This document provides information about air circuit breakers (ACBs) including: 1. An introduction to ACBs including their purpose of distributing and protecting power, type designation information, features, classifications by installation type, operation mode, connection, pole, and accessories. 2. Details about the structure of ACBs including labeled diagrams of their main components. 3. Specification tables listing technical parameters like rated current and voltage values for different frame sizes. 4. Sections on intelligent controller specifications and protection characteristics, characteristic curves, usage instructions, secondary wiring diagrams, accessories and functions, safety distances, temperature compensation, dimensions, mounting instructions, and maintenance.

Uploaded by

LUAT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
309 views

Distributor: Breaker & Switchgears Overseas Sales Dept

This document provides information about air circuit breakers (ACBs) including: 1. An introduction to ACBs including their purpose of distributing and protecting power, type designation information, features, classifications by installation type, operation mode, connection, pole, and accessories. 2. Details about the structure of ACBs including labeled diagrams of their main components. 3. Specification tables listing technical parameters like rated current and voltage values for different frame sizes. 4. Sections on intelligent controller specifications and protection characteristics, characteristic curves, usage instructions, secondary wiring diagrams, accessories and functions, safety distances, temperature compensation, dimensions, mounting instructions, and maintenance.

Uploaded by

LUAT
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 58

http://www.seec.com.

tw
http://circuit-breaker.seec.com.tw
Contents

AIR CIRCUIT BREAKER


1. Introduction 1
1.1 Purposes 1
1.2 Type designation 1
1.3 Feature 1
1.4 Classification 1
1.5 Conditions of use 1
2. Structure specifications 2
3. Specification 3
3.1 Specification 3
3.2 Accessory Specification 4
4. Intelligent Controller 5
4.1 Specification 5
4.2 Function Table 6
4.3 Protection Characteristics 7
4.3.1 Technical parameters 7
4.3.2 AIC-H other function 14
4.3.3 Display Measurement Parameter 17
4.3.4 Other functions 19
5. Characteristic Curves 22
5.1 Overload(EIT)、Short-circuit、Instantaneous protection 22
5.2 Five Tripping Curves (EIT、SIT、VIT、DT、HVF) 23
5.3 Ground fault protection 23
5.4 Leakage protection 24
6. Intelligent Controller Usage 25
6.1 Panel Schematic Diagram 25
6.2 Page Description 27
6.2.1 Measurement Page 27
6.2.2 Parameter page 31
6.2.3 Maintenance page 34
6.2.4 Testing page 35
6.2.5 Language, communication page 35
6.2.6 Record page 36
6.3 Factory setting 37
7. Secondary Wiring Diagram 39
7.1 Controller and Circuit Breaker Wiring 39
7.2 Secondary Wiring Diagram 40
7.2.1 AIC-E/A Type Controller 40
7.2.2 AIC-H Type Controller 40
7.2.3 Remote Control Secondary Wiring 41
8. Accessories and functions 42
8.1 Mechanical interlock 42
8.2 Door Frame 43
8.3 Door Interlock 43
8.4 Under voltage release 43
8.5 Power Module 44
8.6 External sensor for neutral conductor (for 3P+N) 44
8.7 Zero-phase sequence current sensor (ZCT) 45
8.8 External units of transformer's center 45
9. Safety Distance 47
10. Temperature Compensate 47
11. Busbar Dimension 47
12. Outline and Installation Dimensions 48
12.1 Draw out type 48
12.2 Fixed type 49
13. Mounting, Usage, and Maintenance 50
13.1 Mounting 50
13.2 Commonly Problem and Trouble-shooting 51
1. Introduction
INSTRUCTIONS

1.1 Purposes
BW-1600 series air circuit breakers(referred to as circuit breaker) are used in rated voltage AC720V and below, 50/60Hz
distribution system, with rated current from 400A to 1600A. It's used for distributing power and protecting circuits in
the electrical distribution system is protected from overloading, short circuit, ground fault, and other hazardous faults.
The protective actions have a high precision for preventing unnecessary power failure, closing power supply much more
reliable.

1.2 Type Designation

BW-1600

Pole:3: 3P, 4: 4P
Model:SN

Frame size(AF)

BW series

1.3 Feature
■ Compact structure, smaller size
■ High breaking capacity
■ No arcing distance, high security
■ Intelligent protection and network communication
■ Energy measurement, harmonic analysis
■ Wiring direction does not affect product.

1.4 Classification
■ Installation type: Draw-out, fixed type
■ Operation mode: Electric and manual operation
■ Connection: Horizontal
■ Pole: 3P, 4P
■ Accessory: Intelligent tripping unit, Under-voltage release, Shunt release

1.5 Conditions of use


■ Ambient temperature:-25℃ ~ +70℃ , E type can be use at -40℃ .
Note: (1) If the ambient temperature exceed 40℃ , should consider derating.
(2) If the ambient temperature exceed above range, please notify us when ordering the product
■ The product cannot be installed at places above 2000m altitude.
■ Atmospheric conditions: Relative humidity could not exceed 50% when the surrounding temperature is +40℃ .
For lower temperature, the relative humidity can be higher. The average maximum relative humidity for the month
with the highest humidity is 90%, and the average lowest temperature of that month is +25℃ . Please consider
the possibility of frosting on the surface of the product due to temperature change.
■ Pollution level: 3
■ Mounting conditions: Consult this manual for circuit breaker installation.
ACB
■ Wiring: Can be reverse wiring.
1
2. Structure Specifications

AIR CIRCUIT BREAKER


1

5
6
3
7
8
9
10
11
12

4 13

18
14
15
17 16

1. Secondary circuit terminal (Fixed)


2. Cradle
3. Safety baffle
4. Position indicator
5. Secondary circuit terminal (Moving)
19
6. Auxiliary contacts
7. Shunt release
8. Under-voltage release
9. Closing release
10. Operation handle
11. Closing button
12. Energy storage status indicator
13. Gear motor
14. Open button
15. Contact position indicator
16. Mechanism
17. Intelligent controller
18. Handle
19. Cover

ACB
2
3. Specification
INSTRUCTIONS

3.1 Specification

Frame Size 1600AF

Rated Current, In (A) 400 、630、800、1000 1250、1600

Rated Voltage, Ue AC690 / 720V、AC400 / 415V

Insulation Voltage, Ui AC1000V

Rated Impulse Withstand Voltage, Uimp 12kV

Pole 3P、4P

Rated Current of Neutral (%) 100%In

Model SN

AC400V / 415V 65 / 65
Icu / Ics (kA)
AC690V / 720V 50 / 50
Breaking
Capacity
Icw (kA) 1sec 50

AC400V / 415V 143


Icm (kA)
AC690V / 720V 105

Arcing distance (mm) 0

Max. total breaking time (s) ≤30

Max. closing time (ms) ≤70

AC400V 10000 8000


Electrical
AC690V 6500 5000
Endurance
(20times /h)
Without maintenance 15000
Mechanical
With maintenance 20000

3P 312 × 265 × 201


Fixed Type
Dimension 4P 312 × 335 × 201
(mm)
(H × W × D) 3P 345 × 275 × 300
Draw out Type
4P 345 × 345 × 300

ACB
3
3.2 Accessory Specification

AIR CIRCUIT BREAKER


AC50Hz DC

Rated voltage

220~240V 380~ 415V 220V 110V

Power consumption 320VA 440VA 290W 140W


Closing
release
Operating voltage range (0.85~1.1) Us

Power consumption 320VA 440VA 290W 140W

Shunt release

Operating voltage range (0. 7~1.1) Us

Power consumption 50VA 50W

Motor gear

Operating voltage range (0.85 ∼ 1.1) Us

Delay: 1s / 3s / 5s
Operating time
Instantaneous

Power consumption 0.5VA 0.5VA

(35%~70%) Ue Break the circuit breaker


Under voltage

release
Operating
<35% Ue Circuit breaker cannot closed
voltage range

(85%~110%) Ue Reliable close the circuit breaker

Operating voltage up to 85%


No break of circuit breaker
Ue in 1/2 delay time

Type 4NO4NC

Auxiliary
Thermal rated current of auxiliary contact 6A
contacts

Power consumption 300VA 60W

ACB
4
4. Intelligent Controller
INSTRUCTIONS

4.1 Specification

Type Protection Optional Other function

AIC-E G

O Overcurrent (LSI) ● MCR protection


● Thermal memory
G Ground fault (vector sum) ● Over temperature
Standard indicator
W Ground fault
(Source Ground Return)
(note 1)

N/A
AIC-A G

O Overcurrent (LSI)
● LCD display

G Ground fault (vector sum) ● Fault record history


● Current-unbalance
Current type ● Test function
W Ground fault
(Source Ground Return)

F Earth leakage + ZCT (note 2)

AIC-H G C

● ZSI protection
O Overcurrent (LSI) ● Voltage protection
● Frequency protection
G Ground fault (vector sum) ● Power and energy
N/A
Harmonic type C ● Harmonic analysis
W Ground fault ● Load monitor
communication
(Source Ground Return) ● Four-set signal output

F Earth leakage + ZCT

Note: 1.Earth grounding (Source Ground Return) function must pair with external sensor of transformer's center and external module
of transformer's center.
ACB 2. Earth leakage function must pair with a ZCT.

5
4.2 Function Table

AIR CIRCUIT BREAKER


Controller
Frame Size 1600AF
AIC-E AIC-A AIC-H
Overload long-time delay protection EIT ■ ■ ■

5 overload characteristics curves selection ■ ■

Short-circuit, short-time delay protection ■ ■ ■

Instantaneous protection ■ ■ ■

Ground fault protection □ □ □

Earth leakage protection □ □

Ground fault alarm (note 1) □ □

Earth leakage alarm □ □

Overload pre-alarm ■ ■ ■

MCR Protection ■ ■ ■

Protection and alarm Neutral protection ■ ■ ■

Load monitor ■

Thermal memory functions ■ ■ ■

Current-unbalance ■ ■

Voltage-unbalance ■

Over (under) voltage ■

Over (under) frequency ■

Phase sequence ■

Reverse Power ■

Demand current ■

ZSI (Zone selective Interlocking) ■

Current ■ ■

Current unbalance ■ ■

Voltage ■

Voltage unbalance ■

Frequency ■

Measurement and display Phase sequence ■

Power ■

Energy ■

Demand Current ■

Demand Power ■

Harmonic ■

Over-temperature ■ ■ ■

Maintenance Contact wear indication ■ ■

Refuse action ■ ■ ■

Trip record ■ ■

Alarm record ■ ■

History and Record Trip times ■ ■

Operation counter ■ ■

Position Change record ■ ■

Four-set signal output ■

Others Self-testing ■ ■

Communication □

■ Standard □ Option
Note 1:Notification by LED indicator only for AIC-E/AIC-A controller. Signal output support for AIC-H controller.
ACB
6
4.3 Protection Characteristics
INSTRUCTIONS

4.3.1 Technical parameters


■ Overload Protection EIT(AIC-E)

Adjust range:
Iu:0.4-0.45-0.5-0.55-0.6-0.65
Current setting Ir=(0.4~1) In -0.7-0.75-0.8-0.85-0.9-0.95In
Ir:0-0.005-0.01-0.015-0.02-0.025
Overload -0.03-0.035-0.04-0.045-0.05In +Iu
long-time delay
protection
Operation characteristics Trip at 1.05~1.2Ir

Time delay Tr=0.5~24s@6Ir 0.5-1-2-4-8-12-16-20-24

Accuracy ±20%

Thermal memory 30min ( factory default)

■ Overload Protection(5characteristic curves, AIC-A/AIC-H)

Adjust range:
Iu:0.4-0.45-0.5-0.55-0.6-0.65
Current setting Ir = (0.4~1) In -0.7-0.75-0.8-0.85-0.9-0.95In
Ir:0-0.005-0.01-0.015-0.02-0.025
-0.03-0.035-0.04-0.045-0.05In +Iu
Overload
long-time delay
Operation characteristics Trip at 1.05~1.2Ir
protection

Time delay Tr = 0.5~24s@6Ir 0.5-1-2-4-8-12-16-20-24 note 1

Accuracy ±20%

Tripping curve EIT-DT-SIT-VIT-HVF

Thermal memory 30min (Can be disabled)

■ Overload long-time delay protection characteristics

Characteristics Current ratio (I/Ir) Trip Time

No trip ≤1.05 ≥2h no trip

Trip >1.2 <2h trip

Note: 1.Maximum Tr setting value=4s when tripping-curve is set to HVF.


2. When Tr=0.5s or Tr=1s, short-circuit short time delay protection is set to definite time.
3. When fault current I≥10Ir, operation time is same as I=10Ir.

ACB
7
Overload long time delay protection characteristics (s):

AIR CIRCUIT BREAKER


EIT 0.5 1 2 4 8 12 16 20 24

1.5×Ir 14 28 56 112 224 336 448 560 672

2×Ir 5.83 11.67 23.33 46.67 93.3 140 186.7 233.3 280

Time delay (s) 6×Ir 0.5 1 2 4 8 12 16 20 24

7.2×Ir 0.5 0.69 1.38 2.75 5.51 8.26 11.01 13.77 16.52

10×Ir 0.5 0.50 0.71 1.41 2.83 4.24 5.66 7.07 8.48

DT 0.5 1 2 4 8 12 16 20 24

1.5×Ir 0.5 1 2 4 8 12 16 20 24

2×Ir 0.5 1 2 4 8 12 16 20 24

Delay time (s) 6×Ir 0.5 1 2 4 8 12 16 20 24

7.2×Ir 0.5 1 2 4 8 12 16 20 24

10×Ir 0.5 1 2 4 8 12 16 20 24

SIT 0.5 1 2 4 8 12 16 20 24

1.5×Ir 3.23 6.45 12.90 25.81 51.61 77.42 103.23 129.04 154.84

2×Ir 1.75 3.50 7.00 14.00 28.00 41.99 55.99 69.99 83.99

Delay time (s) 6×Ir 0.5 1 2 4 8 12 16 20 24

7.2×Ir 0.5 0.86 1.72 3.45 6.89 10.34 13.78 17.23 20.67

10×Ir 0.5 0.67 1.34 2.68 5.36 8.05 10.73 13.41 16.09

VIT 0.5 1 2 4 8 12 16 20 24

1.5×Ir 5 10 20 40 80 120 160 200 240

2×Ir 2.5 5 10 20 40 60 80 100 120

Delay time (s) 6×Ir 0.5 1 2 4 8 12 16 20 24

7.2×Ir 0.5 0.81 1.61 3.23 6.45 9.68 12.90 16.13 19.35

10×Ir 0.5 0.56 1.11 2.22 4.44 6.67 8.89 11.11 13.33

HVF 0.5 1 2 4 8 12 16 20 24

1.5×Ir 159 319 638 1275 2550 3825 5100 6375 7650

2×Ir 43.17 86.33 172.7 345.3 690.7 1036 1381 1727 2072

Delay time (s) 6×Ir 0.5 1 2 4 8 12 16 20 24

7.2×Ir 0.50 0.50 0.96 1.93 3.86 5.78 7.71 9.64 11.57

10×Ir 0.50 0.50 0.50 0.52 1.04 1.55 2.07 2.59 3.11

Note: EIT: extremely inverse time curve (I²t)


DT: definite time curve
SIT: standard inverse time curve (I0.5t)
VIT: very inverse time curve (It)
HVF: compatible with high-voltage fuses (I4t)

ACB
8
■ Short-circuit Short time delay protection characteristics
INSTRUCTIONS

Adjust range:
Current setting Isd = (1.5~10) Ir
1.5-2-2.5-3-4-5-6-8-10+OFF

Accuracy ±10%

Short-circuit, Adjust range:


Short-time delay
I2T on (Inverse time): Tsd = (0.1~0.4) s
protection Time delay I2T on (Inverse time): 0.1-0.2-0.3-0.4
I2T off (Definite time):Tsd = (0~0.4) s

I2T off (Definite time): 0-0.1-0.2-0.3-0.4

Operation characteristics Inverse time / Definite time

Accuracy ±20% or ±30ms (Tsd=0s, tolerance: 0.06s±30ms)

AIC-E: 15min(factory default)


Thermal memory
AIC-A/AIC-H: 15min (Can be disabled)

Short-circuit short time delay protection characteristics (s):

Tsd S (Inverse time)


M=I/Ir 0.1 0.2 0.3 0.4

10.0 0.10 0.20 0.30 0.40

9.0 0.12 0.25 0.37 0.49

8.0 0.16 0.31 0.47 0.63

7.2 0.19 0.39 0.58 0.77

6.0 0.28 0.56 0.83 1.11

5.0 0.40 0.80 1.20 1.60

4.0 0.63 1.25 1.88 2.50

3.0 1.11 2.22 3.33 4.44

2.0 2.50 5.00 7.50 10.00

1.9 2.77 5.54 8.31 11.08

1.8 3.09 6.17 9.26 12.35

1.7 3.46 6.92 10.38 13.84

1.6 3.91 7.81 11.72 15.63

1.5 4.44 8.89 13.33 17.78

Note: 1.when the fault current is greater than maximum setting (10Ir), controller will protect according to current definite time setting.

■ Short-circuit instantaneous protection characteristics

Adjust range:
Current setting Ii = (2~15) In
2-4-6-8-10-11-12-15+OFF
Short-circuit
instantaneous
Accuracy ±15%

Operating time ≤60ms

ACB
9
■ Ground fault protection characteristics

AIR CIRCUIT BREAKER


Adjust range:
Current setting Ig = (0.2~1) In
0.2-0.3-0.4-0.5-0.6-0.7-0.8-1+OFF

Accuracy ±10%

Adjust range:
Ground fault
protection I2T on (Inverse time): Tg = (0.1~0.4) s
Time delay I2T on (Inverse time): 0.1-0.2-0.3-0.4
I2T off (Definite time): Tg = (0~0.4) s

I2T off (Definite time): 0-0.1-0.2-0.3-0.4

Operation characteristics Inverse time / Definite time

Accuracy ±20% or ±30ms (Tg=0s, tolerance: 0.06s±30ms)

There are two kinds of protection modes: Vector sum, Source Ground Return
Vector sum: Measures current between phase line and neutral in a TN-S system. When ground fault occurred,
part of the current will flow back to transformer via PE line, causing the current vector sum
(Ig= Ia+Ib+Ic+IN) no longer equal to 0, thus detecting ground fault. Adding an external current
transformer to 4 poles or the N phase of 3 pole (3P+N) breaker, and pair with an internal sensor to
send signal to controller, opening the breaker when ground fault occurred.

CT CT CT
A A A
B B B
C C C
PEN N
PE Intelligent
Intelligent Intelligent
Controller
Controller Controller
N
PE
3P 4P 3P+N
Grounding current: Measure current between phase line and neutral in a TN-S system, measure in the Neutral
- earth link of the LV transformer (shown below), when there is a grounding fault, PE line will generate current,
causing fault determined.

A
B
C
N
External sensor of Intelligent
transformer's center
Controller
PE
External module of
transformer's center
Grounding Current

Note: TN-S is 3 phase 5 wires, including A、B、C、N、PE.


ITN-C is 3 phase 4 wires, including A、B、C、PEN. TN-C system does not have grounding protection.

ACB
10
Ground fault protection characteristics (s):
INSTRUCTIONS

Tg G (Inverse time)
M=I/In 0.1 0.2 0.3 0.4

1.0 0.10 0.20 0.30 0.40

0.9 0.12 0.25 0.37 0.49

0.8 0.16 0.31 0.47 0.63

0.7 0.20 0.41 0.61 0.82

0.6 0.28 0.56 0.83 1.11

0.5 0.40 0.80 1.20 1.60

0.4 0.63 1.25 1.88 2.50

0.3 1.11 2.22 3.33 4.44

0.2 2.50 5.00 7.50 10.00

■ Earth leakage protection characteristics

Adjust range:
Current setting value If = 1~30A
1-2-3-5-7-10-20-30A+OFF

Accuracy -20%~0%

Adjust range:
Earth leakage
protection Trip: Tf = 0.1~0.8s
Delay setting value 0.1-0.2-0.4-0.8s
Alarm: Tf = 0.1~1s

0.1-0.2-0.4-0.8-1s

Operation characteristics Definite time

Accuracy ±10% or ±30ms(Tf=0.1s, tolerance: 0.1s±30ms)

Another is transformer mode of external Earth Leakage. The controller gets the output current signal from a
current transformer directly to protect. Generally, the secondary output of the transformer is 30A / 300mA.

ZCT ZCT
A A
B B
C C
N
PE
Intelligent Intelligent

Controller Controller

3PT 4PT

ACB
11
■ Ground fault alarm/ Earth leakage alarm/ Overload pre-alarm

AIR CIRCUIT BREAKER


Pickup Dropout
Characteristics
Threshold Time delay Threshold Time delay

Tg
Ground fault alarm 1.0Ig 0.9Ig Tg
Inverse / Definite time

Earth leakage alarm 1.0If Tf 0.8If Tf

Overload pre-alarm 0.9Ir 0.1s 0.8Ir 0.1s

When the current exceeds the pickup threshold, alarm indicators will blink and send the output signal (if
function were set); when the current falls below the dropout threshold, alarm function reset.
Note: Notification by LED indicator only for AIC-E / AIC-A controller. Signal output support for AIC-H controller.

■ MCR Protection
MCR is a protection for instantaneous short-circuit current when circuit breaker is connected. The breaker will
instantaneous trip when a short circuit current (≥12In) occurred during closing operation (≤100ms), operation
time is ≤60ms.

Current setting value IMCR = 12In

MCR Tripping Characteristics Between 0.85~1.15IMCR

Operating time ≤60ms

Note: Within 100ms of closing operation and with external power supply condition.

■ Neutral protection (N Phase)

Setting Type Description

The overload and short circuit short time delay protection for neutral line will activate with the setting of 50% Ir
50%Ir Half protection
The instantaneous and ground fault protection for neutral line will activate with the setting of Ir.

The overload and short circuit short time delay protection for neutral line will activate with the setting of Ir
100%Ir Full protection
The instantaneous and ground fault protection for neutral line will activate with the setting of Ir.

OFF None Non-neutral wire protection

■ Thermal Memory Functions


Repeated overload can heat up the conductor or other devices. The controller can simulate the heating
conditions as well as the Overload long-time delay, short-circuit short time delay and other fault or delay
actions to generate the thermal effect (simulating characteristics of the double-metal piece). The overload
long-time delay thermal effect energy will be completely released in 30 minutes after eliminating the fault. For
short-circuit delay thermal effect energy, it will be completely released in 15 minutes after eliminating the fault.
During the period, the delay time will be shortened if the reclosing circuit breaker has overload long-time delay
or short circuit short-time delay. This is to provide circuits and devices better protection.

ACB
12
■ Current Unbalance Protection
INSTRUCTIONS

Current unbalance protection is to protect when loss of phase or unbalance of phase current, the protection is
based on unbalance percentage.
When the 3 phase current unbalance is greater than Pickup threshold and time, the breaker will trip or send out
alarm signal. When the protection type is set to alarm, alarm signal will disarm when the unbalance value is less
then Pickup threshold and time.
Current unbalance calculation:

I∆max
Iavg
ll∆maxl
lunbal = X 100%
lavg

la+lb+lc
lavg = 0
3 Ia Ib Ic
In the equation, Iavg:Ia,Ib,Ic 3 phase average current (RMS). I∆max:maximum difference of each phase and
Iavg.

Threshold Operation Protection


Item Setting range Step
accuracy accuracy type

Pickup 20%~80%, and ≥ dropout


1%
threshold threshold
Pickup time
Current 1~40s, definite time 1s trip /
delay ±5%
unbalance ±10% alarm /
Dropout 20%~80%, and ≤ Pickup (absolute)
IU 1% OFF
threshold threshold
Dropout time
10~360s, definite time 1s
delay

ACB
13
4.3.2 AIC-H other function

AIR CIRCUIT BREAKER


Threshold Operation Protection
Item Adjustment range Step
accuracy accuracy type

Pickup threshold 0.4~1.0In, and ≥ than Dropout threshold 0.1In


Demand
current Pickup time delay 15~1500s, definite time 15s
±10%
protection Dropout threshold 0.4~1.0In, and ≤ than Pickup threshold 0.1In
ID
Dropout time delay 15~3000s, definite time 15s

Pickup threshold 77~828V, and ≤ Dropout threshold 1V

Under-voltage Pickup time delay 1~30s, definite time 0.1s


±5%
UV Dropout threshold 77~828V, and ≥ Pickup threshold 1V

Dropout time delay 1~100s, definite time 0.1s

Pickup threshold 77~828V, and ≥ than Dropout threshold 1V

Over-voltage Pickup time delay 1~5s, definite time 0.1s


±5% ±10%
OV Dropout threshold 77~828V, and ≤ than Pickup threshold 1V

Dropout time delay 1~36s, definite time 0.1s

Pickup threshold 5%~50%, and ≥ than Dropout threshold 1%

Voltage Pickup time delay 1~40s, definite time 1s ±5%


unbalanced
Dropout threshold 5%~50%, and ≤ than Pickup threshold 1% (absolute)
UU

Dropout time delay 10~360s, definite time 1s Trip /


alarm /
Pickup threshold Order(ABC)- reverse(ACB)-OFF OFF
Phase Pickup time delay 0.3s
sequence —
△Φ Dropout threshold Same as Pickup threshold

Dropout time delay 3s

Pickup threshold 20~500KW, and ≥ than Dropout threshold 1kW

Reverse Pickup time delay 0.2~20s, definite time 0.1s


power ±10%
RP Dropout threshold 20~500KW, and ≤ than Pickup threshold 1kW

Dropout time delay 1~360s, definite time 1s

Pickup threshold 45~65Hz, and ≥ than Dropout threshold 0.5Hz

Over Pickup time delay 0.2~5s, definite time 0.1s ±10% /


frequency ±0.5Hz
Dropout threshold 45~65Hz, and ≤ than Pickup threshold 0.5Hz ±30ms
OF

Dropout time delay 1~360s, definite time 1s

Pickup threshold 45~65Hz, and ≤ Dropout threshold 0.5Hz

Under Pickup time delay 0.2~5s, definite time 0.1s


frequency ±0.5Hz
UF Dropout threshold 45~65Hz, and ≥ Pickup threshold 0.5Hz

Dropout time delay 1~360s, definite time 1s

Protection type Method 1 / Method 2


Load monitor ±10% ±10%
Current Setting Ic1/Ic2 Ic=(0.5~1)Ir1, Ic1≥Ic2 0.1Ir
Trip / OFF
Ground fault / Short
ZSI ON/OFF ±10% 60±30ms
circuit
ACB
14
■ Reverse power protection
INSTRUCTIONS

Reverse power protection is active when sum of 3 phase's active power direction is different form the user
setting, and the value is greater than the setting value and time.

■ Phase sequence protection


If 2 out of the 3 phase voltage is reverse, the protection will activate. If one phase is gone, the protection will
deactivate.

■ Load monitor

Current Ic1 = (0.5~1.0) Ir Adjust step length: 0.1

setting Delay relay closing at 1.05~1.2 Ic1

Operation 0.5Tr protection and the characteristics are the same as overload long time delay protection.
Method 1
characteristics Ic2 = (0.5~1.0) Ir, ≤Ic1 Adjust step length: 0.1

Time delay Delay relay closing at 1.05~1.2 Ic2

Current setting 0.25Tr protection and the characteristics are the same as those of overloading and long-delay.

Operation Ic1 = (0.5~1.0) Ir Adjust step length: 0.1

characteristics Delay relay closing at 1.05~1.2 Ic1

Time delay 0.5Tr protection and the characteristics are the same as overload long time delay.
Method 2
Current Ic2 = (0.5~1.0) Ir, ≤Ic1 Adjust step length:0.1

setting <Ic2, delay relay closing

Operation 60s

The controller can program the output of two passive signal contacts for load monitor. The output signal
contacts can be used for monitoring alerts, controlling the load of tripping sub-circuit and ensuring a normal
power supply for the main system. There are two types of load monitor methods available (the user can choose
one of them).
1. Method 1: It can be used to control two sub-circuit loads. When the working current exceeds 1.2Ic1 or 1.2Ic2,
controller will delay the output of signal contacts according to inverse time characteristics. The
characteristic curve of inverse time and the characteristic curve of overload long-time delay are
the same, but the setting current value can be set independently.
2. Method 2: It is generally used to control sub-circuit loads. When the working current exceeds 1.2Ic1, the controller
will output signal contact point break sub-circuit load according to inverse time characteristics.
The characteristic curve of inverse time and the characteristic curve of overload long-time delay
are the same, but the setting value has to be Ic1Ic2. If after tripping the sub-circuit load, the current
will return to normal. When the current is lower than Ic2 for 60s continuously, the controller will
output another signal contact to pick up the broken load and restore the power supply of system.

ACB
15
■ ZSI (Zone selective Interlocking)

AIR CIRCUIT BREAKER


1# Zo1
Upstream Zo2
Breaker Zi1
Zi2

2# Zo1
Zo2
Zi1
Zi2

Downstream
Zo1 Breaker Zo1
Zo2 Zo2
Zi1 Zi1
Zi2 Zi2

Zone-selective interlocking (ZSI) has multiple classified protection system which is designed to minimize
the faulty impact on whole electrical distribution system by reducing the time it takes to clear the fault and
maintaining system coordination. This function is suit with short circuit and ground fault protection (I2t is set to
off )

Example:
1. Occurrence of Fault A: The upstream breaker (1#) received no signal from downstream breaker and performs
instantaneous trip operation to protect system.
2. Occurrence of Fault B: Breaker (2#) will send ZSI signal to upstream breaker (1#) and breaker (1#) will obey their
delay setting to maintain coordination in other areas of the system. Breaker (2#) received no ZSI signal from
downstream breaker and performs instantaneous trip operation.

Connection and limits:


Use twisted pair or shielded cable, 14AWG-2.5mm2/22AWG-0.4mm2, maximum length of 300m.
Maximum of 15 downstream equipment can be connect to input of ZSI(Zi1-Zi2)
Maximum of 15 upstream equipment can be connect to output of ZSI(Zo1-Zo2).

Note: 1. The terminals breaker's Zi1 and Zi2 should be shorted, if its open, ZSI will trip when short-circuit and ground fault occurred.
2. Upper breaker's Isd or Ig cannot set to 0s, or ZSI may not be working properly.

ACB
16
4.3.3 Display Measurement Parameter
INSTRUCTIONS

Item Adjust range Accuracy Note

Phase current Ia、Ib、Ic


0.2~2In ±3%
N phase current IN AIC-E
AIC-A
Ground Ig 0.2~1In ±5% AIC-H
Current
Earth leakage If 0.5~30A ±5%

AIC-A
Current unbalance 0%~200% ±5% (absolute)
AIC-H

Line voltage Uab、Ubc、Uca 45~900V


±2.5%/±2V
Voltage Phase voltage Uan、Ubn、Ucn 26~528V

Voltage unbalanced 0%~200% (line voltage) ±5% (absolute)

Active power P (W)

Reactive power Q (Var) -30~30MW


Power ±10%
Apparent power S (VA)

Power factor PF -1~+1

Phase current Ia、Ib、Ic


Demand 0.2~2In ±3%
N phase current IN
current
Time window Window 5~60min Step 1min

Active power P

Demand Reactive power Q -30~30MW ±10%


power Apparent power S

Time window Window 5~60min Step 1min

Total energy E.P (kWh)


-2000G~+2000G AIC-H
Total energy E.Q (kVarh)

Total energy E.S (kVAh) 0~4000G

Energy Input energy E.P (kWh) ±10%

Input energy E.Q (kVarh)


-2000G~+2000G
Output energy E.P (kWh)

Output energy E.Q (kVarh)

Frequency F (A phase voltage frequency) 45~65Hz ±0.1Hz

Fundamental wave – Current I 0.2~2In ±3%

Line voltage 45~900V


Fundamental wave– Voltage U ±3%/±2V
Phase voltage 26~528V

THD、thd-current I
Harmonic 0~1000% ±5%
THD、thd- voltage U

FFT- current I
0~1000% ±5%
FFT-voltage U

Harmonic analysis 1~31harmonic analysis


ACB
17
■ System type

AIR CIRCUIT BREAKER


3Φ3W3CT:3 phase 3 wire 3 pole without neutral line, measure line voltage, phase current.
3Φ4W3CT:3 phase 4 wire 3 pole without neutral line, measure line & phase voltage, phase current.
3Φ4W4CT:3 phase 4 wire 4 pole (4Por 3P+N) with neutral line, measure line & phase voltage, phase current.

■ Voltage measuring
3 phase 4 wire, voltage N phase must be connected (secondary circuit terminal 21#).
3 phase 3 wire, voltage N phase (21#) and B phase (23#) must shorted.

■ Demand measurements
Required value:Average of current, power with in a time window for each phase.
Set the time window in measurement parameter (5~60min). If the setting had been change, the value will
automatic be recalculated.

■ Power Sign
P+:Forward measurement, corresponds to the usual flow, meaning from top to bottom
P -:Reverse measurement.
■ Power Diagram

P = - P =+
Q =+ Q =+
pf = - pf = +
P
P = - P =+
Q = - Q = -
pf = - pf = +

■ Energy measurement
Total energy: all of the energy.
Input energy: energy consumption, positive increase.
Output energy: energy release, reverse increase.
Energy measurement vales can be reset.

■ Harmonic measurement
Fundamental wave: measure fundamental wave current, line voltage, phase voltage.
Distortion rate: Total harmonics distortion (THD) rate to fundamental wave.
Total harmonics distortion (THD) rate to valid values.
FFT amplitude: display 3~31times of FFT amplitude of each odd harmonic, use rectangular display to show
different frequency harmonic amplitude, achieving harmonic spectrum analysis.
Waveform: Capture current, voltage waveforms in one cycle with real-time updates.

ACB
18
4.3.4 Other functions
INSTRUCTIONS

■ Self-diagnosed functions
When the working environment of the controller exceeds 70℃ or when 60% of the contact has been worn off
or when the circuit breaker cannot be tripped, the user would be notified by controller and relevant parameters
will meanwhile be recorded.

■ Trip/Alarm / Self-diagnosed records


Record up to 10 events records during faulted, including date, fault status and data.
Tripping fault type: overcurrent, ground fault / leakage (optional), current unbalance, voltage protection,
frequency protection reserves power.
Alarm fault type: ground fault / leakage (optional), current unbalance, voltage protection, frequency
protection reserves power.
Self-diagnosed fault type: over-temperature, contacts worn, breaker refused to trip.

■ Position change record


Every switch of mode is count as a position change, and the record detail is as listed:
Position Change date (year, month, day, hour, minute, second).
Position Change type (Open / close / trip).
Position Change reason (Manual / remote / fault / test).
Position Change record can show up to 10 times of recent switching record.

■ Operation counter
The total number of operating cycles will be registered and the data cannot be manually cleared.

■ Contact wearing rate


The controller will simulate and calculate the circuit breaker's main contact wearing rate according to
information such as the fault current at tripping. The contact value of the controller from the factory is 100%,
indicating no wearing of the contact point. The contact will be worn by a certain level due to every fault
induced tripping. If the value obtained from subtracting the corresponding amount of wearing from the current
contact value is less than 40%, the system will send out a self-diagnosed fault alert signal. After changing the
main contact of the circuit breaker, the user can reset the initial wear rate to 100% through the human-machine
interface or remote communication.

■ Test function
The controller will simulation an instantaneous trip test, causing the breaker to trip. It is use for breaker's on-site
debugging, regular maintenance and trouble shooting. The red reset button must be press before closing the
breaker every time, cannot be press during normal operation.

■ System clock
The system clock function is for recording the time and date during faults.

ACB
19
■ Programmable contact function

AIR CIRCUIT BREAKER


Controller has 2 sets of independent contact signal output; the function can be defined by controller interface
or remote compunction. Contacts function is listed below.

Code Contact type Contact output Contact cleared

1 N/A N/A N/A

2 Pre-alarm Pre-overload alarm Pre-overload cleared

3 Overload Overload long time delay trip Closing after fault is cleared

1. Closing after fault is cleared


4 Short circuit Short circuit short time delay trip
2. Function disable
1. Closing after fault is cleared
5 Instantaneous Instantaneous trip
2. Function disable
1. Closing after fault is cleared
6 MCR MCR fault trip
2. Instantaneous function enable
1. Load 1 abnormal cleared
7 Monitor 1 Load monitor Ic1 uninstall
2.Function disable
Load monitor Ic2 uninstall (method 1) or 1. Load 2 abnormal cleared
8 Monitor 2
overload (method 2) 2.Function disable

9 Ground / leakage Ground / leakage alarm

10 Unbalance (Iunbal) Current unbalance tripping alarm

11 Unbalance (Uunbal) Voltage unbalance tripping alarm

12 Over voltage Over voltage tripping alarm

13 Under voltage Under voltage tripping alarm 1. Closing after fault is cleared
14 Over frequency Over frequency tripping alarm 2. Function disable

15 Under frequency Under frequency tripping alarm

16 Demand value Demand current value tripping alarm

17 Reversed power Reversed power tripping alarm

18 Phase sequence Phase sequence tripping alarm

19 Trip Fault tripping status Closing after fault is cleared

20 Open Breaker in open mode Close the breaker

21 Close Breaker in close mode Open the breaker

22 Refused action Tripping failed, breaker refused to move Open the breaker

23 Over temperature Over temperature alarm Alarm cleared

24 Contact wear Contact serious wearing alarm Reset contact wearing rate

25 Remote open Remote open Contact continue 200ms

26 Remote close Remote close Contact continue 200ms

Note: 1. Contact is normal open, input is normal close (except load monitor lc2 method 2)
2. Non-closure contact: contact will remain operation before eliminating fault alarm.

ACB
20
■ Communication (AIC-HC optional)
INSTRUCTIONS

Achieve remote control, communication, metering and setting with RS-485 / Modbus-RTU support.
"Local" mode: controller will not respond to remote control, such as parameter modification or remote closing
/ opening.
"Remote" mode: Controller will respond to remote control, manual modification will not affect.
Cable: RS485Shielded twisted pair
Baud rate: 4800 / 9600 / 19200 / 38400bps adaptive.

■ Parameter lock
"Unlock" mode: parameter can be modify.
"Lock" mode: parameter cannot be modify.

ACB
21
5. Characteristic Curves

AIR CIRCUIT BREAKER


5.1 Overload (EIT)、Short-circuit、Instantaneous protection

10000
5000
Ir=0.4~1xIn
2000
1000
500

200
100
50
Tr=0.5~24s

20
10
t(s)

2
Isd=1.5~10xIr
1
I2t ON
0.5 0.4s 0.4s
0.3s 0.3s
0.2 0.2s
0.2s
0.1s
0.1 0.1s
0s I2t OFF 0s
0.05
Ii=2~15xIn
0.02
0.01
1 2 3 4 5 6 8 10 20 3 4 5 6 8 10 15 20 30

xIr xIn

ACB
22
5.2 Five Tripping Curves (EIT、SIT、VIT、DT、HVF)
INSTRUCTIONS

10000
5000

2000

1000

500

200
HVF
100
t(s)

50

EIT
20
10 VIT

5
SIT

2
DT
1

0.5
1 2 3 4 5 6 8 10 20

xIr

5.3 Ground fault protection

1000
500

200
100
50
Ig=0.2~1xIn
20
10

5
I2t ON
t(s)

2
1
Tg=0~0.4s
0.5 0.4s
0.3s 0.4s
0.2s 0.3s
0.2 0.2s
0.1s
0.1 0.1s
0s I2t OFF
0s
0.05

0.02
0.01
0.1 0.2 0.3 0.5 1 2 3

xIn
ACB
23
5.4 Leakage protection

AIR CIRCUIT BREAKER


1000
500

200
100
50

20
If=1~30A
10

5
t(s)

2
Tf=0.1~1.0s
1 1.0s
0.8s
0.5 0.6s
0.4s
0.3s
0.2 0.2s

0.1 0.1s

0.05

0.02
0.01
0.5 1 2 3 5 7 10 20 30 100 200 500

If(A)

ACB
24
6. Intelligent Controller Usage
INSTRUCTIONS

6.1 Panel Schematic Diagram E Type

AIC controller has E and A type, schematic diagram is shown.


E type controller can be defined by 3 zones:
LED operation light zone, knob tuning zone, operation status zone.
■ LED operation light zone:
Overload protection light Ir, short circuit protection light Isd,
instantaneous protection light Ii, ground fault protection light Ig.

■ Knob tuning zone: parameter for overload, short circuit, ground fault.

Iu=0.4~0.95In (12 values, step 0.05In)


Overload Current setting Ir
Ir=0~0.05In+Iu (11values, step0.005In))
protection
Time setting Tr 0.5-1-2-4-8-12-16-20-24s (@6Ir)

Current setting Isd 1.5-2-3-4-5-6-8-10Ir-OFF


Short circuit
I2t ON:0.1-0.2-0.3-0.4s (@10Ir)
protection Time setting Tsd
I2t OFF:0-0.1-0.2-0.3-0.4s

Instantaneous
Current setting Ii 2-4-6-8-10-11-12-15In-OFF
protection

Current setting Ig ≥80A 0.2-0.3-0.4-0.5-0.6-0.7-0.8-1In-OFF


Ground fault
I2t ON:0.1-0.2-0.3-0.4s (@1.0In)
protection Time setting Tg
I2t OFF:0-0.1-0.2-0.3-0.4s

■ Operation status zone: Run green light, Overload pre-alarmred light, alarm light.
LED
Status Overload
Run (green) Alarm Ir Isd Ii Ig
pre-alarm (red)

Overload protection trip - - light light - - -

Short circuit protection trip - - light - light - -

Open MCR protection trip - - light - - light -

Instantaneous protection trip - - light - - light -

Ground fault protection trip - - light - - - light

Normal light - - - - - -

Pre overload - blink - - - - -

Not refuse Overload protection - light - - - - -


action Short circuit protection - light - - - - -

Ground fault protection - - blink - - - -


Close Abnormal
power Overload protection - - blink light - - -
grid
Short circuit protection - - blink - light - -
Refuse
MCR protection - - blink - - light -
action
Instantaneous protection - - blink - - light -

Ground fault protection - - blink - - - light

Over temperature - - blink - - blink -


ACB
25
A/H controller can be defined by 4 zones:

AIR CIRCUIT BREAKER


LCD display zone, button control zone, knob tuning zone, operation status zone.
■ LCD display zone:
128*64 dot matrix display, display power grid parameter (current, voltage, etc),
protection parameter, records. Come with English or Chinese language.

■ Button control zone: include"Esc"、" ↑ "、" ↓ "、"↵" buttons.


"Esc":return button
" ↑ ":page up or increase value button
" ↓ ":page down or decrease value button A/H Type
" ↵ ":confirm button

■ Operation status zone: Run green light, Overload pre-alarm red light,
alarm light.
■ Knob tuning zone: parameter for overload, short circuit, ground fault.

Iu=0.4~0.95In (12 values, step 0.05In)


Overload Current setting Ir
Ir=0~0.05In+Iu (11values, step 0.005In)
protection
Time setting Tr 0.5-1-2-4-8-12-16-20-24s (@6Ir)

Current setting Isd 1.5-2-3-4-5-6-8-10Ir-OFF


Short circuit
I2t ON:0.1-0.2-0.3-0.4s (@10Ir)
protection Time setting Tsd
I2t OFF:0-0.1-0.2-0.3-0.4s

Instantaneous
Current setting Ii 2-4-6-8-10-11-12-15In-OFF
protection

Current setting Ig ≥ 80A 0.2-0.3-0.4-0.5-0.6-0.7-0.8-1In-OFF


Ground fault
I2t ON:0.1-0.2-0.3-0.4s (@1.0In)
protection Time setting Tg
I2t OFF:0-0.1-0.2-0.3-0.4s

Current setting If 1-2-3-5-7-10-20-30A-OFF


Earth leakage
Trip:0.1-0.2-0.4-0.8s
protection Time setting Tf
Alarm:0.1-0.2-0.4-0.8-1s

ACB
26
6.2 Page Description
INSTRUCTIONS

6.2.1 Measurement Page

0A
N A B C
简 体 150

繁 体 100

50
English
0

Metering Status
Status :

Setup I (A)
Null
Maint T ( ℃)

Test U (V)

Events F (Hz)

Status Instant Ia= 0A


Ib= 0A
I (A) Iunbal Ic= 0A
In= 0A
T ( ℃) Demand Ig= OA

U (V)

F (Hz)

Instant Ia= 0. 00%


Ib= 0. 00%
Iunbal Ic= 0. 00%

Demand

Instant Ia= 0A
Ib= 0A
Iunbal Ic= 0A
In= 0A
Demand

Status Temperature:

I (A) T= +27.7℃

T ( ℃)

U (V)

F (Hz)

ACB
27
Metering Status

AIR CIRCUIT BREAKER


0A
N A B C Instant Uab= 0V
150 Setup I (A) Ubc= 0V
Uunbal Uca= 0V
100 Maint T (°C)
Sequence
50 U (V)
Test
0
Events F (Hz)

Instant Uab= 0.00%


Ubc= 0.00%
Uunbal Uca= 0.00%
Uan= 0.00%
Sequence Ubn= 0.00%
Ucn= 0.00%

Instant

Uunbal △Φ = A - B - C

Sequence

Status Frequency:
I (A)
f=50.00Hz
T (°C)

U (V)

F (Hz)

P (kW) Instant P(KW)


0
E (kWh) Demand Q(kvar)
0
Harmonic Diagram S(kVA)
0

PF= 0

Instant P(KW)
0
Demand Q(kvar)
0
Diagram S(kVA)
0

Instant
Diagram
Demand Q

Diagram P

ACB
28
INSTRUCTIONS

0A
N A B C
150

100

50

Metering P (kW) E.Total E.Total

Setup E (kWh) E.P(kwh)


E.In
0
Maint Harmonic E.Q(kvarh)
E.Out 0
Test E.S(kVAh)
E.Reset 0
Events

E.Total E.In

E.P(kwh)
E.In
0
E.Q(kvarh)
E.Out 0

E.Reset

E.Total E.Out

E.P(kwh)
E.In
0
E.Q(kvarh)
E.Out 0

E.Reset

E.Total

E.In
Yes
E.Out
No
E.Reset

P (kW) Fundament Fundament Fundament

E (kWh) Ia= 0A
Distortion
I (A) Ib= 0A
Harmonic Ic= 0A
FFT In= 0A
U (V)

Waveform

ACB
29
0A

AIR CIRCUIT BREAKER


N A B C
150

100

50

Metering P (kW) Fundament Fundament Fundament

Setup E (kWh) Uab= 0V


Distortion
I (A) Ubc= 0V
Maint Harmonic Uca= 0V
FFT Uan= 0V
Test U (V) Ubn= 0V
Waveform Ucn= 0V
Events

Fundament Distortion THD


Ia= 0. 00%
Ib= 0. 00%
Distortion Ic= 0. 00%
I
In= 0. 00%
thd
FFT Ia= 0. 00%
U
Ib= 0. 00%
Waveform Ic= 0. 00%
In= 0. 00%

Distortion THD
Uab= 0. 00 %
Ubc= 0. 00 %
Uca= 0. 00 %
Uan= 0. 00 %
I Ubn= 0. 00 %
Ucn= 0. 00 %
thd
Uab= 0. 00 %
Ubc= 0. 00 %
U Uca= 0. 00 %
Uan= 0. 00 %
Ubn= 0. 00 %
Ucn= 0. 00 %

Ia (3.31) Ia 0%
Fundament 3
5
7
Ib (3.31) 9
Distortion 11
13
Ic (3.31) 15
17
FFT 19
In (3.31) 21
23
25
Waveform 27
Uab (3.31) 29

Fundament Waveform Ia Ib Ic

Ia Ib Ic
Distortion

In
FFT
Uab Ubc Uca
Waveform
Uan Ubn Ucn

ACB
30
6.2.2 Parameter page
INSTRUCTIONS

0A
N A B C
150

100

50

Metering Knob Ir= 1600A


Tr= 1.0s
Setup Is= ---- A
Protect
Ts= ---- s
Maint Ii= ---- A
Metering Ig= ---- A
Test Tg= ---- s
Contacts
Events

Knob Curve Curve

Switch EIT
Protect
Ineutral
Metering
Iunbal
Contacts
Uunbal

Curve
Memory
Overload
Switch
Temp(°C) ON
Ineutral
ZSI Short
OFF
Iunbal
Ground
Uunbal

Memory Temperature
Alarm
Temp(°C)
ON
ZSI

Ground

Memory
Short
Temp(°C) ON

ZSI Ground
OFF
Ground

Memory
OFF
Temp(°C)
Trip
ZSI

Ground

ACB
31
Metering Knob Curve ON

AIR CIRCUIT BREAKER


0A
N A B C
150 Setup Switch 100%
Protect
100 Maint Ineutral Irn= 500A
Metering
50
Test Iunbal
0 Contacts
Events Uunbal

Curve Alarm

Switch Pick Up:


I iu = 60%
Ineutral Tiu = 50s

Iunbal Drop Out:


I iu = 40%
Uunbal Tiu = 300s

OverVolt Alarm

UnderVolt Pick Up:


Uov= 600V
OverFreq Tov= 2.5s

UnderFreq Drop Out:


Uov= 400V
Idemand Tov= 5.0s

rPower Alarm

Monitor Pick Up:


Prp = 400Kw
Sequence Trp = 5.0s

Drop Out :
Prp = 50Kw
Trp = 10.0s

rPower ON

Monitor TYPE1

Sequence Ic 1= 1. 0Ir

Ic 2= 1. 0Ir

rPower Alarm

Monitor
△Φ=A - B - C
Sequence

ACB
32
Metering Knob SysType SysType
INSTRUCTIONS

0A
N A B C
150 Setup RatedFreq 3Φ 4W
Protect
4CT
100 Maint PowerSign
Metering
50
Test Idwindow
0 Contacts
Events Pdwindow

SysType RatedFreq

RatedFreq
50Hz
PowerSign

Idwindow

Pdwindow

SysType PowerSign

RatedFreq P+

PowerSign

Idwindow

Pdwindow

SysType Idemand
Metering
RatedFreq Window

PowerSign 30 Min

Idwindow

Pdwindow

SysType Pdemand
Metering
RatedFreq Window

PowerSign 30 Min

Idwindow

Pdwindow

Knob CON1:
Overload
Protect CON2:
Null

Metering

Contacts

ACB
33
6.2.3 Maintenance page

AIR CIRCUIT BREAKER


0A
N A B C
150

100

50

Metering Password
Enter New
Setup DataTime Enter Enter New Password
Password: Password: Again:
Maint State
XXXX XXXX XXXX
SysInfo
Test
ParaLock
Events

Password
Data
DataTime 18/01/03

State
Time
SysInfo
10:05:45
ParaLock

Password Contact ContactWear

DataTime
Trips 0. 00%
State

SysInfo Reset
Operation
ParaLock

Contact Total Trips

Trips
999 次
Operation

Contact Operation
Counter
Trips
999 次
Operation

Password Type:
AIC-
DataTime 1000HG

State Data:
180103
SysInfo

ParaLock

Password Parameter
Enter
DataTime Password: Lock

State XXXX Yes

SysInfo Lock
No
ParaLock

ACB
34
6.2.4 Testing page
INSTRUCTIONS

0A
N A B C
150

100

50

Metering Trip Test


Enter
Setup Password:
Yes
Maint XXXX
No
Test

Events

6.2.5 Language, communication page

0A Language
N A B C
150 Comm 简 体

100 繁 体

50 English
0

Language Com.Para Baudrate


9600
Comm Mode
Address
002

Com.Para Mode

Mode Local

ACB
35
6.2.6 Record page

AIR CIRCUIT BREAKER


0A
N A B C
150

100

50

Metering Trip TP 1/10


13 - 09 - 04
11:01:15
Setup Ground
Alarm Ir = 640A
Maint
Tr = 1.0s
I = 4076A
Diagnosis T = 0.9s
Test Ia = 0A
Ib = 0A
Change Ic = 0A
Events I n = 4076A

Trip 13- 09- 04


11:01:15
Iunbal
Alarm Iur = 60.0%
Tur = 19.00s
Iu = 200%
Diagnosis Tu = 19.00s
Ia = 0A
Ib = 0A
Change Ic = 8607A

Trip 1/10
13- 09- 04
11:01:15
Alarm
ContactWear

Diagnosis 60%

Change

Trip 1/10
13- 09- 04
11:01:15
Alarm
Manual.Close

Diagnosis

Change

ACB
36
6.3 Factory setting
INSTRUCTIONS

Item Adjust range Factory setting

Curve EIT / DT / SIT / VIT / HVF EIT

Current setting Ir 0.4~1In 1In


Overload protection
Standard:0.5~24s Standard:24s
Time setting Tr
HVF:0.5~4s HVF:4s
Current setting Isd 1.5~10Ir 4Ir
Short circuit protection 2
Inverse time I T on:0.1~0.4s
Time setting Tsd Inverse time 0.4s
Definite time I2T off:0~0.4s
Instantaneous protection Current setting Ii 2~15In 15In

Current setting Ig 0.2~1In 1In


Ground fault protection 2
Inverse time I T on:0.1~0.4s
Time setting Tg Inverse time 0.4s
Definite time I2T off:0~0.4s
Current setting If 1~30A 30A
Leakage protection Trip: Tf=0.1~0.8s
Time setting Tf Trip 0.8s
Alarm:Tf=0.1~1s, Definite time
Ground fault Trip / Alarm Trip

Overload: On / Off
Thermal memory On
Short circuit: On / Off
Function
Short circuit: On / Off
ZSI Off
Ground fault: On / Off

Temperature alarm On / Off On


3P:Off
Protection On / Off
Neutral protection 4P:On
Setting 50% / 100% 100%

Protection Off / Trip / Alarm Off

Pickup threshold 20%~80%, and ≥ Dropout threshold 80%


Current unbalance
Pickup time delay 1~40s, Definite time 40s
IU
Dropout threshold 20%~80%, and ≤ Pickup threshold 20%

Dropout time delay 10~360s, Definite time 10s

Protection Off / Trip / Alarm Off

Pickup threshold 0.4~1In, and ≥ Dropout threshold 1In


Demand current
protection Pickup time delay 15~1500s, Definite time 1500s
ID
Dropout threshold 0.4~1.0In, and ≤ Pickup threshold 0.4In

Dropout time delay 15~3000s, Definite time 15s

Protection Off / Trip / Alarm Off

Pickup threshold 5%~50%, and ≥ Dropout threshold 50%


Voltage unbalanced
Pickup time delay 1~40s, Definite time 40s
UU
Dropout threshold 5%~50%, and ≤ Pickup threshold 10%

Dropout time delay 10~360s, Definite time 10s

Protection Off / Trip / Alarm Off

Pickup threshold 77~828V, and ≤ Dropout threshold 77V


Under-voltage
Pickup time delay 1~30s, Definite time 30s
UV
Dropout threshold 77~828V, and ≥ Pickup threshold 100V
ACB Dropout time delay 1~100s, Definite time 10s
37
Item Adjust range Factory setting

AIR CIRCUIT BREAKER


Protection Off / Trip / Alarm Off

Pickup threshold 77~828V, and ≥ Dropout threshold 725V


Over-voltage
Pickup time delay 1~5s, Definite time 5s
OV
Dropout threshold 77~828V, and ≤ Pickup threshold 704V

Dropout time delay 1~36s, Definite time 10s

Phase sequence Protection Off / Trip / Alarm Off


△Φ Setting Sequence (ABC) / Reverse (ACB) ABC

Protection Off / Trip / Alarm Off

Pickup threshold 45~65Hz, and ≥ Dropout threshold 65Hz


Over frequency
Pickup time delay 0.2~5s, Definite time 5s
OF
Dropout threshold 45~65Hz, and ≤ Pickup threshold 60Hz

Dropout time delay 1~360s, Definite time 1s

Protection Off / Trip / Alarm Off

Pickup threshold 45~65Hz, and ≤ Dropout threshold 45Hz


Under frequency
Pickup time delay 0.2~5s, Definite time 5s
UF
Dropout threshold 45~65Hz, and ≥ Pickup threshold 50Hz

Dropout time delay 1~360s, Definite time 1s

Protection Off / Trip / Alarm Off

Pickup threshold 20~500KW, and ≥ Dropout threshold 500kw


Reverse power
Pickup time delay 0.2~20s, Definite time 20s
RP
Dropout threshold 20~500KW, and ≤ Pickup threshold 100kw

Dropout time delay 1~360s, Definite time 1s

Protection On / Off Off

Method Method 1 / Method 2 Method 1


Load monitor
Ic1=0.5~1Ir, Ic1≥Ic2 1.0Ir
Current setting
Ic2=0.5~1Ir, Ic1≥Ic2 0.5Ir
3P:3Φ4W3CT
System type 3Φ3W3CT / 3Φ4W3CT / 3Φ4W4CT
4P:3Φ4W4CT
Frequency 50Hz/60Hz Fn

Power direction P+ or P- P+

Current requirement measure time window 5~60min 15min

Power requirement measure time window 5~60min 15min

Contact 1 Instantaneous
Contact 26 status 
Contact 2 Short circuit

Password 0000~9999 1234

Parameter lock Unlock / Lock Unlock


Simplified Chinese / Traditional Chinese /
Language English
English
Communication Baud rate 4800 / 9600 / 19200 / 38400bps adaptive  9600bps

Communication address 001~247 001

Communication mode Local / Remote Local

Note: 1. Factory setting parameter is different for different type of controller.


2. Factory setting can be customizing for different needed.
ACB
38
7. Secondary Wiring Diagram
INSTRUCTIONS

7.1 Controller and Circuit Breaker Wiring

1 2
L1
N
PE

RS485 Voltage External


Communication Ports ZSI Ports Input Transformer
Zo1 Zi1
A B Zo2 Zi2 UN U1U2 U3 S1 S2

2 4 6 8 10 12 14 16 18 22 24 26

DW

1 3 5 7 9 11 13 15 17 19 21 23 25

Major
Loop AIC Intelligent Controller

■1#,2#:
Working power supply input with DC24V, 1 # is positive and 2 # is negative.
■3#,4#,5#:
Fault tripping contact, passive output. When no fault tripping occurred, 3# and 4# is closing output, 4# and5# is open
output. Contact capacity is AC1/AC380V/2A, DC1/DC250V/0.3A.
■6#,7#:
Status auxiliary contact, passive output. Breaker at closing mode is closing output, open mode is open output.
Contact capacity is AC1/AC380V/2A, DC1/DC250V/0.3A.
■8#,9#:
Status auxiliary contact, passive output. Breaker at closing mode is closing output, open mode is open output.
Contact capacity is AC1/AC380V/2A, DC1/DC250V/0.3A.
■ 10 # , 11 # (for AIC-HC type) :
RS485communication outlet, 10 # is terminal A, 11 # is terminal B.
■ 12 # , 13 # (for AIC-H type):
First set of programmable contacts, passive output, normal open. Contact capacity is AC1/AC250V/2A, DC1/
DC30V/2A.
■ 14 # , 15 # (for AIC-H type):
Second set of programmable contacts, passive output, normal open. Contact capacity is AC1/AC250V/2A, DC1
DC30V/2A.
■ 16 # , 17 # (for AIC-H type):
ZSI output, Zo1, Zo2.
■ 18 # , 19 # (for AIC-H type):
ZSI input, Zi1, Zi2.
■ 21#, 22#, 23#, 24# (for AIC-H type):
3 phase voltage input, UN、U1、U2、U3.
Note: a. Phase sequence cannot be wrong.
b. 3 phase 4 wires system, UN must be connect.
c. 3 phase 3 wire system, UN and U2(B) must be shorted.
■ 25 # , 26 # ( for leakage protection or 3P+N):
input terminal for external transformer, N phase external CT or leakage ZCT
Note: a. for leakage protection, only use for ZCT input terminal.
ACB
b. for 3P+N, only use for external sensor for neutral input terminal.
39
7.2 Secondary Wiring Diagram

AIR CIRCUIT BREAKER


7.2.1 AIC-E/A Type Controller
1 2
L1
N
PE
Main Circuit
Power Supply

External
Transformer
S1 S2
SB3 SB2 SB1 Connect Testing Open

2 4 6 8 10 12 14 16 18 22 24 26 28 30 32 34 36 38 40 42 44 46 50 52 54

UVT SHT CC

DW
M

1 3 5 7 9 11 13 15 17 19 21 23 25
27 29 31 33 35 37 39 41 43 45 47 49 51 53
energy
storage

Power
Storage
Instructions

Major Position
Loop AIC Intelligent Controller UVT SHT CC Auxiliary contacts
Indications
Electric
Motor Operation
Device

7.2.2 AIC-H Type Controller


1 2
L1
N
PE
Main Circuit
Power Supply
RS485 Voltage External
Communication Ports ZSI Ports Input Transformer
Zo1 Zi1
A B Zo2 Zi2 UN U1U2U3S1S2
SB3 SB2 SB1

2 4 6 8 10 12 14 16 18 22 24 26 28 30 32 34 36 38 40 42 44 46 50 52 54

UVT SHT CC

DW
M

1 3 5 7 9 11 13 15 17 19 21 23 25
27 29 31 33 35 37 39 41 43 45 47 49 51 53

energy
storage

Power
Storage
Instructions

Major Position
Loop AIC Intelligent Controller UVT SHT CC Auxiliary contacts
Indications
Electric
Motor Operation
Device

Note: (1) If CC, SHT and M are using different control voltage, they should connect to different power source.
(2) Terminal 35 and directly connect to power (automatic charging), or connect to a normally open button then connect to power
(manual charging)

ACB
40
7.2.3 Remote Control Secondary Wiring
INSTRUCTIONS

1 2
L1
N
PE
Main Circuit
Power Supply
RS485 Voltage External
Communication Ports ZSI Ports Input Transformer
Zo1 Zi1
A B Zo2 Zi2 UNU1U2U3 S1S2
SB3 SB2 SB1 Connect Testing Open

2 4 6 8 10 12 14 16 18 22 24 26 28 30 32 34 36 38 40 42 44 46 50 52 54

UVT SHT CC

DW
M

1 3 5 7 9 11 13 15 17 19 21 23 25
27 29 31 33 35 37 39 41 43 45 47 49 51 53

energy
storage

Power
Storage
Instructions

Major Position
Loop AIC Intelligent Controller UVT SHT CC Auxiliary contacts
Indications
Electric
Motor Operation
Device

Note: Set the first set of programmable contact (12 # , 13 # )"remote open" and pair with a SHT; set the second programmable contact
(14 # , 15 # ) to "remote close" and pair with a CC; then use the controller to send out signal for remote control.

ACB
41
8. Accessories and functions

AIR CIRCUIT BREAKER


8.1 Mechanical interlock 2000 (max)

■ Use for 2 set of ACB for horizontal


connection, shown on the right.
■ Maximum distance is 2000mm.
■ The interlock can be install following
the manual from manufacture.
R≥120

Vertical installation combination

■ 2 breakers
Backup Normal BW1600 1
ACB 1 ACB 2
0 0 BW1600 2
0 1
55 1 0
40 52
180
50

■ 3 breakers
Backup Normal Normal BW1600 1
600

ACB 1 ACB 2 ACB 3


0 0 0 BW1600 2
1 0 0
0 1 0 BW1600 3
40 55
180 0 0 1
50

52

■ 3 breakers
600

Backup Normal Normal BW1600 1


ACB 1 ACB 2 ACB 3
basic point
0 0 0
BW1600 2
65
1 0 0
BW1600 3
166 100 0 1 0
45

circuit breaker
cradle
0 0 1

"Open" position lock (shown on the right)


"Open" position lock can lock the breaker at open position and
prevent it from closing.

Can be choosing form:


(1) 1 breaker with 1 set of lock and key
(2) 2 breakers with 2 locks and 1 key
(3) 3 breakers with 3 locks and 2 keys

ACB
42
8.2 Door Frame
INSTRUCTIONS

■ Install on the door for sealing purpose


with protection level of IP40.
■ Draw out type and fixed type to choose
from, both are 11mm thick

Fixed
Draw out

8.3 Door Interlock

■ Use to interlock the breaker and the door, to prevent the door be open at"connected"position.
■ Right and left installation to choose from.

8.4 Under voltage release

■ Break the breaker when the voltage is below 35%~70% of rated operation voltage.
■ Tripping time: Instantaneous, time delay 1, 3, 5s±10%
■ The coil cannot close the breaker without excitation, only reset when the voltage is back to 80%
of rated operation voltage.
■ Suction acid type and self-priming type to choose form.

ACB
43
8.5 Power Module

AIR CIRCUIT BREAKER


Transform external power source to DC24V via power module to supply to intelligent controller.
Connect to secondary wiring terminal 1# and 2#. 1# is positive and 2# is negative.
Installation method 1: The standard guide way with 35mm in width inside the switchgear cabinet
Installation method 2: M4 screws installation

Input voltage (V) Output voltage (V) Output current(A)

AC/DC 100~240

AC 380~415 DC 24±5% 0.3

DC 24~60

2 1 PE + -
Input Output

Rated Input Voltage:


DC100V~240V
AC100V~240V 50/60Hz

35.5
135

Output Voltage:
DC24V/300mA

Power Supply

71.0 49.3
3
4.
Ø

8.6 External sensor for neutral conductor (for 3P+N)

It is used together with circuit breaker with three poles in the power distribution system of TN-S and
Installed on the neutral conductor with 2m at maximum far from the installation point. Connect to
secondary wiring terminal 25# and 26#.

S1-K S1-1

11
95.5
51

20

81

P1-K

40.5

124.5

ACB
44
8.7 Zero-phase sequence current sensor (ZCT)
INSTRUCTIONS

Rectangular sensor enables the detection of zero-phase sequence current which is required for the
earth-leakage protection. It is installed around the bus-bars (phases + neutral). Ratio: 30A:300mA.
D

S1

H
e

S2
a

M N
A E

Shape Bore Install


Type
A H D E a e M N

BH-LMB-280 ℅ 120 380 250 54 114 285 120 250 72

8.8 External units of transformer's center

Use for Ground fault (Source ground return) protection.


■ External sensor of transformer's center (ratio 1In:1A)
It is used together with three-phase circuit breakers or four-phase circuit breakers in TN-S distribution system.
The sensor is installed around the connection of the transformer neutral point to earth and connected to intelligent
circuits via a module to provide the source ground return protection.
H
e

M D
W N

Size Shape Bore Install

Standard W H D a e M N

ACB 60II 102 125 45 61 33 42 57.5


45
■ External module of transformer's center

AIR CIRCUIT BREAKER


S1 and S2 connect with the external sensor of transformer's center and S3 and S4 connect with terminals 25# and
26# of the secondary circuit. The module is installed by getting stuck to the standard guide way with 35mm in width
inside the switchgear cabinet.

S1 S2 S3 S4
Input Output

External module of

35.5
135

transformer’s center

71 49.3
3
4.
Ø

ACB
46
9. Safety Distance
INSTRUCTIONS

A
B B
B B

Draw-out Type Fixed Type

To insulator To metal

A B A B

Draw out 0 0 0 0

Fixed 0 30 0 70

10. Temperature Compensate

Ambient temperature +40℃ +45℃ +50℃ +55℃ +60℃

Continued
Inm:1600A 1In 0.96In 0.92In 0.87In 0.8In
capacity

11. Busbar Dimension

Model BW1600-SN

in 200A 400A 630A 800A 1000A 1250A 1600A

Thickness mm 5 5 5 5 5 5 10

Width mm 20 50 40 50 40 40 50

Number for each pole 1 1 2 2 3 4 2

Note: the data above is according to standard IEC60947-1.

ACB
47
12. Secondary Wiring Diagram

AIR CIRCUIT BREAKER


12.1 Draw out type (Unit : mm)

Draw-out BW1600-SN 3P/4P

2-Ø8.5 2-8.5X10.5

95

Draw-out type
73

In a (mm)
72.5(3P) 630-1000A 10
142.5(4P) 72.5 1250, 1600A 18
Switchboard
Door Position

a
345
318

320

107
a
68
109 109 300

137.5(3P)
341(Disconnection)
207.5(4P) 137.5

258

220
10-Ø5

12-Ø11(3P)
70(4P) 70 70 16-Ø11(4P)
Normal
Type
15

32.5
120.5

321

357

25
50

70(4P) 70 70
161

ACB
Elongated
20 15

Bottom
52.5

Type
25 12-Ø11(3P)

Door Frame Dimensions


50 16-Ø11(4P)

ACB
48
12.2 Fixed type (Unit : mm)
INSTRUCTIONS

Fixed type BW1600-SN 3P/4P

4-9X14

100
Fixed type

52
121(3P) In a (mm)
191(4P) 121 630-1000A 10
Switchboard
Door Position 1250, 1600A 18
312

a
107
a
30
109 109

132.5(3P) 201

202.5(4P) 132.5

257

8-Ø5 220

12-Ø11(3P)
70(4P) 70 70 16-Ø11(4P)
Normal
Type
15

32.5

25
50
143

ACB 70(4P) 70 70

Bottom Elongated
20 15

52.5

Type
25

Door Frame Dimensions


12-Ø11(3P)
50 16-Ø11(4P)

ACB
49
13. Mounting, Usage, and Maintenance

AIR CIRCUIT BREAKER


13.1 Mounting

■ Before mounting, check the specifications of the circuit breaker to make sure if they meet
the requirements.
■ Before mounting, check the insulator resistance with a 500V megger. The resistance should
not be less than 10MÙwhen the surrounding medium temperature is 20℃ +5℃ with a
relative humidity between 50% and 70%. If not, please dry it until the insulator resistance
satisfies the requirements.
■ The base of the breaker should be installed horizontally and ¬fixed by M10 screws.
■ Circuit breakers should have reliable ground fault, and the ground fault points should be
clearly marked. Fixed-type circuit breakers should strictly follow safe distance regulations.
■ After mounting a circuit breaker according to the wiring diagram, the circuit breaker should
be tested for the following matters before the main circuit is powered (for a drawer-type of
circuit breaker, follow the instructions on the cradle for testing).
A. Check if the under-voltage, shunt release and closing electromagnet have well matched electric motor
operation voltage (the breaker cannot be operated unless the under-voltage release is closed).

B. Energy-storage will be indicated after tripping the handle on the cover seven times. When hearing a click
sound, energy storing is completed. Press the closing button or turn o-the electromagnetic switch to securely
close the circuit breaker. Flip the handle again to start energy storage.

C. Turn on the power of electric motor energy storage device and"energy storage"will be displayed.
There will be a click sound when energy storage is completed. The motor will be turned o-automatically.
Press the"closing"button or closing the electromagnetic switch for closing the circuit breaker reliably.

D. When the breaker is closed in a tripping test (See 8.2.3d), the circuit breaker should be tripped by the tripping
button of under-voltage or the release shunt or the tripping button on the cover.

ACB
50
13.2 Commonly Problem and Trouble-shooting
INSTRUCTIONS

No Problem Possible causes Troubleshooting

● Under voltage release is active. ● Check the wiring, and turn on the
● Intelligent controller has not been reset. power of under voltage release.
● Operation mechanical has no energy ● Press the reset button.
1 Circuit breaker can not be closed storage. ● Manual charging.
● Draw out type is not in"connect" ● Use the handle and operate the breaker
or "testing"position. to"connect"or"testing"position.
● "Open" lock is in lock. ● Use the key to unlock.

● Power of the electric operation machine ● Check the wiring, and turn on the power.
Circuit breaker cannot use
2 is not on. ● Check if the operating voltage is greater
automatic charging
● Insufficient power capacity. than 85%Us.

● Check the wiring, and turn on the power.


Closing release does not close ● No power / no voltage.
3 ● Check if the operating voltage is greater
the breaker ● Insufficient power capacity.
than 85%Us.

● Check the wiring, and turn on the power.


Shunt release does not open ● No power/ no voltage.
4 ● Check if the operating voltage is greater
the breaker ● Insufficient power capacity.
than 85%Us.

● Check the voltage should be within


● Under voltage frequently.
85%~110%Ue.
5 Breaker frequently tripping ● On-site overloading causing the
● Adjust Ir value or change the rated
overload protection.
current In.

● The track of the cradle or the


Draw out type breaker's handle ● The track or the circuit breaker has to be
6 circuit breaker itself is not pushed
cannot be inserted pushed all the way to the end.
incompletely.

The breaker cannot be ● The handle was not pulled out


● Pull out the handle.
pulled out from the body of completely.
7 ● Make the circuit breaker to the
draw out type circuit breaker ● The circuit breaker is not completely
"disconnected"position completely.
at"disconnected"position disconnected.

ACB
51
MEMO
MOTOR CONTROL (CONTACTOR/ MS/ MMS), CIRCUIT BREAKER (MCCB/ ELCB/ EMCCB/ MCB), AIR CIRCUIT BREAKER, AUTOMATIC
TRANSFER SWITCHES (Panel Board Type/ Residential Unit Use), SURGE PROTECTIVE DEVICE, LOW VOLTAGE POWER CAPACITORS,
SMART METER, INVERTER

Breaker & switchgears overseas sales dept.


3F, No.9, Sec. 1, Chang-an E. Rd., Zhongshan Dist., Taipei City 10441, Taiwan
T. +886-2-2541-9822 F. +886-2-2581-2665
e-mail. [email protected]