P)

45(Disconnected position)

528
30

258
439
112

42.5
92

70
37

10 97 175
217.5

494 352
550
21.5

20
155

Φ11
40
302
268

103

362
378
440

20

12-Φ13
2-11×17
50
47

Φ14
140
202
55

11-Φ5 Installation panel


175 197.5 197.5 77.5
33 404
Right & outer
Right & outer side of breaker 217.5 side of breaker

Opening hole on panel

> >> 13
Air Circuit Breaker
NA1

NA1-4000 Drawout-type (4P)

756
45(Disconnected position)
C Direction

20

439
258
112

42.5

70
92
10 97 175

37
187.5

292
490
788
21.5

155
Φ11

302
268

C Direction
302

378
678

16-φ13

20
N Pole 155

40
20

2-11×17
47

Φ14

103
172
55

11-Φ5 Installation panel


175
33 344
Right & outer 80 50
Right & outer side of breaker 187.5 side of breaker
142.5 206.5 206.5 140

Opening hole on panel

NA1-6300 (In=4000A,5000A) Drawout-type

45(Disconnected position) 903(4P)

813(3P)
30

258

439
42.5
112

37

70
92

217.5

10 97 175 352

835(3P)
494

928(4P)
21.5

155

302
268

Φ11 362
378
818(4P)

N Pole 28-Φ15
703(3P)

20

100 155 210


20

2-11×17
47

Φ14
40
103

202
11-Φ5 Opening hole on panel
55

175 404
33 Right & outer
217.5 side of breaker
Right & outer side of breaker 55
199.5 247 247 170.5
Opening hole on panel

14 > >>
Air Circuit Breaker
NA1

NA1-6300 (In=6300A) Drawout-type (3P)

45(Disconnected position)

903

30

258

439
112

42.5
37
92

70
10 97 175
217.5

494 352

928
21.5

155
Φ11
180 260

302
268

20
362

378
818

40
103
20

2-11×17
47

Φ14
24-Φ15

202 80
55

11-Φ5 Installation panel


175 337 337 138
33 404
Right & outer
Right & outer side of breaker 217.5 side of breaker

Opening hole on panel

> >> 15
Air Circuit Breaker
NA1
6. Secondary circuit wiring
6.1 NA1-1000 Standard type, type (M)

Emergency Motor-driven Motor-driven Motor-driven


Main circuit Intelligent controller Auxiliary contact Auxiliary contact
break break make energy-storage

SB1 SB2 SB3


HL1 HL2 HL3


3 5 7 9 14 15 17 19 21 23 25 27 29 31 33 35 37 39 XT

FU

Intelligent Q F X M
controller
Power of
DF1 DF2 DF3 control circuit
SA DF4

TA

FU

1 2 4 6 8 10 11 12 13 16 18 20 22 24 26 28 30 32 34 36 38 40 XT

DC24V
+ -
Power
module

# #
Hl1: Failure indicator 8 ,9 : Making indicator (capacity AC400V,1A)
HL2: Close indicator 10#: Over-current pre-alarm signal output (selective)
HL3: Energy storage indicator 11#: Short current trip signal output (selective)
SB1: Under-voltage button 12#: Earthing trip alarm output (selective)
SB2: Shunt button 13#: Self-checking alarm signal output (selective)
SB3: Close button 14#: Common line of different contacts
Q: Under-voltage release 15#: Earthing protection line
F: Shunt release # #
16 ,17 : Normal contact of the controller
X: Close electromagnet (contact capacity AC400V 1A)
M: Energy storage motor 27#,28#: Under-voltage release
DF1-F4: Auxiliary switch 29#,30#: Shunt release
1#, 2#: Auxiliary power input(DC24V) 31#,32#: Closing electromagnet
3#,4#,5#: Fault trip contact output(4# common terminal, 33#,34#,35#: Energy storage motor
contact capacity AC230V,5A 18#~26#, 36#~38#: Auxiliary contact
6#,7#: To be connected with current transformer(selective) (auxiliary contact capacity: AC230V,5A)

Note:
Dashed is to be connected by users.

16 > >>
Air Circuit Breaker
NA1

Communication type, type (H)

Emergenay Motor-driven Motor-driven


Main circuit Intelligent controller break break make Auxiliary switch

L1 FU
N
PE

Profibus-DP L N PE

ST-4 Power module


- + - + - + - + HL3
ST-DP
Device
12 13 14 15 16 17 18 19

Fault indicator 1 2 3 4 5 6 7 8 9 10 11
+ + D11D12 D13
DC24V COM
Green ST201 SB1 SB2 SB3
D01 D02 D03
HL1 HL2 12 13 14 15 16 17

Red
3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 XT

Intelligent Q F X M
controller
SA

DF1 DF2 DF3

TA

1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 XT
DC24V
+ -
Power
module

Hl1: Failure indicator # #


8 ,9 : Making indicator(capacity AC400V,1A)
HL2: Close indicator
10#, 11#: communication output
HL3: Energy storage indicator
SB1: Under-voltage button 12#, 13#: Signal alarm of load 1 output
SB2: Shunt button 14#, 15#: Signal alarm of load 2 output
SB3: Close button 16#, 17#: Making signal output
Q: Under-voltage release 18#, 19#: Closing signal output
F: Shunt release 20#: Communication shield ground line
# #
X: Close electromagnet 21 ~24 : Voltage signal input of phase N,A,B,C
# #
M: Energy storage motor 25 , 26 : Auxiliary contact (capacity:AC230V,5A)
DF1-F4: Auxiliary switch 27#,28#: Under-voltage release
1#, 2#: Auxiliary power input(DC24V) 29#,30#: Shunt release
3#,4#,5#: Fault trip contact output(4# common terminal, 31#,32#: Closing electromagnet
contact capacity AC230V,5A 33#,34#,35#: Energy storage motor
6#, 7#: To be connected with current transformer(N/O auxiliary 36#~40#: Auxiliary contact (capacity:AC230V,5A)
contact, capacity AC400V, 1A,when no current transformer)

Note:
Dashed is to be connected by users.

> >> 17
Air Circuit Breaker
NA1

6NO(normal open) 6NC (normal close) standard type (M)

Main Auxiliary Emergency Motor-driven Motor-driven Motor-driven


circuit Intelligent controller contact break break make energy-storage
Auxiliary contact

SB1 SB2 SB3


HL1 HL2 HL3


3 5 7 9 14 15 17 19 21 23 25 27 29 31 33 35 37 39 XT

FU

Q F X M
Intelligent Power of
controller control circuit
DF5 DF6 DF1 DF2 DF3
SA DF4

TA

FU

1 2 4 6 8 10 11 12 13 16 18 20 22 24 26 28 30 32 34 36 38 40 XT

+ -
DC24V Power
module

Hl1: Failure indicator 8#,9#: Making indicator (capacity AC400V,1A)


HL2: Close indicator 12#~26#: Auxiliary contact(auxiliary
HL3: Energy storage indicator contact capacity: AC230V,5A)
SB1: Under-voltage button 27#,28#: Under-voltage release
SB2: Shunt button 29#,30#: Shunt release
SB3: Close button 31#,32#: Closing release
Q: Under-voltage release 33#,34#:Energy storage indicator
F: Shunt release 34#,35#: Energy storage motor
X: Close release 38#~40#: Auxiliary contact(auxiliary
M: Energy storage motor contact capacity: AC230V,5A)
DF1-DF4: Auxiliary switch
1#, 2#: Auxiliary power input(DC24V)
3#,4#,5#: Fault trip contact output(4# common
terminal,contact capacity AC230V,5A
6#, 7#: to be connected with current
transformer(selective)

Note:
6NO(normal open) 6NC(normal close), without any additional function.
Dashed is to be connected by users.

18 > >>
Air Circuit Breaker
NA1
6.2 NA1-2000~3600
The secondary circuit wiring for NA1-2000~3600 with standard type (M) intelligent controller and instantaneous under-voltage release

Emergency
Main circuit Over-current release break
Motor-driven Motor-driven
make
Auxiliary contact
break

SB2

Failure Energy storage


SB1 SB3

3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 36 38 40 42 44 46 48 50

FU
Q F X M

SA
AX
Power

Processing
unit
Intelligent Controller

FU

1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 37 39 41 43 45 47 49 51

Open Close

_ 110V
~
_ 220V Intelligent release power ("1" connect positive pole, and "2" connect negative pole for direct current)
~
~380V

SB1: Shunt button


The auxiliary contact modes for customer use SB2: Under-voltage button
SB3: Making button
Ⅰ Four switch contact (acquiescence) Ⅱ Five switch contact Q: Under-voltage release
F: Shunt release
36 38 40 42 44 46 36 38 40 42 44 46 48 50
X: Closing electromagnet
M: Energy storage motor
XT: Connection terminal
SA: Position switch
Note: If control voltage of Q, F, X is different from each other,
they can be connected to different power.
37 39 41 43 45 47 37 39 41 43 45 47 49

Circuit explanation for signal output:


a. Broken-line parts shall be provided by customers.
# #
b. Terminals 6 ,7 can output NC (normal close) contact if that is required by users.
#
c. Terminal 35 can be directly connected to power (automatic pre-storing energy),
alternatively connect power after connecting NO button (manual-controlled
pre-storing energy).
d. Terminals 21#~24# is only for wiring with function meter display.
(excluding the special wiring)

> >> 19
Air Circuit Breaker
NA1

The secondary circuit wiring for NA1-2000~6300 with type (3M) intelligent controller and instantaneous under-voltage release

1 2
L1
N
PE

to the incoming-line side


PE Un U1 U2 U3 SB2 SB1 SB3
Transformer
connected

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

Q F X

AX
M

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Energy-
Fault storage Open Close

Main Shunt Closing Energy- Energy-


circuit
Intelligent controller Undervoltage storage storage Auxiliary switch
release release electromagnet indication motor

The auxiliary contact modes for customer use SB1: Shunt button
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence) Ⅱ Five switch contact
SB3: Making button
# #
36 38 40 42 44 46 36 38 40 42 44 46 48 50 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
# #
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
# #
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
# #
of the DC power supply module, and the 1 ~2 connect to
37 39 41 43 45 47 37 39 41 43 45 4 7 49 the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.

# #
12 ~19 : The programmable output terminal. The normal products without these terminals,
but if the customer special ordered, the cost extra added.

M type acquiescence output:


# #
12 ,13 : Signal alarm of load 1 output
14 ,15 #: Signal alarm of load2 output
#

# # # #
16 ,17 : Self-diagnose alarm; 18 ,19 : Fault trip
# # #
20 : PE line; 21 ~24 : Display the voltage of the signal input.
The normal products without these terminals,
if the customer special ordered the function meter, the cost extra added.
#
21 : N phase input terminal
22 # ,23 # ,24 # : A, B, C three phase power input terminal (note the sequence)
25 # ,26 # : Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.

Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
( If the voltage exceeds 400V, special explanation when ordered)

20 > >>
Air Circuit Breaker
NA1

The secondary circuit wiring for NA1-2000~6300 with type (3H) intelligent controller and instantaneous under-voltage release

1 2
L1
N
PE
To TO3 busbar 1 2 3 4 5
ST Power Supply
L N L N PE Modular IV
Profibus-DP - + - + -+ - +

ST-DP 12 13 14 15 16 17 18 19

Device + - + -
1 2 3 4 5 6 7 8 9 10 11
Special connecting wire
D11D12D13
To the inconnecting-line side DO24VDO24VCOM
Modbus-RTV PE Un U1 U2 U3 SB2 SB1 SB3 ST201
DO1 DO3
Transformer 12 13 14 15 16 17 18 19
connected
Red Green

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

Q F X

AX
M

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Energy
Fault
storage Open Close

Main Closing Energy-


circuit
Intelligent controller Undervoltage Shunt
release
Energy-
electromagnet storage storage Auxiliary switch
release indication motor

The auxiliary contact modes for customer use SB1: Shunt button
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence) Ⅱ Five switch contact
SB3: Making button
# #
36 38 40 42 44 46 36 38 40 42 44 46 48 5 0 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
is AC power, the 1#~2# connects to the AC power directly.
When the power supply is DC power, forbid connecting the
1#~2# to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
37 39 4 1 43 45 47 37 39 41 4 3 4 5 47 49
of the DC power supply module, and the 1#~2# connect to
the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.

# #
12 ,13 : Signal alarm of load 1 output
# #
14 ,15 : Signal alarm of load2 output
# #
16 ,17 :Breaking signal output
# #
18 ,19 :Making signal output
# #
20 : PE line; 21 : N phase input terminal
# # #
22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence)
25#26#: Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
ST~DP: DP protocol module. There is no need for the ST-DP protocol module,
if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP,
the ST-DP protocol module is necessary, but the cost extra added.
ST power module IV: power converter (optional components)
ST201: Magnify the signal capacity of the controller. ( optional components) If the customer special ordered,
the cost extra added.

Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
(If the voltage exceeds 400V, special explanation when ordered)

> >> 21
Air Circuit Breaker
NA1

The secondary circuit wiring for NA1-2000~6300 with standard type (M) intelligent controller and time-delay under-voltage release

Main Emergency Motor Motor Motor


driven Under-voltage
Over-current release driven driven energy time-delay Auxiliary switch
circuit disconnection break close storage release

SB2 SB1 SB3 Energy


storage

Failure Under-voltage
time-delay controller

3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 36 38 40 42 44 46 48 50

FU

AX
Power

Processing
unit
Intelligent controller

FU

1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 37 39 41 43 45 47 49 51

Open Close

~_ 110V
Intelligent release power(”1” connect positive pole, and “2” connect negative pole for direct current)
~_ 220V
~380V

The auxiliary contact modes for customer use


Ⅰ Four switch contact (acquiescence)

38 40 4 2 44 46 4 8 50

39 4 1 43 45 47 49

SB1: Shunt button SB2: Under-voltage button SB3: Making button


Q: Under-voltage time-delay release F: Shunt release
X: Closing electromagnet M: Energy storage motor
XT: Connection terminal SA: Position switch
Note: If control voltage of Q, F, X is different from each other, they can be connected to different power.

Circuit explanation for signal output:


a. Broken-line parts shall be provided by customers.
b. Terminals 6#,7# can output NC (normal close) contact if that is required by users.
#
c. Terminal 35 can be directly connected to power (automatic pre-storing energy),
alternatively connect power after connecting NO button (manual-controlled pre-storing energy).
d. The 21#~24# is only for wiring with function meter display. (Excluding the special wiring)

22 > >>
Air Circuit Breaker
NA1

The secondary circuit wiring for NA1-2000~6300 with type (3M) intelligent controller and time-delay under-voltage release

1 2
L1
N
PE

SB2 SB1 SB3

To the incoming-line side


PE Un U1 U2 U3

Transformer
Under-voltage
connected time-delay controller

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

F X Q

AX
M

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51
Energy
Fault storage Open Close

Energy- Energy-
Main Shunt Closing Under-voltage
circuit
Intelligent controller Emergency release electromagnet
storage storage time-delay
release
Auxiliary switch
break indication motor

SB1: Shunt button


The auxiliary contact modes for customer use
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence)
SB3: Making button
# #
38 40 42 44 46 48 50 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
# #
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
# #
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
# #
of the DC power supply module, and the 1 ~2 connect to
39 41 43 45 47 49 the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.

12#~19# are the programmable output terminal. The normal products without these terminals,
but if the customer special ordered, the cost extra added.

M type acquiescence output:


12#,13#: Signal alarm of load 1 output
14#,15#: Signal alarm of load2 output
16#,17#: Self-diagnose alarm; 18#,19#: Fault trip
20#: PE line; 21#~24#: Display the voltage of the signal input. The normal products without these terminals,
if the customer special ordered the function meter, the cost extra added.
# # # #
21 : N phase input terminal; 22 ,23 ,24 : A, B, C three phase power input terminal (note the sequence)
# #
25 ,26 Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.

Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2. (If the voltage exceeds 400V,
special explanation when ordered)

> >> 23
Air Circuit Breaker
NA1

The secondary circuit wiring for NA1-2000~6300 with type (3H) intelligent controller and time-delay under-voltage release

1 2
L1
N
PE
To TO3 busbar 1 2 3 4 5
STPower Supply
L N L N PE Modular IV
Profibus-DP - + - + - + - +

ST-DP 12 13 14 15 16 17 18 19

+ -
1 2 3 4 5 6 7 8 9 10 11
Device D11D12D13
SB2 SB1 SB3 DO24VDO24VCOM
Special connecting wire
ST201
To the inconnecting-line side DO1 DO3
Modbus-RTV PE Un U1 U2 U3 12 13 14 15 16 17 18 19

Transformer
Under-voltage
connected
Red Green time-delay controller

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50

F X Q

AX
M

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51

Fault Energy
storage Open Close

Main Energy Energy


Shunt Under-voltage
circuit
Intelligent controller Emergency release
Closing
electromagnet
storage storage time-delay
release
Auxiliary switch
indication motor
break

The auxiliary contact modes for customer use SB1: Shunt button
SB2: Under-voltage button
Ⅰ Four switch contact (acquiescence)
SB3: Making button
# #
38 40 42 44 46 48 50 1 , 2 : Intelligent controller power input
Note: When the power supply of the intelligent controller
# #
is AC power, the 1 ~2 connects to the AC power directly.
When the power supply is DC power, forbid connecting the
# #
1 ~2 to the DC power directly. Add a DC power supply
module, then the DC power connect to the input terminal
# #
of the DC power supply module, and the 1 ~2 connect to
39 41 43 45 47 49
the output terminal of the DC power supply module,
or else the intelligent controller will be damaged.
12#,13#: Signal alarm of load 1 output
14#,15# : Signal alarm of load 2 output
16#,17#: Breaking signal output; 18#,19#: Closing signal output
20#: PE line; 21#: N phase input terminal
22#,23#,24#: A, B, C three phase power input terminal (note the sequence)
25#,26# Connect to the N phase current transformer or the input terminal of the current leakage transformer.
The normal products without these terminals, if the customer special ordered, the cost extra added.
ST~DP: DP protocol module. There is no need for the ST-DP protocol module,
if the communication protocol is Modbus-RTV. But when the communication protocol is Profibus-DP,
the ST-DP protocol module is necessary, but the cost extra added.
ST power module IV: power converter (optional components)
ST201: Magnify the signal capacity of the controller. ( optional components)
If the customer special ordered, the cost extra added.

Note:
a. Red colored part is to be connected by users
b. When the power system is three phase three wire, directly connect the Un to U2.
(If the voltage exceeds 400V, special explanation when ordered)

24 > >>
Air Circuit Breaker
NA1
7. Installation
7.1 Installation
7.1.1 Unload the breaker from the soleplate of package. When the guide rod points to separated position and handle
If it is drawout type, firstly pull out the handle under can't be rotated any longer, pull out the handle and firmly
the drawer-base of breaker, and plug it into the hole grasp the aluminum handle on drawer-base, pull out the
on central part of plastic cover under the drawer-base breaker body and remove it form the base, then move the
crossbeam, anticlockwise turns the handle, the body base from the sole plate and clean up the dirty things inside
will slowly slide along the outside of drawer-base. the drawer-base.

Possible positions

7.1.2 Check the insulation resistance with a 500V megger, 7.1.3 Power supply
resistance should not be less than 20M Ω when NA1 devices can be supplied either from the top or
ambient temperature is 20 ℃± 5 ℃ and relative from the bottom without reduction in performance,
humidity is 50%~70%. Otherwise dry it. in order to facilitate connection when installed in a
switchboard.

> >> 25
Air Circuit Breaker
NA1
7.1.4 Put the breaker (fixed-type) or drawer-base (drawout-type) Mounting the circuit-breaker
into the installation-bracket, and make it fixed, directly It is important to distribute the weight of the device
connect the cable wire of main circuit to the bus wire of uniformily over a rigid mounting surface such as rails
fixed-type circuit breaker. Alternatively put breaker body or a base plate.
onto the slideway of drawer-base. Plug the handle into This mounting plane should be perfectly flat (tolerance
installation hole, clockwise turns it until the under-part of on support flatness: 2 mm).This eliminates any risk of
drawer-base points at the connection position and ”click” deformation which could interfere with correct
sound is heard. It indicates that breaker body has been operation of the circuit breaker.
connected to its place, then connect the cable of main NA1 devices can also be mounted on a vertical plane
circuit to drawer-base. using the special brackets.

Mounting with vertical brackets Mounting on rails

7.1.5 Partitions
A:non magnetic material
Sufficient openings must be provided in partitions to ensure
good air circulation around the circuit breaker;
Any partition between upstream and downstream connections
of the device must be made of nonmagnetic material.
For high-currents, of 2500 A and upwards, the metal supports
or barriers in the immediate vicinity of a conductor must
be made of non-magnetic material A;Metal barriers through
which a conductor passes must not form a magnetic loop.
A

Busbars
The mechanical connection must be exclude the possibility non magnetic material
of formation of a magnetic loop around a conductor.

26 > >>
Air Circuit Breaker
NA1
7.1.6 Busbar connections
The busbars should be suitably adjusted to ensure the
connection points are positioned on the terminals before
the bolts are inserted B The connections are held by the
supporter which is fixed to the framework of the
switchboard, in this way the circuit breaker terminals
do not have to support its weight C.
(This support should be placed close to the terminals).

B C B

7.1.7 Main circuit adopts cable connection


Users should not apply too strong mechanical strength on
the terminals of Air Circuit Breaker. Extend the bus-bar of
circuit breaker with connecting bus-bar, position the wiring
piece of cable before inserting bolts; the cable should be
fixed on the frame of distributing cabinet firmly.

18min 18min

> >> 27
Air Circuit Breaker
NA1
7.1.8 Clamping 1 2 3 4
Correct clamping of busbars depends on the tightening
torques used for the nuts and bolts,etc. Over-tightening
may have the same consequences as under-tightening.

For connecting busbars to the circuit breaker, the tightening


torques to be used are shown in the table below. These
values are for use with copper busbars and steel nuts and 1 breaker terminal
bolts, class 8.8. 2 busbar
3 bolt
4 washer
5 nut
5

Examples

Preferred tightening torque for NA1's tightening components

Type of screw Application Preferred tightening torque

M4 Screws for secondary terminals 11 Nm

M10 Installing bolts of Air Circuit Breaker 45 Nm

M12 Connection terminals 50 Nm

Connected position Test position Disconnected position Drawout position

[Link] main circuit and control [Link] main circuit is disconnected,


circuit are connected. and the control circuit is connected. Neither the main circuit Main body is out
[Link] application conditions [Link] application conditions. nor the control circuit is connected. of the drawer seat.

28 > >>
Air Circuit Breaker
NA1
7.2 Wiring the secondary circuit according to electric principle
diagram.
Note: Bolts, nuts, gaskets shouldn't be left inside the drawer
seat to avoid being blocked. Secondary connecting part
Arcing chamber
7.3 Operation
Check the rated voltage of the following components
Main body
whether conforms to the power voltage . Such as under
voltage release, shunt release, closing electromagnet,
motor-driven mechanism and intelligent controller. Drawer seat

7.4 Maintenance
Check the technical parameters in time or add some
lubricating oil, etc.
This breaker structure is arranged vertically and modularized
composition with each functioncell separated, which make
the maintenance easy.
It has compact structure, reliable operation and strong free Handle Slideway

maintenance capability. Please check the technical parameters


on the nameplate in accordance with the requirements of
order before installation.

Making the secondary circuit power, the motor-driven Manual energy-storage


mechanism can store energy automatically until hearing the click
and energy stored indicating on the panel.

Otherwise press the storage handle for 6 times until hearing


the click and the indicator display energy stored

And the closing operation can be realized either by closing


electromagnet or manual button.

Shake with the manual energy-storage handle


up and down about six times to "click".

8. Recommendation for user's connecting bus-bar


Inm(A) NA1-1000 NA1-2000 NA1-3200 NA1-4000 NA1-6300
In(A) 200 400 630 800 1000 630 800 1000 1250 1600 2000 2000 2500 2900 3200 4000/3P 4000/4P 4000 5000 6300
Thickness(mm) 5 5 5 6 8 5 6 8 10 12 10 8 10 10 10 10 10 10 10 10
Busbar Width(mm) 30 30 40 50 50 60 60 60 60 60 60 100 100 100 100 120 120 120 100 100
Number 1 2 2 2 2 2 2 2 2 2 3 2 2 4 4 4 4 4 7 8

Note: the specifications in the table is obtained as the ambient temperature of air circuit breaker is 40℃, with open installation; this is in
compliance with the specification of copper busbars adopted under the heating conditions regulated in IEC/EN60947-2.

9. Power loss
Inm(A) NA1-1000 NA1-2000 NA1-3200 NA1-4000 NA1-6300
In(A) 200 400 630 800 1000 630 800 1000 1250 1600 2000 2000 2500 3200 4000/3P 4000/4P 4000 5000 6300
Power Drawer type 40 101 123 110 177 70 110 172 268 440 530 384 600 737 921 900 575 898 1426
loss (W) Fixed type 33 85 107 94 476 34.4 50 78 122 200 262 200 312 307 - - - - -

> >> 29
Air Circuit Breaker
NA1
10. A2S curve

I2t(A2s×106)
741

341

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
20 40 60 80 100 120 Is(kA)

Is: prospective symmetrical current(of an a.c. circuit)

11. Temperature compensation correction


Ambient NA1-3200
Standard NA1-1000 NA1-2000 NA1-6300
temperature NA1-4000
40℃ 200 400 630 800 1000 630 800 1000 1250 1600 2000 2000 2500 3200 4000 4000 5000 6300
45℃ 195 395 623 790 985 630 800 1000 1250 1600 1900 2000 2400 3000 3800 4000 5000 6000
50℃ 192 384 605 768 960 630 800 1000 1250 1500 1900 2000 2300 3000 3600 4000 5000 5600
IEC/EN60947-2
55℃ 182 328 584 725 924 630 800 1000 1200 1500 1800 2000 2200 2800 3400 4000 4800 5400
60℃ 174 248 548 696 870 610 800 1000 1150 1300 1700 2000 2200 2800 3200 4000 4800 5200
65℃ 163 192 500 620 810 610 800 1000 1150 1300 1650 2000 2200 2600 3200 4000 4800 5100

Note: The ACB is to calibrated at 40℃, special application please refer to the table above and the curve below.

30 > >>
Air Circuit Breaker
NA1

1200 5000
4800
1100
4600
1000 In=1000A 4400
900
4200
4000 In=4000A
Rated current (A)

800 In=800A 3800

Rated current (A)


700
3600
In=630A 3400
600 3200 In=3200A
500 3000
2800
400 In=400A 2600 In=2500A
2400
300
In=200A 2200
In=2000A
200 2000
1800
100
40 45 50 55 60 65 70
0
40 45 50 55 60 65 70

Ambient temperature(℃)
Ambient temperature(℃) NA1-3200, NA1-4000
NA1-1000

2000 7000
In=2000A
1900 6800
1800 6600
1700 6400
In=1600A
1600 6200
1500 6000
Rated current (A)

In=6300A
5800
Rated current (A)

1400
In=1250A
1300 5600
1200 5400
1100 5200 In=5000A
In=1000A
1000 5000
900 4800
In=800A
800 4600
700 In=630A 4400
600 4200
In=4000A
500 4000
400 3800

40 45 50 55 60 65 70 40 45 50 55 60 65 70

Ambient temperature(℃) Ambient temperature(℃)


NA1-2000 NA1-6300

> >> 31
Air Circuit Breaker
NA1
12. Coordination recommendations

Capacity of transformer Breaking capacity of


Rated current Short circuit current
(kVA) & parallelly air circuit breaker for
of transformer In(A) of main circuit (kA)
connected number main circuit (kA)

1×250 360 9 9
2×250 360 9 9
3×250 360 9 18.5
1×315 455 11.4 11.4
2×315 455 11.4 11.4
3×315 455 11.4 22.7
1×400 578 14.4 14.4
2×400 578 14.4 14.4
3×400 578 14.4 28.8
1×500 722 18 18
2×500 722 18 18
3×500 722 18 36.1
1×630 910 22.7 22.7
2×630 910 22.7 22.7
3×630 910 22.7 44.5
1×800 1154 19.3 19.3
2×800 1154 19.3 19.3
3×800 1154 19.3 38.5
1×1000 1444 24 24
2×1000 1444 24 24
3×1000 1444 24 48.1
1×1250 1805 30 30
2×1250 1805 30 30
3×1250 1805 30 60.1
1×1600 2310 36.5 36.5
2×1600 2310 36.5 36.5
3×1600 2310 36.5 73
1×2000 2887 48.2 48.2
2×2000 2887 48.2 48.2
3×2000 2887 48.2 96.3
1×2500 3608 60 60
2×2500 3608 60 60
1×3150 4550 75.8 75.8
2×3150 4550 75.8 75.8

32 > >>
Air Circuit Breaker
NA1

Type of air circuit Number and area of the Breaking capacity of


busbar for main circuit Air circuit breaker
breaker for air circuit breaker
for branch circuit
main circuit (n×W×T) for branch circuit (kA)

NA1-1000-400 9
NA1-1000-400 2×(5×30) 18.5 NA1, NM8
NA1-1000-400 27.5
NA1-1000-630 11.4
NA1-1000-630 2×(5×40) 22.7 NA1, NM8
NA1-1000-630 34.1
NA1-1000-630 14.4
NA1-1000-630 2×(5×40) 28.8 NA1, NM8
NA1-1000-630 43.2
NA1-1000-800 18
NA1-1000-800 2×(6×50) 36.1 NA1, NM8
NA1-1000-800 54.1
NA1-1000-1000 22.7
NA1-1000-1000 2×(8×50) 44.5 NA1, NM8
NA1-2000-1000 67.2
NA1-2000-1250 19.3
NA1-2000-1250 2×(10×60) 38.5 NA1, NM8
NA1-2000-1250 57.8
NA1-2000-1600 24
NA1-2000-1600 2×(12×60) 48.1 NA1, NM8
NA1-2000-1600 72.1
NA1-2000-2000 30
NA1-2000-2000 3×(10×60) 60.1 NA1, NM8
NA1-2000-2000 90.1
NA1-3200-2500 36.5
NA1-3200-2500 2×(10×100) 73 NA1, NM8
NA1-3200-2500 109.5
NA1-3200-3200 48.2
NA1-3200-3200 4×(10×100) 96.3 NA1, NM8
NA1-3200-3200 144.5
NA1-6300-4000 60
4×(10×120) NA1, NM8
NA1-6300-4000 120
NA1-6300-5000 75.8
7×(10×100) NA1, NM8
NA1-6300-5000 151.6

> >> 33
Air Circuit Breaker
NA1
13. Selectivity protection
13.1 Selective protection between NM8 and NA1

Circuit breaker NA1-2000

Rated
400 630 800 1000 1250
current (A)
Default setting ratings
3.2 5.04 6.4 8 10
of short time-delay 8In (kA)

Downstream Upstream Setting


0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75
range (kA)

Delayed tripping
0.1, 0.2, 0.3, 0.4
time (s)
Returnable time 0.06, 0.14, 0.23, 0.35
Frame size Rated Instantaneous
rated current current (A) setting ratings (kA)

0.16 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75


16
0.19(motor) 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75

0.2 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75


20
0.24(motor) 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75

0.25 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75


25
0.30(motor) 0.414~6 0.63~9.45 0.8~12 1~15 1.25~18.75

0.32 0.4416~6 0.63~9.45 0.8~12 1~15 1.25~18.75


32
0.38(motor) 0.5224~6 0.63~9.45 0.8~12 1~15 1.25~18.75

0.40 0.552~6 0.63~9.45 0.8~12 1~15 1.25~18.75


40
NM8-125 0.48(motor) 0.6624~6 0.6624~9.45 0.8~12 1~15 1.25~18.75
NM8S-125 0.50 0.69~6 0.69~9.45 0.8~12 1~15 1.25~18.75
50
0.60(motor) 0.828~6 0.828~9.45 0.828~12 1~15 1.25~18.75

0.63 0.8694~6 0.8694~9.45 0.8694~12 1~15 1.25~18.75


63
0.75(motor) 1.035~6 1.035~9.45 1.035~12 1.035~15 1.25~18.75

0.80 1.104~6 1.104~9.45 1.104~12 1.104~15 1.25~18.75


80
0.96(motor) 1.325~6 1.325~9.45 1.325~12 1.325~15 1.325~18.75

1.0 1.38~6 1.38~9.45 1.38~12 1.38~15 1.38~18.75


100 1.20(motor) 1.656~6 1.656~9.45 1.656~12 1.656~15 1.656~18.75

1.25 1.725 ~6 1.725~9.45 1.725~12 1.725~15 1.725~18.75


125 1.5(motor) 2.07~6 2.07~9.45 2.07~12 2.07~15 2.07~18.75

1.0 1.38~6 1.38~9.45 1.38~12 1.38~15 1.38~18.75


100
1.2(motor) 1.656~6 1.656~9.45 1.656~12 1.656~15 1.656~18.75

1.6 2.208~6 2.208~9.45 2.208~12 2.208~15 2.208~18.75


160
NM8-250 1.92(motor) 2.65~6 2.65~9.45 2.65~12 2.65~15 2.65~18.75
NM8S-250 2.0 2.76~6 2.76~9.45 2.76~12 2.76~15 2.76~18.75
200
2.4(motor) 3.312~6 3.312~9.45 3.312~12 3.312~15 3.312~18.75

2.5 3.45~6 3.45~9.45 3.45~12 3.45~15 3.45~18.75


250
3.0(motor) 4.14~6 4.14~9.45 4.14~12 4.14~15 4.14~18.75

34 > >>
Air Circuit Breaker
NA1

NA1-3200 NA1-4000 NA1-6300

1600 2000 2000 2500 3200 3200 4000 4000 5000 6300

16 16 20 25.6 25.6 32 32 40 50.4

2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5

0.1, 0.2, 0.3, 0.4

0.06, 0.14, 0.23, 0.35

1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5

1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.656~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5

1.725~24 1.725~30 1.725~30 1.725~37.7 1.725~48 1.725~48 1.725~60 1.725~60 1.725~75 1.725~94.5
2.07~24 2.07~30 2.07~30 2.07~37.7 2.07~48 2.07~48 2.07~60 2.07~60 2.07~75 2.07~94.5
1.6~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
1.656~24 2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
2.208~24 2.208~30 2.208~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
2.65~24 2.65~30 2.65~30 2.65~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
2.76~24 2.76~30 2.76~30 2.76~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5
3.312~24 3.312~30 3.312~30 3.312~37.7 3.312~48 3.312~48 4~60 4~60 5~75 6.3~94.5
3.45~24 3.45~30 3.45~30 3.45~37.7 3.45~48 3.45~48 4~60 4~60 5~75 6.3~94.5
4.14~24 4.14~30 4.14~30 4.14~37.7 4.14~48 4.14~48 4.14~60 4.14~60 5~75 6.3~94.5

> >> 35
Air Circuit Breaker
NA1

Circuit breaker NA1-2000

Rated
400 630 800 1000 1250
current (A)
Default setting ratings
3.2 5.04 6.4 8 10
of short time-delay 8In (kA)
Setting
Downstream Upstream 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75
range (kA)
Delayed tripping
0.1, 0.2, 0.3, 0.4
time (s)
Returnable time 0.06, 0.14, 0.23, 0.35
Frame size Rated Instantaneous
rated current current (A) setting ratings (kA)

2.5 3.45~6 3.45~9.45 3.45~12 3.45~15 3.45~18.75


250
3.0(motor) 4.14~6 4.14~9.45 4.14~12 4.14~15 4.14~18.75

3.15 4.347~6 4.347~9.45 4.347~12 4.347~15 4.347~18.75


315
3.78(motor) 5.216~6 5.216~9.45 5.216~12 5.216~15 5.216~18.75
NM8-630 3.5 4.83~6 4.83~9.45 4.83~12 4.83~15 4.83~18.75
350
NM8S-630 4.2(motor) 5.796~6 5.796~9.45 5.796~12 5.796~15 5.796~18.75

4.0 5.52~6 5.52~9.45 5.52~12 5.52~15 5.52~18.75


400
4.8(motor) 6.624~9.45 6.624~12 6.624~15 6.624~18.75

5.0 6.9~9.45 6.9~12 6.9~15 6.9~18.75


500
6.0(motor) 8.28~9.45 8.28~12 8.28~15 8.28~18.75

6.3 8.694~9.45 8.694~12 8.694~15 8.694~18.75


NM8S-630 630
7.56(motor) 10.44~12 10.44~15 10.44~18.75

6.3 8.694~9.45 8.694~12 8.694~15 8.694~18.75


630
7.56(motor) 10.44~12 10.44~15 10.44~18.75

7.0 9.66~12 9.66~15 9.66~18.75


700
8.4(motor) 11.59~12 11.59~15 11.59~18.75
NM8-1250 8.0 11.04~12 11.04~15 11.04~18.75
800
NM8S-1250 9.6(motor) 13.25~15 13.25~18.75

10 13.8~15 13.8~18.75
1000
12(motor) 16.56~18.75

12.5 17.25~18.75
1250
15.0(motor)

36 > >>
Air Circuit Breaker
NA1

NA1-3200 NA1-4000 NA1-6300

1600 2000 2000 2500 3200 3200 4000 4000 5000 6300

16 16 20 25.6 25.6 32 32 40 50.4

2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5

0.1, 0.2, 0.3, 0.4

0.06, 0.14, 0.23, 0.35

3.45~24 3.45~30 3.45~30 3.45~37.7 3.45~48 3.45~48 4~60 4~60 5~75 6.3~94.5
4.14~24 4.14~30 4.14~30 4.14~37.7 4.14~48 4.14~48 4.14~60 4.14~60 5~75 6.3~94.5
4.347~24 4.347~30 4.347~30 4.347~37.7 4.347~48 4.347~48 4.347~60 4.347~60 5~75 6.3~94.5
5.216~24 5.216~30 5.216~30 5.216~37.7 5.216~48 5.216~48 5.216~60 5.216~60 5.216~75 6.3~94.5
4.83~24 4.83~30 4.83~30 4.83~37.7 4.83~48 4.83~48 4.83~60 4.83~60 5~75 6.3~94.5
5.796~24 5.796~30 5.796~30 5.796~37.7 5.796~48 5.796~48 5.796~60 5.796~60 5.796~75 6.3~94.5
5.52~24 5.52~30 5.52~30 5.52~37.7 5.52~48 5.52~48 5.52~60 5.52~60 5.52~75 6.3~94.5
6.624~24 6.624~30 6.624~30 6.624~37.7 6.624~48 6.624~48 6.624~60 6.624~60 6.624~75 6.624~94.5
6.9~24 6.9~30 6.9~30 6.9~37.7 6.9~48 6.9~48 6.9~60 6.9~60 6.9~75 6.9~94.5
8.28~24 8.28~30 8.28~30 8.28~37.7 8.28~48 8.28~48 8.28~60 8.28~60 8.28~75 8.28~94.5
8.694~24 8.694~30 8.694~30 8.694~37.7 8.694~48 8.694~48 8.694~60 8.694~60 8.694~75 8.694~94.5
10.44~24 10.44~30 10.44~30 10.44~37.7 10.44~48 10.44~48 10.44~60 10.44~60 10.44~75 10.44~94.5
8.694~24 8.694~30 8.694~30 8.694~37.7 8.694~48 8.694~48 8.694~60 8.694~60 8.694~75 8.694~94.5
10.44~24 10.44~30 10.44~30 10.44~37.7 10.44~48 10.44~48 10.44~60 10.44~60 10.44~75 10.44~94.5
9.66~24 9.66~30 9.66~30 9.66~37.7 9.66~48 9.66~48 9.66~60 9.66~60 9.66~75 9.66~94.5
11.59~24 11.59~30 11.59~30 11.59~37.7 11.59~48 11.59~48 11.59~60 11.59~60 11.59~75 11.59~94.5
11.04~24 11.04~30 11.04~30 11.04~37.7 11.04~48 11.04~48 11.04~60 11.04~60 11.04~75 11.04~94.5
13.25~24 13.25~30 13.25~30 13.25~37.7 13.25~48 13.25~48 13.25~60 13.25~60 13.25~75 13.25~94.5
13.8~24 13.8~30 13.8~30 13.8~37.7 13.8~48 13.8~48 13.8~60 13.8~60 13.8~75 13.8~94.5
16.56~24 16.56~30 16.56~30 16.56~37.7 16.56~48 16.56~48 16.56~60 16.56~60 16.56~75 16.56~94.5
17.25~24 17.25~30 17.25~30 17.25~37.7 17.25~48 17.25~48 17.25~60 17.25~60 17.25~75 17.25~94.5
20.7~24 20.7~30 20.7~30 20.7~37.7 20.7~48 20.7~48 20.7~60 20.7~60 20.7~75 20.7~94.5

> >> 37
Air Circuit Breaker
NA1
13.2 Selective protection in NA1

Circuit breaker NA1-2000

Rated
400 630 800 1000 1250
current (A)
Default setting ratings
3.2 5.04 6.4 8 10
of short time-delay 8In (kA)
Setting
Downstream Upstream 0.4~6 0.63~9.45 0.8~12 1~15 1.25~18.75
range (kA)

Delayed tripping
0.1, 0.2, 0.3, 0.4
time (s)
Returnable time 0.06, 0.14, 0.23, 0.35
Frame size Rated Default instantaneous
rated current current (A) setting ratings 12In (kA)
400 4.8 6.348~9.45 6.348~12 6.348~15 6.348~18.75
630 7.56 9.998~12 9.998~15 9.998~18.75
800 9.6 12.696~15 12.696~18.75
NA1-2000 1000 12 15.87~18.75
1250 15
1600 19.2
2000 24
2000 24
NA1-3200 2500 30
3200 38.4
3200 38.4
NA1-4000
4000 48
4000 48
NA1-6300 5000 60
6300 75

Note: It can satisfy the selective protection if only the short time-delay setting value of the superior breaker 1.32 times more than the
subordinate breaker, when the instantaneous setting value is adjustive.

38 > >>
Air Circuit Breaker
NA1

NA1-3200 NA1-4000 NA1-6300

1600 2000 2000 2500 3200 3200 4000 4000 5000 6300

16 16 20 25.6 25.6 32 32 40 50.4

2~30 2~30 2.5~37.7 3.2~48 3.2~48 4~60 4~60 5~75 6.3~94.5

0.1, 0.2, 0.3, 0.4

0.06, 0.14, 0.23, 0.35

6.348~24 6.348~30 6.348~30 6.348~37.7 6.348~48 6.348~48 6.348~60 6.348~60 6.348~75 6.348~94.5
9.998~24 9.998~30 9.998~30 9.998~37.7 9.998~48 9.998~48 9.998~60 9.998~60 9.998~75 9.998~94.5
12.696~24 12.696~30 12.696~30 12.696~37.7 12.696~48 12.696~48 12.696~60 12.696~60 12.696~75 12.696~94.5
15.87~24 15.87~30 15.87~30 15.87~37.7 15.87~48 15.87~48 15.87~60 15.87~60 15.87~75 15.87~94.5
19.837~24 19.837~30 19.837~30 19.837~37.7 19.837~48 19.837~48 19.837~60 19.837~60 19.837~75 19.837~94.5
25.392~30 25.392~30 25.392~37.7 25.392~48 25.392~48 25.392~60 25.392~60 25.392~75 25.392~94.5
31.74~37.7 31.74~48 31.74~48 31.74~60 31.74~60 31.74~75 31.74~94.5
31.74~37.7 31.74~48 31.74~48 31.74~60 31.74~60 31.74~75 31.74~94.5
39.675~48 39.675~48 39.675~60 39.675~60 39.675~75 39.675~94.5
50.784~60 50.784~60 50.784~75 50.784~94.5
50.784~60 50.784~60 50.784~75 50.784~94.5
63.48~75 63.48~94.5
63.48~75 63.48~94.5
79.35~94.5

> >> 39
Air Circuit Breaker
NA1
14. Intelligent controller
14.1 The intelligent controller of NA1-1000
a. The standard M type intelligent controller (NA1-1000)

1: Reset key
1 2: Rated current
3: MCU indicator( normal operation indicator)
4: Current indicator 5-Earthing fault indicator
2 3
6: Short circuit instantaneous fault indicator
4
7 7: Short circuit short time-delay fault indicator
5 8 8: Overload fault indicator
6 9: Time setting table
10: Current setting table
9 11: Overload long time-delay time setting key
12: Overload long time-delay current setting key
10 13: Fault cheking key
14: Short circuit short time-delay time setting key
15: Short circuit short time-delay current setting key
16: Test key
17: Short circuit instantaneous current setting key
18: Clear LED key
19: Earthing current setting key
11
12 20: Earthing time setting key
13
14
15 16
The function of keys show as followed:
17 18 “Fault checking“ key: After the breaker tripping,
press this key to indicate the kind of fault.
19 20
“Test key” key: used for checking the controller and the action of
the breaker.
“Clear LED” key: After the setting,testing and fault checking of the
controller, make the circuit breaker at normal operation.

b. The communication H type intelligent controller(NA1-1000)

2 1: Reset key
2: LCD display window
3: Fault and alarm reset key
4: Curve LED indication
3 5: ”Fault/alarm” LED
6: ”Normal” LED
4 5
7: ”Communication” indicator
6
7 8: Test key
9: Setting key
10: Message key
10 11: Protection key
12: Increasing key
8 11 13: Decreasing key
9 14: Choosing key
12 14
15: Exit key
15
13 16: Testing port

16

40 > >>
Air Circuit Breaker
NA1
c. Basic functions
● stands for definite setting ■ stands for optional setting — stands for no funcion
Standard (M type) Communication (H type)
Controller type Three cascades Four cascades Three cascades Four cascades
protection protection protection protection
Long time-delay protection ● ● ● ●
Short time-delay protection ● ● ● ●
Instantaneous protection ● ● ● ●
Earthing fault protection — ● ● ●
Load current display ● ● — —
Load current digital display (Ampere Meter) — — ● ●
Test function ● ● ● ●
Basic Fault recall ● ● ● ●
function Self-diagnose function ● ● ● ●
MCR making and breaking function ● ● ● ●
Fault alarm ● ● ● ●
Fault breaking indication ● ● ● ●
Customer setting, testing ● ● ● ●
Load monitor — — — —
RS485 port MODBUS protocol — — — —
Voltage measuring — — — —
Frequency display — — — —
Active power measuring — — — —
Power factor measuring — — — —
Electric energy measuring — — — —
Over voltage protection — — — —
Under voltage protection — — — —
Optional Phase protection — — ● ●
auxiliary
Current transformer earthing protection ■ (3P+N model) ■ (3P+N model) ■ ■
function
Exceed breaking function ■ ■ ■ ■
Thermal recall fuction ■ ■ ■ ■
Four output contacts ■ ■ ■ ■
LED display, code switch and LCD display, LED indication,
Man-machine interface instruction
toggle switch setting keyboard operation

d. Operation instructions
Standard intelligent controller setting
According to the panel number 9 showed, dial the switch 11,14,20 to set the time you need.
According to the panel number 10 showed, dial the switch 12,15,17,19 to set the current you need.
Example 1: means that overload long time-delay current is 0.9In, overload long time-delay time is 60s.
Example 2: means that short circuit short time-delay current is 4In, short circuit short time-delay time is 0.4s.

> >> 41
Air Circuit Breaker
NA1
Example 1 Example 2

tr tsd
Ir Isd

Communication intelligent controller setting and operation. 547 A


It provides 4 main menu and 1 default interface. N A B C
150
Default interface
Without other function action, it displays phases current column 100
chart.
50

1. “Testing” menu 2. “System data setting” menu

Current I Harmonic Clock setting


wave H
Voltage U Measure metre setting
Frequency F Testing lock
Power P Communication setting
Electric energe E I/O setting

Press or key to return default interface. Press or key to return default interface.
On other non-fault interface, press to skip to testing On other non-fault interface, press to skip to
menu. system data setting menu.
Without action for several minutes, Without action for several minutes,
it returns to the default interface. it returns to the default interface.

3. “Protection data setting” menu 4. “Historical record and maintain” menu

Current protection Present alarm Alarm record


Load monitor Operation times Shift record
Voltage protecting Contact wearing

Other protection Product information


Trip record

Press or key to return default interface. Press or key to return default interface..
On other non-fault interface, press to skip to On other non-fault interface, press to skip to
protection data setting menu. testing menu.
Without action for several minutes, Without action for several minutes,
it returns to the default interface. it returns to the default interface.

42 > >>
Air Circuit Breaker
NA1
5. Submenu operation show:
overload longtime-delay protection setting

Long time-delay Long time-delay Long time-delay

Ir=400A Ir=1000A Ir=1000A


(40.0%In) (100%In) (100%In)
Curve type Curve type Curve type

= SI = SI = SI


+
-

then ▲
+
-

Setting definite value Save definite value

Note: communication controller actual menu will change as


customers' choice.

e. Over current protection characteristic


The characteristic of intelligent controller

10000

5000
I R =(0.4~1)In

2000
tl=(30~240)s
(M type)
1000

500

200

100

50

20

10

5
t(a)

1
Isd=(3~10)IR(M type)
0.4s or(1.5~15)In(H type)
0.5

0.3s
0.2
0.2s
0.1
0.1s

0.05

0.02 Ii=(3~15)In+OFF(M type)


or(1~20)In+OFF(H type)

0.01
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 70 80 100
xIn kA

> >> 43
Air Circuit Breaker
NA1
Long time-delay overcurrent protection, inverse time characteristic.

Setting current
Error Current Tripping time (s) time error
(IR)
1.05IR <2h Non-trip
1.3IR <1h trip
1.5IR(M) 30 60 120 240 ±10%
(0.4~1)In+OFF ±10%
2.0IR(M) 16.9 33.8 67.5 135 ±10%
1.5IR(H) 0.61~86 ±10%
6.0IR(H) 0.14~19.2 ±10%

Short time-delay overcurrent protection characteristic.

Setting current
Error Setting delay time (s) Time error
(IR)
Isd ts(s)
M (3~10)IR+OFF ±10% 0.2 0.4 ±15%
H OFF+(1.5~15)IR ±10% 0.1 0.2 0.3 0.4 ±15%

Instantaneous characteristic.
Type Setting current (Ii) Tripping Error
M (3~15)In+OFF ≤0.85Ii 30ms Non-trip;>1.15Ii trip ±15%
H (1~20)In+OFF ≤0.85Ii 40ms Non-trip;>1.15Ii trip ±15%

Earthing fault protection characteristic

Type Rated current (Ig) Error Rated delay time (Tg) Time error
M (0.2~0.8)In+OFF,min 100A ±10% 0.1, 0.2, 0.3, 0.4 ±15%
H (0.2~1.0)In+OFF,min 100A ±10% (0.1~1.0)s ±15%

Single phase earthing protection curre (M type)

Ig=(0.2~0.8)In(M type)
min 100A

T(s)

0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8

XIn

44 > >>
Air Circuit Breaker
NA1
Wiring diagram of the earthing fault protection.

Transformer Current transformer Transformer Current transformer

Intelligent Intelligent
controller controller

Transformer Transformer Current transformer


Current transformer

N
N

Intelligent
Intelligent
controller
controller

PE

Load monitor characteristic.

10

×In ×In

> >> 45
Air Circuit Breaker
NA1
14.2 The intelligent controller of NA1-2000, 3200, 4000, 6300
14.2.1 The standard M type intelligent controller (NA1-2000 3P 4P; NA1-3200 3P 4P; NA1 4000 3P)
The M type intelligent controller is the core part of the NA1 Air Circuit Breaker to protect the electric circuit and the power supply
against the dangers such as overload, short circuit and single-phase earthing fault. The controller adopts highly-integrated and high-
performance digital signal processor that featuring power functions and reliable performance to perform real-time processing to the
signal so as to achieve various protection function and numerous auxiliary functions.

Appearance and panel illustration

Reset button

Frame size rated current

Rated current

Ammeter display window

Select key
Clear key
Fault indicator
Protection indicator

Fault checking key

Function key

Program interface

Selectivity protection Earth fault protection

t t

IL IS II I IG I

46 > >>
Air Circuit Breaker
NA1
a. Symbol designation table

Number Symbol Designation


1 Inm Frame size rated current of breaker
2 In Rated current
3 IL(Ir1),Is(Ir2),Ii(Ir3) Action current of long time-delay, short time-delay and instantaneous
4 IG(Ir4) Action current of earth fault or phase N
5 tL,ts,tG Action time of long time-delay, short time-delay and grounding
6 L1,L2,L3,G Phase A, B, C and N (or earth)
7 Ic1,Ic2 Action current of load monitor 1 and load monitor 2
8 T,I Time, current
9 A,kA,s Unit Indicator: Ampere, kilo-Ampere, second

[Link] power supply Step 6: Repeat step 3 ~ step 5 in case requiring changing
The operating power supply input to the intelligent controller: other parameters. If not, press “reset” key till the characteristic
AC 400V/380V, 230V/220V, AC 110V, 50Hz; curve indicator is off.
DC220V, 110V, 24V. Note: In case of occurrence of malfunction under setup status,
c. Basic functions of intelligent controller it will automatically exit the setup status and enter into
Main protection function malfunction status.
Query function During the adjustment of the parameters, the longer the time of
Parameter setting function pressing or holding the “+” or “-” key is, the faster the up or
Test function down speed is.
Load monitor function (optional)
Making current release (MCR) and High-Set Instantaneous Failure inquiry operation
Short Circuit (HSISC) function (optional) Query operation method
Signal alarm function (optional) Step 1: Make sure the controller is under reset status.
d. Operation instructions Step 2: Press “fault display” key till the ammeter display window
Parameter setting operation indicates the failure action value and the action time alternately.
Step 1: Setting right confirmation. The key must be switched Press “select” to inquiry relevant parameters.
to ”setting” position for type H. Step 3: Press “reset” key to exit the inquiry status.
This step is no necessary for type M.
Step 2: Make sure the controller is under reset status. If the Test operation method
controller isn't under reset status, press ”reset” key till the Step 1: Make sure the controller is under reset status.
ammeter displays operation current. Step 2: Press “set” key till the indicator of the short time-delay
Note: When the controller is under malfunction alarm status, characteristic curve current is on. Press “+””-” to adjust the
then the setup function is locked and the setup operation required current.
can't be conducted. Press “trip” key, then the breaker will trip. The ammeter display
Step 3: Press “set” key till the ammeter display window window will display the action current and action time in turn.
displays required action current or time setting. Step 3: Press “reset” key to exit the test status.
Step 4: Press ”+” and ”-” to set the items to be changed.
Step 5: Press “save” key. At that time, the “save“ indicator
will flash once to indicate that the parameters are saved.
If not desiring to save, then directly press “reset” key.
Then the parameters won't be changed and will remain the
original values.

> >> 47
Air Circuit Breaker
NA1
e. Characteristic

Over-current protection characteristic curve figure

10000

5000
Ir1=(0.4~1)In
2000
Tr=(15~480)s
1000

500

200

100

50

20

10

5
t(a)

1
Ir2=(1.0~15)Ir1

0.5 0.4s

0.3s
0.2
I 2t 0.2s
OFF
0.1
0.1s
0.05

Ir3=1.0In~50kA/75kA/100kA
0.02

0.01
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30 40 50 60 70 80 100
xIn kA

Overload long time-delay protection

Current Ratings
Error Current Action Time Time Error
Range(lr1)

≤1.05Ir1 <2h Non-trip


>1.30Ir1 <1h trip
(0.4~1) In ±10%
1.51Ir1(setting time) 15 30 60 120 240 480 ±10%
2.0Ir1 8.4 16.9 33.7 67.5 135 270 ±10%
Phase N Overload and
Over-Current Characteristic 100% or 50% (Applicable to 3P+N or 4P)

Short-circuit short-delay protection

Current Ratings
Error Current Action Time Time Error
Range(lr2)
≤0.9Ir2 Non-trip
NA1-2000 1.3Ir1~15Ir1+OFF (OFF Position)
>1.10Ir2 Delayed-trip
NA1-3200 1.3Ir1~15Ir1+OFF (OFF Position), Ir2≤40KA ±10%
Time setting (ts) 0.1 0.2 0.3 0.4 ±25%
NA1-6300 1.3Ir1~15Ir1+OFF (OFF Position), Ir2≤50KA
Returnable Time 0.06 014 0.19 0.25 ±25%

Short circuit instantaneous protection


Current Ratings Range(lr3) Error Current Action Characteristic

NA1-2000 1.3In~50kA ≤0.85Ir3 Non-trip


NA1-3200 1.3In~65kA ±15%
NA1-6300 1.3In~75kA >1.15Ir3 trip

48 > >>
Air Circuit Breaker
NA1
f. Earth fault protection
The earth fault protection has definite time-delay characteristic
with the failure delayed time no less than the definite time-delay time setting.

Earth fault Protection Characteristic Curve

1000

500

100

50

20
10 Ir4=(0.2~0.8)In

t(s) 5

2
1

0.5 0.4s 0.4s


0.3s 0.3s
0.2 0.2s 0.2s

0.1 0.1s 0.1s

0.05

0.02
0.01
.05 .06 .08 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
xIn

Single phase earth fault protection technical data:

Current Ratings
Error Current Action Time Time Error
Range(lr4)
≤0.8 lr4 Non-tripping
(0.2~0.8)ln
>1.0 lr4 Tripping
+OFF (OFF position) ±10%
Setting time (Tg) 0.1 0.2 0.3 0.4 ±25%
(NA1-2000, min160A)
Returnable time 0.06 014 0.19 0.25 ±25%

> >> 49
Air Circuit Breaker
NA1
14.3 NA1 Multifunctional Intelligent Controller
a. Menu Operation Explanation
Display operation kneading board

7 7

1 1

2
3 2
4 3
4
5
6 6

16 16

1: LCD interface display 6: curve LED


2: fault and warning Reset There is the red LED indicating lamp hiding in the curve.
3: fault/warning LED The corresponding LED lamp will flash to indicate the fault
The LED will not flash when it works normally; type when tripping at fault.
the red LED will flash fast when tripping at fault; The LED is on to indicate the project set at the moment
the red LED will on when warning occurs. when protective parameter is set.
4: “normal” LED 7: machinery reset button
The green LED will always flash if only the ST40-3 is The button will spring when fault trips or test trips.
powered and works stably. When not press down, the circuit breaker are not allowed
5: communication indicating lamp to shut off.
The communication condition is indicating as follows: When press down, fault indication will be reset
Profibus: off when no communication; at the same time.
on when communication.
Modbus: off when no communication;
flash when communication.
Device Net: Flash when no communication,
on when communication.

50 > >>
Air Circuit Breaker
NA1

8 9 10 11 8: Measure— function key 1, switch to measure default theme


menu (the key in the password input interface is “left”)
9: Set— function key 2, switch to parameter set theme menu
(the key in the password input interface is “right”)
10: protection—function key 3, switch to protection parameter
set theme menu.
11: Information—function key 4, switch to history and
maintenance theme menu.
12: Up—up to move the menu content under the current used
grade, or up to change the chose parameter.
13: Down—down to move the menu content under the current
used grade, or down to change the chose parameter.
14: Escape—to escape from this grade and return to upper
menu; or cancel the current parameter selected.
15: Select—enter into the next menu directed by the current
12 13 14 15 item, or for the current parameter selected and store
modifications.
16: Test port—The bottom of the front board has a 16 pin test
port, which can insert a inserted portable power supply or
inspection unit.

Selective protection Earth fault/residual current protection

t t

0 I 0 I

b. Panorama of intelligent controllers for NA1 series

Type Rated current (A) Number of poles M 3M 3H

NA1-2000 630 800 1000 1250 1600 2000 Yes Yes Yes

NA1-3200 2000 2500 3200 3P, 4P Yes Yes Yes

4000 5000 No Yes Yes


NA1-6300
6300 3P No Yes Yes

> >> 51
Air Circuit Breaker
NA1
c. NA1 Multifunctional Intelligent Controller subject menu
NA1 Multifunctional Intelligent controller has provided
4 subject menu and 1 default interface

1. Default interface 2. “measure” menu

452 A 3H
150
A B C N current I
100 voltage U
50 frequency F

3H
energy E
power P
·The controller displays the default interface harmonic H
when on electiicity.
·Under each subject menu, press or the
corresponding subject key can return to default
interface.
·press to enter into measure main menu
·If don't press any keys in 5 minutes and then the
·press or to return to default interface
pane cursor will show the maximum phase
automatically. ·In other non-fault interface, press to jump to
·In the non-activated fault interface, measure menu
if don't press any key in 30 minutes
and then will automatically return to the
default interface.

3. “system parameter set”menu 4. “protection parameter set”menu

3H 3H
clock set current protection
measurement meter set load monitor
test & clock voltage protection

3H 3H
communication set other protection
I/O set

·Press or to return to default interface ·Press or to return to default interface


·In other non-fault interface, press to jump to ·In other non-fault interface, press to jump to
system parameter set menu protection parameter set menu

52 > >>
Air Circuit Breaker
NA1
5. “history and maintenance”menu

3H 3H 3H
current warning production information Variable-record
operating time release record
contact wearout warning record

·Press or to return to default interface


·In other non-fault interface, press to jump to history and maintenance menu

6. Sub-menu operation example:


overload long delay protection set

Ir Ir Ir
=10 00 A =40.4 %In 1200 A =48.0 %In =1200 A =48.0 %In
curve type curve type curve type
=VI =VI =VI


+
-

then adjust ▲
+
-

fixed value save fixed value

d. Instruction to technical property

5000

2000

1000

500

Express inverse-time 1
(Ordinary use)
200
Express inverse-time 2
(Motor protection)
100
Express inverse-time

50
Standard
inverse-time
20

10

t(s)
5 High-voltage fuse
compatibility

0.5

0.2

0.1

0.05

0.02

0.01
0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 20
Xin1

> >> 53
Air Circuit Breaker
NA1
Function of intelligent controller
● stands for definite setting ■ stands for optional setting — stands for no funcion

Type
Function configuration
M 3M 3H

Current display function ● ● ●


Overload long time delay protection(inverse) ● ● ●
Short circuit short time delay protection(inverse and definite) ● ● ●
Short circuit instantaneous protection ● ● ●
Single-phase earthing fault protection ● ● ●
Current imbalance protection caused by phase failure ● ● ●
Parameter setting function ● ● ●
Test(simulate trip)function ● ● ●

Inquiry function ● ● ●
Self-diagnose function — ● ●
Programing interface function — — —
Communication function — — ●

Contact abrasion extent record — ● ●

Operating times record — ● ●


Clock function — ● ●

Alarm record — ● ●

Position (making, energy storage or breaking) change record — ● ●


The history current peak value record — ● ●
MCR(Making current release) and HSISC(High-setting instantaneous short circuit) — ● ●
Current leakage protection(inverse and definite) — ■ ■
Neutral (N phase) protection — ● ●
Load monitor function (Modes 1 and Modes 2) — ■ ●
Voltage measurement display function — ■ ●
Frequency measurement display function — ■ ●
Voltage imbalance measurement display function — ■ ●
Power measurement display function — ■ ●
Power factor measurement display function — ■ ●
Electrical energy measurement display function — ■ ●
Fault clock function — ■ ■

History data record function — ■ ■


Phase sequence checking — ■ ■
Average value in a certain period of time measurement function (current and power) — ■ ■
Humorous-wave measurement — ■ ■
Over-voltage protection — ■ ■
Under-voltage protection — ■ ■
Voltage imbalance protection — ■ ■
Over-frequency protection — ■ ■
Under-frequency protection — ■ ■
Phase sequence protection — ■ ■
Inverse power potection — ■ ■
Position lock function — — —

54 > >>
Air Circuit Breaker
NA1
e. Overload long time-delay protection

■Power distribution or motor protection


Ir1= (0.4~1.0)In + OFF (Exit position)
Setting current I≤1.05Ir1 without actions in 2h
Acting property
I>1.3Ir1 with actions while it's less than 1h
Property curve Curve 1~curve 5, could be rectified, rectified as curve 3 for ex-factory
Inverse-time (s)
Curve speed IEC255 standard, 80 level points totally, could be rectified
(Corresponding 2Ir1)
Precision ±10% (intrinsic 40ms)

Note: When N-phase is 50%, protective settings are treated as 50% for N-phase. If long delay setting is 2000A, long delay setting for
phase A, B and C is 2000A, and 1000A for phase N.

f. Instruction to short time-delay property


Ir2= (1.5~15) Ir1 + OFF (exit position)
Setting current ≤0.9Ir2 without actions
Acting property
>1.1Ir2 delay action
Inverse-time delay (s) Ts= (0.1~0.4)s (0.1s level error)
(Corresponding 2Ir1) Precision ±10% (intrinsic 40ms)
Inverse-time property Curve is the same as overload long delay, but curve speed is 10 times faster
Short delay inverse-time thermal memory (15min) Standard + OFF

Note: When controller is frame I (Inm=2000A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1;
when controller is frame II (Inm=3200A, 4000A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1 and max is 40kA;
When controller is frame III (Inm=6300A), rectified value of short time-delay protection is 1.5 Ir1~15 Ir1 and max is 50kA.

g. Instruction to short circuit instantaneous property


Ir3= 1.01n~50kA/65kA/75kA+OFF (Exit position)
Setting current ≤0.85Ir3 without actions
Acting property
>1.15Ir3 with actions

Note: When controller is frame I (Inm=2000A), rectified value of instantaneous protection is 1.0In~50kA+OFF;
when controller is frameII (Inm=3200A), rectified value of instantaneous protection is 1.0In~65kA+OFF;
When controller is frame III (Inm=6300A), rectified value of instantaneous protection is 1.01n~75kA+OFF.

h. Earth fault or residual current protective property: t=TG×KG×If /I


■Earth fault protection
(0.2~0.8)In + OFF (with 160A as the minimum and 1200A as the maximum.
If= OFF means it only alarms without tripping)
Setting current
<0.8If without actions
Acting property
≥1.0 If delayed action
■Earth fault protection
TG = (0.1~1.0)s + OFF (Level difference 0.1s, OFF means it only alarms without tripping.)
Inverse-time (s) Inverse-time cutting
1.5~6 + OFF (Level difference 0.5, OFF means earth fault is definite-time)
(Corresponding 2Ir1) coefficient KG
Precision ±10% (intrinsic 40ms)
If= (0.1~1.0)Io + OFF (Level different 0.01A, OFF means exit position)
Setting current <0.8If without actions
Acting property
≥1.0 If delayed action
Property curve Curve 1~curve 5, could be rectified, rectified as curve 3 for ex-factory
Delay (s) TG = (1.5~6)s + OFF (Level difference 0.5s, OFF means is definite-time)
Precision ±15%

> >> 55
Air Circuit Breaker
NA1
Wiring diagram of earth fault protection

3PT type 4PT type (3P+N) T method

CT CT L1 CT L1
L1
L2 L2
L2
L3 L3
L3
N
PEN intelligent
PE
intelligent controller
intelligent
controller
controller N
PE

externally connected zero sequence current externally connected zero sequence current externally connected zero sequence current
inductor type 1 applied(ZCT) inductor type 2 applied(ZCT) inductor type 3 applied(ZCT)

ZCT ZCT
CT CT CT
L1 L1 L1
L2 L2 L2

L3 L3 L3

N N
PEN
PE intelligent
intelligent ZT100
intelligent controller
controller
controller
PE or PEN

I. Load monitor protection property

load type method 1 property curve load monitor type 2 property curve

10000
10000
5000
5000
Ir1=(0.4~1)In
Ir1=(0.4~1)In
Ic1=(0.2~1)In
2000 Ic1=(0.2~1)In
2000
Ic2=(0.2~1)In Ic2=(0.2~1)In
1000
1000
500 500

200 200

100 100

50 50
t1=(15~480)S tr2=60s t1=(15~480)S
20 20
Tr1=(1/2)tL
10 Tr2=(1/4)tL 10 tr2=1/4tL

5 5
t(a) t(a)

2 2
tr1=1/2tL
1 1

0.5 0.5

0.2
0.2
0.05
0.05

0.02
0.02
0.01
0.01 30
0.010.02 0.03.1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 30
0.01 0.02 0.03 .1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 20 xIn
xIn

56 > >>
Air Circuit Breaker
NA1
Technical parameter:

■Load monitor type 1


IC1= (0.2~1.0)In + OFF (OFF means exit position)
Rectified current ≤1.05Ic1 without action
Acting property
>1.21c1 delay relay action
Property curve The same as overload long delay
Inverse-time (s)
Curve speed Could be set separately (Setting content is the same as that of overload long delay)
Ic2= (0.2~1.0)In + OFF (OFF means exit position)
Rectified current ≤1.05Ic2 without action
Acting property
>1.21c2 delayed relay
Maximal inverse- Property curve The same as overload long delay
time delay (s) Curve speed Could be set separately (Setting content is the same as that of overload long delay)

■Load monitor type 2


Ic1= (0.2~1.0)In + OFF (OFF means exit position)
Rectified current ≤1.05Ic1 without action
Acting property
>1.21c1 delay relay action
Property curve The same as overload long delay
Inverse-time (s) Curve speed Could be set separately (Setting content is the same as that of overload long delay)
Ic2= (0.2~1.0)In + OFF (OFF means exit position)
Rectified current Acting property ≤0.9Ic2 without action
Fixed delay (s) Fixed as 60s
Precision ±10% (Intrinsic 40ms)
Thermal memory (30min, could be eliminated while power-off) Standard + OFF

j. Protective property on unbalance current

δ= 40%~100% + OFF (Level difference 0.1, OFF means exit)


Rectified current ≤0.9δ without actions
Action or alarm property
>1.1δ delay action
Delay time (s) Tδ= (0.1~1.0)s (Level difference 0.1, OFF means exit)
Precision ±10% (Intrinsic 40ms)

k. Communication networking
Make key-lock at “communication” position, connect to
secondary terminals “10#” and “11#” through cable to
achiveve the communication function.

Modbus protocol networking Profibus-DP protocal networking

Rt
Rt
ST-DP ST-DP ST-DP
CP5×11Main
RS232 RS485 station card r
Converter RS485
NA1 NA1 NA1

NA1 NA1 NA1

Monitor host Monitor host

Communication connection diagram (Modbus protocol)


Communication connection diagram (Profibus-DP protocol)

> >> 57
Air Circuit Breaker
NA1
15. Accessories
15.1 Under-voltage release
Without power supply, under-voltage release can't close.
It is classified into instantaneous and time-delay type.
Delay time 0, 1s, 2s, 3s, 4s, 5s, 6s, 7s are fixed for NA1-1000; 1s, 3s, 5s are fixed for NA1-2000, 3200, 4000, 6300.
Within 1/2 time-delay range, circuit breaker does not trip when power voltage recovers and exceeds 85%Ue.

Characteristic

Type NA1-1000 NA1-2000, 3200, 4000, 6300


Rated control power voltage Us(V) AC230, 400 AC400, 230, 127 DC220, 110
Action voltage(V) (0.35-0.7)Us
Reliable making voltage(V) (0.85-1.1)Us
Reliable non-making voltage(V) ≤0.35Us
Power loss(W) 20VA 48VA

Make sure there is power supply on the under-voltage release, before making the circuit breaker.

15.2 Shunt release


Shunt release can realize the remote control to break the circuit breaker.
Characteristic

Type NA1-1000 NA1-2000, 3200, 4000, 6300


Rated control power voltage Us(V) AC230, 400 DC220, 110 AC400, 230, 127 DC220, 110
Work voltage (0.7-1.1)Us
Power loss 56VA 250W 300VA 134W 75W
Breaking time 50±10ms 30~50ms

Forbid making the power for long time to avoid the shunt release being damaged.

15.3 Closing electromagnet


After the motor finishing the energy storage, closing release can instantly close the circuit breaker.
Characteristic

Type NA1-1000 NA1-2000, 3200, 4000, 6300


Rated control power voltage Us(V) AC230, 400 DC220, 110 AC400, 230, 127 DC220, 110
Work voltage (V) (0.85-1.1)Us
Power loss (W) 56VA 250W 300VA 134W 75W
Closing time (50±10)ms ≤70ms

Forbid making the power for long time to avoid the closing release being damaged.

58 > >>
Air Circuit Breaker
NA1

15.4 Motor-driven energy-storage mechanism


With the function of motor-driven energy storing and auto restoring energy after closing the circuit breaker, the mechanism can
ensure closing the circuit breaker instantly after breaking the circuit breaker.
Manual energy-store is available.

Characteristic

Type NA1-1000 NA1-2000, 3200, 4000, 6300


Rated control power voltage Us(V) AC230, 400 DC220, 110 AC400, 230, 127 DC220, 110
Work voltage (V) (0.85-1.1)Us
Power loss (W) 75VA 75W 85/110/150W 192W
Energy-storage time <4s <5s
Operation frequency No more than 3 times per minute

15.5 Auxiliary contact NO


Standard model: 4NO(normal open)/4NC(normal close) and 6NC(normal close).

Characteristic

Type NA1-1000 NA1-2000~6300


Rated voltage (V) AC230 AC400 DC220 AC230 AC400 DC220
conventional free-air thermal current Ith (A) 10 6 0.5 6 6 6
Rated control capacity 300VA 100VA 60W 300VA 300VA 60W

15.6 Doorcase
Installed on the door of the distribution cubicle, for sealing 15.7 Phases barrier
the distribution cubicle and making the Installed between the busbars to increase the creepage
protection class to IP40( fixed type and drawout type). distance.

15.9 Transparent shield (NA1-2000)


15.8 Operation pushbutton lock Installed on the doorcase of the cubicle's small door,
Used for locking the break pushbutton and the close make the protection class to IP54. It is suitable for the
pushbutton. ( Padlock is prepared by users) fixed, drawout type circuit breaker and the load switch.

> >> 59
Air Circuit Breaker
NA1
15.10 Off position locking mechanism
When the circuit breaker is disconnected, padlock can be used to lock it after pulling out the lock lever, then the circuit breaker
can't be “Test” or “connected” position.( Padlock is prepared by users)
15.11 Key lock
Lock the circuit breaker on the OFF position, then the circuit breaker can't be closed.
Locks and keys will be provided by us.
Separate lock and key is matched with one set of the circuit breaker.
Three same locks and two same keys are matched with three circuit breaker.
Note: Before pulling out the key, the break pushbutton should be pressed first, rotate the key anticlockwise, then pull it out.

★ NA1Install the locking system


1. Components of the locking system:

lock washer key

2. Installation sequence:

1. Boring here, and 2. Put the into 3. Install the 4. Push the red button “ON”, and take the
polish the hole hole
make the hole lock here key out, then install the cover.
it smooth

15.12 Cable mechanical interlock


It can realize the interlock of two horizontal or vertical-installed, three poles or four poles ,
drawout type or fixed type circuit breaker.
a. If need bend the cable, make sure the radian is more than 120°.
b. Check and make sure enough lubricating oil of the cable.
c. The maximal distance between two interlock circuit breaker is 2m.

2m(max)

Circuit diagram Available running manner

1QF 2QF
1QF 2QF
0 0
0 1
1 0

Notes: a. when the steel cable needs to be bent, enough transition arc should be reserved to guarantee flexible movement of steel cable;
b. check the steel cable and make sure there is enough lubricant in the steel cable to guarantee flexible movement of steel cable.

60 > >>
Air Circuit Breaker
NA1
15.13 Connecting-rod type mechanical interlock
Three vertical-installed three-poles or four-poles, drawout-type or fixed type circuit breakers realize the interlock between one
breaker with another two different-state breakers.

Circuit diagram Available running manner

Manner 1: three power supplies are provided


for one circuit breaker only
1QF 2QF 3QF
0 0 0
1QF 2QF 3QF
0 0 1
0 1 0
1 0 0

15.14 Drawer base misplug-proof device (NA1-1000)


Only the matched circuit breaker body could inserted to the drawer base. When not matched, it can't be inserted.

Bracket 2

Nameplate

Bracket 1

Body
Drawout base

Match Mis-match Mis-match

> >> 61
Air Circuit Breaker
NA1
16. Regular malfunction and solutions
Fault description Reasons analysis Maintenance method

1. Check the breaking current value and operation time of intelligent release.
Over load tripping 2. Analyze the load and electric network, exclude the overload if it happens.
(IL indicator flashing) 3. Match the actual operating current with long time-delay current setting value.
4. Press the reset button to reclose the breaker

1. Check the breaking current value and operation time of intelligent release.
2. Exclude the short circuit fault if it happens
Short circuit tripping
3. Check the setting value of intelligent release
(“Is”or“Ii”indicator flashing)
4. Check the normal state of breaker
5. Press the reset button to reclose the breaker
Tripping of
circuit breaker
1. Check the breaking current value and acting time of intelligent release.
Earthing fault tripping 2. Exclude the earthing fault if that happens.
(IG indicator flashing) 3. Match the fault current setting value with the actual protection.
4. Press the reset button to reclose the breaker.

Under-voltage release fault: [Link] the power is on or not


1. Rated working voltage is [Link] the power voltage of under-voltage release, it shouldn't be less
less than 70%Ue than 85%Ue.
2. Fault of control unit [Link] the control unit of under-voltage release

Mechanical interlock acting Check the working state of two circuit breakers fixed with mechanical interlock
Intelligent release don't reset
Press the reset button to reclose the breaker
(panel is raised)

The breaker Secondary circuit of drawerout- Make the breaker to "making" position
can't be type breaker isn't connected ("click" sound will be heard)
closed
Check the secondary circuit:
Breaker hasn't stored energy 1. Power voltage of motor shouldn't less than 85%Ue.
2. Check the storage mechanism, replace it if necessary.

Mechanical interlock acting Check the working state of two circuit breakers
leads to locking of breaker fixed with mechanical interlock

The breaker Closing electromagnet:


can't be [Link] control voltage is 1. Power voltage of closing electromagnet
closed less than 85%Us; shouldn't less than 85%Us.
[Link] electromagnet 2. Replace the electromagnet.
is damaged

Tripping immediately: 1. Check the breaking current value and operation time of intelligent release;
Tripping after
1. Short circuit current is closed 2. Exclude the short circuit fault if it happens;
closing the
[Link] tripping because of 3. Exclude overload fault
circuit breaker
(Fault indicator transient current is high 4. Check the normal state of breaker
flashing) when closing; 5. Modify the current setting value of intelligent release
3. Overload current is closed 6. Press the reset button to reclose the breaker

The breaker can't be opened manually


1. There is fault with mechanical operating 1. Check the mechanism, if there is fault happened.
mechanism

The breaker can't be opened by


Circuit breaker motor remotely
can't be opened 1. Check the mechanism, if there is fault happened.
1. There is fault with mechanical
2. Check the Power voltage of shunt release is less
operating mechanism
than 70%Us or not
2. Power voltage of shunt
3. Replace shunt release
release is less than 70%Us;
3. Shunt release is damaged

62 > >>
Air Circuit Breaker
NA1
Fault description Reasons analysis Maintenance method

Manual storage can't be realized Mechanical fault with the energy-storage device

Motor storage can't be realized


Circuit breaker [Link] voltage of motor 1. Power voltage of motor energy-stored device shouldn't less
can't store energy energy-stored device is less than 85%Us; than 85%Us
[Link] is mechanical fault 2. Mechanical fault with the energy-storage device
with energy-storage device

Handle of drawerout- 1. There is padlock at the "opening" position


[Link] away the padlock
type circuit breaker 2. Slideway or breaker body
[Link] the slideway or breaker body into its position
can't be drawn in or out isn't pulled into its position

Drawerout-type breaker
[Link] isn't pulled out
can't be drawn out [Link] out the handle
[Link] is not totally at the
at the "opening" [Link] the circuit breaker totally at “opening” position
“opening" position
position

1. Something drop into the drawer base,


Drawerout-type breaker and lock the mechanism or mechanism
1. Check and clean the drawer base, or contact with manufacturer
can't reach the fault happens.
2. Match the body with relevant drawer base
"making" position 2. Breaker body not match with the frame-size
rated current of drawer base

1. Release isn't connected [Link] the power is connected or not


with power [Link] off the power, then connect again. Otherwise contact
No display on [Link] is fault with release with manufacturer
intelligent release
panel Closing electromagnet: 1. Check the electromagnet power voltage shouldn't be less
1. Rated control voltage is less than 85%Us; than 85%Us.
2. Electromagnet is damaged 2. Replace the closing electromagnet.

Fault indicator still Fault happened with Cut off the power, then connect again. Otherwise contact
flashing after pressing
intelligent release with manufacturer
the clear button

> >> 63
Air Circuit Breaker
NA1
NA1-1000 Orde sheet
Customer: Tel: Date:
Quantity:
Model NA1-1000
Rated current In ( A ) □ 200 □ 4 00 □ 63 0 □ 8 00 □ 10 00
Installation mode □ Drawerout type □ Fixed type
Number of poles □ Three poles □ Four poles

Conventional setting before delivery: IR=1In, 30s, Isd=8In, Tsd 0.4s; Ii=12In; Ig=OFF tg=0.4s

Long time-delay Current setting: In (0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, OFF)
protection IR(Ir1) Time setting: s (30, 60, 120, 240)
Short circuit short time- Current setting: IR (3, 4, 5, 6, 7, 8, 10,OFF)
□Standard delay protection Isd(Ir2) Time setting: s (0.2, 0.4)
M type Short circuit instantaneous
Current setting: In (3, 4, 6, 8, 10, 12, 15, OFF)
protection Ii(Ir3)

Earthing Current setting: In (0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, OFF Min100A)
protection Ig Time setting: s (0.2, 0.4, 0.6, 0.8)
Protection data setting: LED display; Test function; Fault recall; Self-diagnose function;
MCR and HSISC function; Fault breaking indication

Intelligent Optional □ Exceed skipping function □ Self-diagnose alarm □ Fault breaking alarm
controller function □ Overload alarm □ Earthing fault alarm

Conventional setting before delivery: IR=1In, 17.2s,; Is=6IR, Isd=8IR; Tsd 0.4s; Ii=12In; Ig=OFF tg=0.4s

Current setting:(0.4~1)In
Long time-delay
Time setting(1.5In): 0.61, 0.98, 1.47, 2.46, 3.68, 4.91, 6.14, 8.29,
protection IR(Ir1)
11.1, 17.2, 24.6, 36.8, 49.1, 61.4, 73.7, 86s
Short circuit short time- Current setting: (1.5~15)IR + OFF
delay protection Isd(Ir2)
□Comm- Time setting: (0.1~0.4)s

unication Instantaneous Current setting: (1.0~20)In+OFF


protection Ii(Ir3)
H type
Current setting: (0.2~1.0) In
Earthing protection Ig
Time setting: (0.1~1)s
LCD display; Code switch and toggle switch; Fault recall; Self-diagnose function; LED indication; Clock
Peak current recall;Test function: Earthing current measuring; Thermal recall fuction; Earthing fault alarm;
Phase protection; unbalanced current protection; MCR making and breaking function; Fault recall;

Optional □ Modbus communication □ Profibus-DP communication □ Display of voltage □ Display of frequency


function □ Display of power □ Over voltage/under voltage protection □ Phases protection
Other Power of controller: □ AC400V □ AC230V □ DC220V □ DC110V □ DC24V
Under-voltage release: □ Instantaneous □ delay s(Delay of RC under-voltage release: (1~7)s )
□ AC400V □ AC230V
Shunt release: □ AC400V □ AC230V □ DC220V □ DC110V
Electrical
Closing electromagnet: □ AC400V □ AC230V □ DC220V □ DC110V
accessories
Motor for breaker: □ AC400V □ AC230V □ DC220V □ DC110V
Auxiliary contact: □ 4NO(normal open)and 4NC(normal close) □ 6NO(ornmal open)and 6NC(normal close)
Busbar □ Horizontal Connection □ Vertical Connection

Special □ Phases barrier □ Steel cable interlocking


requireme nts □ Off position locking device

Note: 1) Please mark “√” or fill figure in the relative ”□” if no mark, we will provide according to conventional.

NA1-1000

64 > >>
Air Circuit Breaker
NA1
NA1-2000~6300 Orde sheet
Customer: Tel: Date:
Quantity:

Model NA1-2000 NA1-3200 NA1-4000 NA1-6300


Rated current □630 □800□1000 □2000 □2500 □4000□5000
□4000
(In)A □1250 □1600 □2000 □3200 □6300(only 3 poles)

Installation mode □Drawerout type □Fixed type (note: =In 4000A fixed type is not available)
Number of poles □Three poles □Four poles
Protection function Others functions Optional function
□M-typ e
1. □Ir1 protection for overload long time-delay, Ir2 inverse-time protection
sta ndard + definite time-delay protection for short-circuit short time-delay, Ir3 □ Display of voltage
typ e (default instantaneous protection for short-circuit, Ir4 4-section protection for □ Display of frequency
single-phrase earthing. 1. Function of current □ Display of power factor
configuration)
2. □Ir1 protection for overload long time-delay, Ir2 definite time-delay meter □ Display of power
protection for short-circuit short time-delay, Ir3 instantaneous protection 2. Function of □ Function of monitoring
for short-circuit, Ir4 4-section protection for single-phrase earthing. self-diagnosis load
3. Function of setting
Intelligent controller

1. Ir1 protection for overload long time-delay, Ir2 definite time-delay protection ! Not items to be selected
□H-type for short-circuit short-delay, Ir3 instantaneous protection for short-circuit, 4. Function of test necessarily, cost of the
Communication- 4-section protection for single-phrase earthing. 5. Function of display increased will be calculated
type (optional) 2. Ir1 protection for overload long time-delay, Ir2 inverse-time protection + additionally
definite time-delay protection for short-circuit short time-delay, Ir3 instantaneous
protection for short-circuit, 4-section protection for single-phrase earthing.

Available set range of Ir1 long-delay current:(0.4~1)In !Conventional setting before delivery: overload long time-delay: 1.0In
Explanation:
Available set range of operating time with overload 1.5In: 15, 30, 60......480s !Conventional setting before delivery: overload 1.5In, operating 15s
Available set
range of ! Conventional setting before delivery: short time-delay current 8Ir1
protection Available set range of current of Ir2 short-delay; Operating time of short-delay: 0.1~0.4s ! Conventional setting before delivery: operating time of short time-delay: 0.4s 0.1~0.4s
function and
conventional Available set range of Ir3 instantaneous current : 1.0 In~50kA/75kA/100kA
setting before ! Conventional setting before delivery: 12In
delivery Available set scope of Ir4 earthing protection current: 0.2~0.8 In; Available set scope of operating time of earthing protection: 0.1~0.4s
! Conventional setting before ex-factory: 0.5 In;OFF
Power supply of controller □AC380V, □AC220V, □DC220V, □DC110V (Optional)
Under-voltage □AC380V, □AC220V, □DC220V, □customize V (Optional)
Electrical accessories

release (default
configuration) □Instantaneous □Delay s; □ Time delay of R-C (Resistance-Capacity) type Undser-voltage release: (1~5)s (Optional)
Shunt release
(default □AC380V, □AC220V, □DC220V, □DC110V (Optional)
configuration)
Motor (default
□AC380V, □AC220V, □DC220V, □DC110V (Optional)
configuration)

Interlocking □ Connecting-rod interlocking (only provided for drawer-type)


requirements

device (cost will □ Steel cable interlocking :( for both types of drawer-type and fixed-type) □ Button lock (Optional)
be calculated □ Key lock: ( for both types of drawer-type and fixed-type) □ Door interlock (open or closed position)
Special

additionally) □ Door interlock(status of ON/OFF)


Others functions (cost will be calculated additionally) □ Function of earthing protection with external mutual-inductor (Mutual-inductor is prepared by the user)

Connection of main circuit □ Explanation of vertical connection (prepared with vertical bus-bar): conventional supply is horizontal connection
□ Revolving bus-bar (Drawerout type In≤3200) (cost of the increased will be burden by the user)

Remark: Current of frame size, rated current, and auxiliary control voltage must be indicated when ordering

Note: 1) Please mark “√”or fill figure in the relative“□”if no mark, we will provide according to conventional factory settings.
2) For ordering products with optional function or special requirements, please contact with us.

NA1-6300 NA1-4000 NA1-3200 NA1-2000

> >> 65
Air Circuit Breaker
NA1
Configurations explanation 2. NA1-1000 fundamental configurations
a. Motor-driven:
1. NA1-2000~6300 fundamental configurations Under-voltage instantaneous release;
a. Motor-driven: Shunt release;
Under-voltage instantaneous release; Closing electromagnet;
Shunt release; Motor driven operating mechanism;
Closing electromagnet; 4 normal open and 4 normal close auxiliary contacts;
Motor driven operating mechanism; M-type Intelligent Controller;
4 suits of transform contact; Closing and breaking push button lock;
M-type Intelligent Controller; Horizontal wiring of main circuit;
Horizontal wiring of main circuit; Doorcase;
Doorcase; Element of main circuit;
Element of main circiut; Operating instructions of Air Circuit Breaker;
Operating instructions of Air Circuit Breaker; Packing box;
Packing box; Drawer seat(Drawout type)
Drawer seat (Drawout type)
b. Manual:
b. Manual: Under-voltage instantaneous release;
Under-voltage instantaneous release; 4 normal open and 4 normal close auxiliary contacts;
4 suits of transform contact; M-type Intelligent Controller;
M-type Intelligent Controller; Horizontal wiring of main circuit;
Horizontal wiring of main circuit; Closing and breaking push button lock;
Doorcase; Doorcase;
Element of main circuit; Element of main circuit;
Operating instructions of Air Circuit Breaker; Operating instructions of Air Circuit Breaker;
Packing box; Packing box;
Drawer seat(Drawout type) Drawer seat(Drawout type)

3. Additional selective configurations(need extra cost) 4. Additional selective configurations(need extra cost)
NA1-2000~6300 selective configurations explanation: NA1-1000 selective configurations explanation:

Under-voltage time release(1s, 3s, 5s). Breaking button locking device;


Connecting-rod type mechanical interlock Vertical bus bar;
(Drawerout type). Mechanical interlock;
Cable mechanical interlock; Transparent cover;
Operation pushbutton lock; Multifunctional intelligent controller;
Key lock;
Door interlock; Note: Please indicate the voltage when orderd
Outer transformer with earthing protect function; If there is additional function and special
Vertical bus bar; requirement, please contact with the manufacturer.
Rotating bus bar(In≤3200);
Indication mechanism;
Counter;
Shield;
5 suits of transform contact.

66 > >>
Air Circuit Breaker
NA1
Detailed certificate

Model Voltage Frame size Rated current Poles EU Netherlands Ukraine Russia South Africa

1000 200 400 630 800 1000 ■ ■ ■ _ _

630 800 1000 1250


2000 3P 4P ■ ■ ■ ■ ■
1600 2000 Except 800

NA1 400V 3200 2000 2500 3200 ■ ■ ■ ■ _


Except 2000

4000 3P _ _ _ _ _
4000


4000 5000 3P 4P ■ ■ ■ Except 5000 ■
6300

6300 3P ■ ■ ■ ■ ■

1000 200 400 630 800 1000 _ _ ■ _ _

630 800 1000 1250 _


2000 3P 4P ■ ■ ■ ■
1600 2000 Except 800

NA1 690V 3200 2000 2500 3200 ■ ■ ■ ■ _


Except 2000

4000 3P _ _ ■ _ _
4000

■ _
4000 5000 3P 4P ■ ■ ■ Except 5000
6300

3P ■ ■ ■ ■ _
6300

> >> 67
Air Circuit Breaker

ZHEJIANG CHINT ELECTRICS CO.,LTD


Add: No. 1, CHINT Road, CHINT Industrial Zone, North Baixiang,
Yueqing, Zhejiang Province, [Link] 325603
Tel: +86-577-62877777
Fax: +86-577-62775769 62871811
EN B03

E-mail: global-sales@[Link]
Website: [Link] Jan 2010

CHINT Electric All Rights Reserved Recycle Paper Printed Specifications and technical data are subject to change without notice.