Distributor: Breaker & Switchgears Overseas Sales Dept
Distributor: Breaker & Switchgears Overseas Sales Dept
tw
http://circuit-breaker.seec.com.tw
Contents
1.1 Purposes
BW-1600 series air circuit breakers(referred to as circuit breaker) are used in rated voltage AC720V and below, 50/60Hz
distribution system, with rated current from 400A to 1600A. It's used for distributing power and protecting circuits in
the electrical distribution system is protected from overloading, short circuit, ground fault, and other hazardous faults.
The protective actions have a high precision for preventing unnecessary power failure, closing power supply much more
reliable.
BW-1600
Pole:3: 3P, 4: 4P
Model:SN
Frame size(AF)
BW series
1.3 Feature
■ Compact structure, smaller size
■ High breaking capacity
■ No arcing distance, high security
■ Intelligent protection and network communication
■ Energy measurement, harmonic analysis
■ Wiring direction does not affect product.
1.4 Classification
■ Installation type: Draw-out, fixed type
■ Operation mode: Electric and manual operation
■ Connection: Horizontal
■ Pole: 3P, 4P
■ Accessory: Intelligent tripping unit, Under-voltage release, Shunt release
5
6
3
7
8
9
10
11
12
4 13
18
14
15
17 16
ACB
2
3. Specification
INSTRUCTIONS
3.1 Specification
Pole 3P、4P
Model SN
AC400V / 415V 65 / 65
Icu / Ics (kA)
AC690V / 720V 50 / 50
Breaking
Capacity
Icw (kA) 1sec 50
ACB
3
3.2 Accessory Specification
Rated voltage
Shunt release
Motor gear
Delay: 1s / 3s / 5s
Operating time
Instantaneous
Type 4NO4NC
Auxiliary
Thermal rated current of auxiliary contact 6A
contacts
ACB
4
4. Intelligent Controller
INSTRUCTIONS
4.1 Specification
AIC-E G
N/A
AIC-A G
O Overcurrent (LSI)
● LCD display
AIC-H G C
● ZSI protection
O Overcurrent (LSI) ● Voltage protection
● Frequency protection
G Ground fault (vector sum) ● Power and energy
N/A
Harmonic type C ● Harmonic analysis
W Ground fault ● Load monitor
communication
(Source Ground Return) ● Four-set signal output
Note: 1.Earth grounding (Source Ground Return) function must pair with external sensor of transformer's center and external module
of transformer's center.
ACB 2. Earth leakage function must pair with a ZCT.
5
4.2 Function Table
Instantaneous protection ■ ■ ■
Overload pre-alarm ■ ■ ■
MCR Protection ■ ■ ■
Load monitor ■
Current-unbalance ■ ■
Voltage-unbalance ■
Phase sequence ■
Reverse Power ■
Demand current ■
Current ■ ■
Current unbalance ■ ■
Voltage ■
Voltage unbalance ■
Frequency ■
Power ■
Energy ■
Demand Current ■
Demand Power ■
Harmonic ■
Over-temperature ■ ■ ■
Refuse action ■ ■ ■
Trip record ■ ■
Alarm record ■ ■
Operation counter ■ ■
Others Self-testing ■ ■
Communication □
■ Standard □ Option
Note 1:Notification by LED indicator only for AIC-E/AIC-A controller. Signal output support for AIC-H controller.
ACB
6
4.3 Protection Characteristics
INSTRUCTIONS
Adjust range:
Iu:0.4-0.45-0.5-0.55-0.6-0.65
Current setting Ir=(0.4~1) In -0.7-0.75-0.8-0.85-0.9-0.95In
Ir:0-0.005-0.01-0.015-0.02-0.025
Overload -0.03-0.035-0.04-0.045-0.05In +Iu
long-time delay
protection
Operation characteristics Trip at 1.05~1.2Ir
Accuracy ±20%
Adjust range:
Iu:0.4-0.45-0.5-0.55-0.6-0.65
Current setting Ir = (0.4~1) In -0.7-0.75-0.8-0.85-0.9-0.95In
Ir:0-0.005-0.01-0.015-0.02-0.025
-0.03-0.035-0.04-0.045-0.05In +Iu
Overload
long-time delay
Operation characteristics Trip at 1.05~1.2Ir
protection
Accuracy ±20%
ACB
7
Overload long time delay protection characteristics (s):
2×Ir 5.83 11.67 23.33 46.67 93.3 140 186.7 233.3 280
7.2×Ir 0.5 0.69 1.38 2.75 5.51 8.26 11.01 13.77 16.52
10×Ir 0.5 0.50 0.71 1.41 2.83 4.24 5.66 7.07 8.48
DT 0.5 1 2 4 8 12 16 20 24
1.5×Ir 0.5 1 2 4 8 12 16 20 24
2×Ir 0.5 1 2 4 8 12 16 20 24
7.2×Ir 0.5 1 2 4 8 12 16 20 24
10×Ir 0.5 1 2 4 8 12 16 20 24
SIT 0.5 1 2 4 8 12 16 20 24
1.5×Ir 3.23 6.45 12.90 25.81 51.61 77.42 103.23 129.04 154.84
2×Ir 1.75 3.50 7.00 14.00 28.00 41.99 55.99 69.99 83.99
7.2×Ir 0.5 0.86 1.72 3.45 6.89 10.34 13.78 17.23 20.67
10×Ir 0.5 0.67 1.34 2.68 5.36 8.05 10.73 13.41 16.09
VIT 0.5 1 2 4 8 12 16 20 24
7.2×Ir 0.5 0.81 1.61 3.23 6.45 9.68 12.90 16.13 19.35
10×Ir 0.5 0.56 1.11 2.22 4.44 6.67 8.89 11.11 13.33
HVF 0.5 1 2 4 8 12 16 20 24
1.5×Ir 159 319 638 1275 2550 3825 5100 6375 7650
2×Ir 43.17 86.33 172.7 345.3 690.7 1036 1381 1727 2072
7.2×Ir 0.50 0.50 0.96 1.93 3.86 5.78 7.71 9.64 11.57
10×Ir 0.50 0.50 0.50 0.52 1.04 1.55 2.07 2.59 3.11
ACB
8
■ Short-circuit Short time delay protection characteristics
INSTRUCTIONS
Adjust range:
Current setting Isd = (1.5~10) Ir
1.5-2-2.5-3-4-5-6-8-10+OFF
Accuracy ±10%
Note: 1.when the fault current is greater than maximum setting (10Ir), controller will protect according to current definite time setting.
Adjust range:
Current setting Ii = (2~15) In
2-4-6-8-10-11-12-15+OFF
Short-circuit
instantaneous
Accuracy ±15%
ACB
9
■ Ground fault protection characteristics
Accuracy ±10%
Adjust range:
Ground fault
protection I2T on (Inverse time): Tg = (0.1~0.4) s
Time delay I2T on (Inverse time): 0.1-0.2-0.3-0.4
I2T off (Definite time): Tg = (0~0.4) s
There are two kinds of protection modes: Vector sum, Source Ground Return
Vector sum: Measures current between phase line and neutral in a TN-S system. When ground fault occurred,
part of the current will flow back to transformer via PE line, causing the current vector sum
(Ig= Ia+Ib+Ic+IN) no longer equal to 0, thus detecting ground fault. Adding an external current
transformer to 4 poles or the N phase of 3 pole (3P+N) breaker, and pair with an internal sensor to
send signal to controller, opening the breaker when ground fault occurred.
CT CT CT
A A A
B B B
C C C
PEN N
PE Intelligent
Intelligent Intelligent
Controller
Controller Controller
N
PE
3P 4P 3P+N
Grounding current: Measure current between phase line and neutral in a TN-S system, measure in the Neutral
- earth link of the LV transformer (shown below), when there is a grounding fault, PE line will generate current,
causing fault determined.
A
B
C
N
External sensor of Intelligent
transformer's center
Controller
PE
External module of
transformer's center
Grounding Current
ACB
10
Ground fault protection characteristics (s):
INSTRUCTIONS
Tg G (Inverse time)
M=I/In 0.1 0.2 0.3 0.4
Adjust range:
Current setting value If = 1~30A
1-2-3-5-7-10-20-30A+OFF
Accuracy -20%~0%
Adjust range:
Earth leakage
protection Trip: Tf = 0.1~0.8s
Delay setting value 0.1-0.2-0.4-0.8s
Alarm: Tf = 0.1~1s
0.1-0.2-0.4-0.8-1s
Another is transformer mode of external Earth Leakage. The controller gets the output current signal from a
current transformer directly to protect. Generally, the secondary output of the transformer is 30A / 300mA.
ZCT ZCT
A A
B B
C C
N
PE
Intelligent Intelligent
Controller Controller
3PT 4PT
ACB
11
■ Ground fault alarm/ Earth leakage alarm/ Overload pre-alarm
Tg
Ground fault alarm 1.0Ig 0.9Ig Tg
Inverse / Definite time
When the current exceeds the pickup threshold, alarm indicators will blink and send the output signal (if
function were set); when the current falls below the dropout threshold, alarm function reset.
Note: Notification by LED indicator only for AIC-E / AIC-A controller. Signal output support for AIC-H controller.
■ MCR Protection
MCR is a protection for instantaneous short-circuit current when circuit breaker is connected. The breaker will
instantaneous trip when a short circuit current (≥12In) occurred during closing operation (≤100ms), operation
time is ≤60ms.
Note: Within 100ms of closing operation and with external power supply condition.
The overload and short circuit short time delay protection for neutral line will activate with the setting of 50% Ir
50%Ir Half protection
The instantaneous and ground fault protection for neutral line will activate with the setting of Ir.
The overload and short circuit short time delay protection for neutral line will activate with the setting of Ir
100%Ir Full protection
The instantaneous and ground fault protection for neutral line will activate with the setting of Ir.
ACB
12
■ Current Unbalance Protection
INSTRUCTIONS
Current unbalance protection is to protect when loss of phase or unbalance of phase current, the protection is
based on unbalance percentage.
When the 3 phase current unbalance is greater than Pickup threshold and time, the breaker will trip or send out
alarm signal. When the protection type is set to alarm, alarm signal will disarm when the unbalance value is less
then Pickup threshold and time.
Current unbalance calculation:
I∆max
Iavg
ll∆maxl
lunbal = X 100%
lavg
la+lb+lc
lavg = 0
3 Ia Ib Ic
In the equation, Iavg:Ia,Ib,Ic 3 phase average current (RMS). I∆max:maximum difference of each phase and
Iavg.
ACB
13
4.3.2 AIC-H other function
Reverse power protection is active when sum of 3 phase's active power direction is different form the user
setting, and the value is greater than the setting value and time.
■ Load monitor
Operation 0.5Tr protection and the characteristics are the same as overload long time delay protection.
Method 1
characteristics Ic2 = (0.5~1.0) Ir, ≤Ic1 Adjust step length: 0.1
Current setting 0.25Tr protection and the characteristics are the same as those of overloading and long-delay.
Time delay 0.5Tr protection and the characteristics are the same as overload long time delay.
Method 2
Current Ic2 = (0.5~1.0) Ir, ≤Ic1 Adjust step length:0.1
Operation 60s
The controller can program the output of two passive signal contacts for load monitor. The output signal
contacts can be used for monitoring alerts, controlling the load of tripping sub-circuit and ensuring a normal
power supply for the main system. There are two types of load monitor methods available (the user can choose
one of them).
1. Method 1: It can be used to control two sub-circuit loads. When the working current exceeds 1.2Ic1 or 1.2Ic2,
controller will delay the output of signal contacts according to inverse time characteristics. The
characteristic curve of inverse time and the characteristic curve of overload long-time delay are
the same, but the setting current value can be set independently.
2. Method 2: It is generally used to control sub-circuit loads. When the working current exceeds 1.2Ic1, the controller
will output signal contact point break sub-circuit load according to inverse time characteristics.
The characteristic curve of inverse time and the characteristic curve of overload long-time delay
are the same, but the setting value has to be Ic1Ic2. If after tripping the sub-circuit load, the current
will return to normal. When the current is lower than Ic2 for 60s continuously, the controller will
output another signal contact to pick up the broken load and restore the power supply of system.
ACB
15
■ ZSI (Zone selective Interlocking)
2# Zo1
Zo2
Zi1
Zi2
Downstream
Zo1 Breaker Zo1
Zo2 Zo2
Zi1 Zi1
Zi2 Zi2
Zone-selective interlocking (ZSI) has multiple classified protection system which is designed to minimize
the faulty impact on whole electrical distribution system by reducing the time it takes to clear the fault and
maintaining system coordination. This function is suit with short circuit and ground fault protection (I2t is set to
off )
Example:
1. Occurrence of Fault A: The upstream breaker (1#) received no signal from downstream breaker and performs
instantaneous trip operation to protect system.
2. Occurrence of Fault B: Breaker (2#) will send ZSI signal to upstream breaker (1#) and breaker (1#) will obey their
delay setting to maintain coordination in other areas of the system. Breaker (2#) received no ZSI signal from
downstream breaker and performs instantaneous trip operation.
Note: 1. The terminals breaker's Zi1 and Zi2 should be shorted, if its open, ZSI will trip when short-circuit and ground fault occurred.
2. Upper breaker's Isd or Ig cannot set to 0s, or ZSI may not be working properly.
ACB
16
4.3.3 Display Measurement Parameter
INSTRUCTIONS
AIC-A
Current unbalance 0%~200% ±5% (absolute)
AIC-H
Active power P
THD、thd-current I
Harmonic 0~1000% ±5%
THD、thd- voltage U
FFT- current I
0~1000% ±5%
FFT-voltage U
■ Voltage measuring
3 phase 4 wire, voltage N phase must be connected (secondary circuit terminal 21#).
3 phase 3 wire, voltage N phase (21#) and B phase (23#) must shorted.
■ Demand measurements
Required value:Average of current, power with in a time window for each phase.
Set the time window in measurement parameter (5~60min). If the setting had been change, the value will
automatic be recalculated.
■ Power Sign
P+:Forward measurement, corresponds to the usual flow, meaning from top to bottom
P -:Reverse measurement.
■ Power Diagram
P = - P =+
Q =+ Q =+
pf = - pf = +
P
P = - P =+
Q = - Q = -
pf = - pf = +
■ Energy measurement
Total energy: all of the energy.
Input energy: energy consumption, positive increase.
Output energy: energy release, reverse increase.
Energy measurement vales can be reset.
■ Harmonic measurement
Fundamental wave: measure fundamental wave current, line voltage, phase voltage.
Distortion rate: Total harmonics distortion (THD) rate to fundamental wave.
Total harmonics distortion (THD) rate to valid values.
FFT amplitude: display 3~31times of FFT amplitude of each odd harmonic, use rectangular display to show
different frequency harmonic amplitude, achieving harmonic spectrum analysis.
Waveform: Capture current, voltage waveforms in one cycle with real-time updates.
ACB
18
4.3.4 Other functions
INSTRUCTIONS
■ Self-diagnosed functions
When the working environment of the controller exceeds 70℃ or when 60% of the contact has been worn off
or when the circuit breaker cannot be tripped, the user would be notified by controller and relevant parameters
will meanwhile be recorded.
■ Operation counter
The total number of operating cycles will be registered and the data cannot be manually cleared.
■ Test function
The controller will simulation an instantaneous trip test, causing the breaker to trip. It is use for breaker's on-site
debugging, regular maintenance and trouble shooting. The red reset button must be press before closing the
breaker every time, cannot be press during normal operation.
■ System clock
The system clock function is for recording the time and date during faults.
ACB
19
■ Programmable contact function
3 Overload Overload long time delay trip Closing after fault is cleared
13 Under voltage Under voltage tripping alarm 1. Closing after fault is cleared
14 Over frequency Over frequency tripping alarm 2. Function disable
22 Refused action Tripping failed, breaker refused to move Open the breaker
24 Contact wear Contact serious wearing alarm Reset contact wearing rate
Note: 1. Contact is normal open, input is normal close (except load monitor lc2 method 2)
2. Non-closure contact: contact will remain operation before eliminating fault alarm.
ACB
20
■ Communication (AIC-HC optional)
INSTRUCTIONS
Achieve remote control, communication, metering and setting with RS-485 / Modbus-RTU support.
"Local" mode: controller will not respond to remote control, such as parameter modification or remote closing
/ opening.
"Remote" mode: Controller will respond to remote control, manual modification will not affect.
Cable: RS485Shielded twisted pair
Baud rate: 4800 / 9600 / 19200 / 38400bps adaptive.
■ Parameter lock
"Unlock" mode: parameter can be modify.
"Lock" mode: parameter cannot be modify.
ACB
21
5. Characteristic Curves
10000
5000
Ir=0.4~1xIn
2000
1000
500
200
100
50
Tr=0.5~24s
20
10
t(s)
2
Isd=1.5~10xIr
1
I2t ON
0.5 0.4s 0.4s
0.3s 0.3s
0.2 0.2s
0.2s
0.1s
0.1 0.1s
0s I2t OFF 0s
0.05
Ii=2~15xIn
0.02
0.01
1 2 3 4 5 6 8 10 20 3 4 5 6 8 10 15 20 30
xIr xIn
ACB
22
5.2 Five Tripping Curves (EIT、SIT、VIT、DT、HVF)
INSTRUCTIONS
10000
5000
2000
1000
500
200
HVF
100
t(s)
50
EIT
20
10 VIT
5
SIT
2
DT
1
0.5
1 2 3 4 5 6 8 10 20
xIr
1000
500
200
100
50
Ig=0.2~1xIn
20
10
5
I2t ON
t(s)
2
1
Tg=0~0.4s
0.5 0.4s
0.3s 0.4s
0.2s 0.3s
0.2 0.2s
0.1s
0.1 0.1s
0s I2t OFF
0s
0.05
0.02
0.01
0.1 0.2 0.3 0.5 1 2 3
xIn
ACB
23
5.4 Leakage protection
200
100
50
20
If=1~30A
10
5
t(s)
2
Tf=0.1~1.0s
1 1.0s
0.8s
0.5 0.6s
0.4s
0.3s
0.2 0.2s
0.1 0.1s
0.05
0.02
0.01
0.5 1 2 3 5 7 10 20 30 100 200 500
If(A)
ACB
24
6. Intelligent Controller Usage
INSTRUCTIONS
■ Knob tuning zone: parameter for overload, short circuit, ground fault.
Instantaneous
Current setting Ii 2-4-6-8-10-11-12-15In-OFF
protection
■ Operation status zone: Run green light, Overload pre-alarmred light, alarm light.
LED
Status Overload
Run (green) Alarm Ir Isd Ii Ig
pre-alarm (red)
Normal light - - - - - -
■ Operation status zone: Run green light, Overload pre-alarm red light,
alarm light.
■ Knob tuning zone: parameter for overload, short circuit, ground fault.
Instantaneous
Current setting Ii 2-4-6-8-10-11-12-15In-OFF
protection
ACB
26
6.2 Page Description
INSTRUCTIONS
0A
N A B C
简 体 150
繁 体 100
50
English
0
Metering Status
Status :
Setup I (A)
Null
Maint T ( ℃)
Test U (V)
Events F (Hz)
U (V)
F (Hz)
Demand
Instant Ia= 0A
Ib= 0A
Iunbal Ic= 0A
In= 0A
Demand
Status Temperature:
I (A) T= +27.7℃
T ( ℃)
U (V)
F (Hz)
ACB
27
Metering Status
Instant
Uunbal △Φ = A - B - C
Sequence
Status Frequency:
I (A)
f=50.00Hz
T (°C)
U (V)
F (Hz)
PF= 0
Instant P(KW)
0
Demand Q(kvar)
0
Diagram S(kVA)
0
Instant
Diagram
Demand Q
Diagram P
ACB
28
INSTRUCTIONS
0A
N A B C
150
100
50
E.Total E.In
E.P(kwh)
E.In
0
E.Q(kvarh)
E.Out 0
E.Reset
E.Total E.Out
E.P(kwh)
E.In
0
E.Q(kvarh)
E.Out 0
E.Reset
E.Total
E.In
Yes
E.Out
No
E.Reset
E (kWh) Ia= 0A
Distortion
I (A) Ib= 0A
Harmonic Ic= 0A
FFT In= 0A
U (V)
Waveform
ACB
29
0A
100
50
Distortion THD
Uab= 0. 00 %
Ubc= 0. 00 %
Uca= 0. 00 %
Uan= 0. 00 %
I Ubn= 0. 00 %
Ucn= 0. 00 %
thd
Uab= 0. 00 %
Ubc= 0. 00 %
U Uca= 0. 00 %
Uan= 0. 00 %
Ubn= 0. 00 %
Ucn= 0. 00 %
Ia (3.31) Ia 0%
Fundament 3
5
7
Ib (3.31) 9
Distortion 11
13
Ic (3.31) 15
17
FFT 19
In (3.31) 21
23
25
Waveform 27
Uab (3.31) 29
Fundament Waveform Ia Ib Ic
Ia Ib Ic
Distortion
In
FFT
Uab Ubc Uca
Waveform
Uan Ubn Ucn
ACB
30
6.2.2 Parameter page
INSTRUCTIONS
0A
N A B C
150
100
50
Switch EIT
Protect
Ineutral
Metering
Iunbal
Contacts
Uunbal
Curve
Memory
Overload
Switch
Temp(°C) ON
Ineutral
ZSI Short
OFF
Iunbal
Ground
Uunbal
Memory Temperature
Alarm
Temp(°C)
ON
ZSI
Ground
Memory
Short
Temp(°C) ON
ZSI Ground
OFF
Ground
Memory
OFF
Temp(°C)
Trip
ZSI
Ground
ACB
31
Metering Knob Curve ON
Curve Alarm
OverVolt Alarm
rPower Alarm
Drop Out :
Prp = 50Kw
Trp = 10.0s
rPower ON
Monitor TYPE1
Sequence Ic 1= 1. 0Ir
Ic 2= 1. 0Ir
rPower Alarm
Monitor
△Φ=A - B - C
Sequence
ACB
32
Metering Knob SysType SysType
INSTRUCTIONS
0A
N A B C
150 Setup RatedFreq 3Φ 4W
Protect
4CT
100 Maint PowerSign
Metering
50
Test Idwindow
0 Contacts
Events Pdwindow
SysType RatedFreq
RatedFreq
50Hz
PowerSign
Idwindow
Pdwindow
SysType PowerSign
RatedFreq P+
PowerSign
Idwindow
Pdwindow
SysType Idemand
Metering
RatedFreq Window
PowerSign 30 Min
Idwindow
Pdwindow
SysType Pdemand
Metering
RatedFreq Window
PowerSign 30 Min
Idwindow
Pdwindow
Knob CON1:
Overload
Protect CON2:
Null
Metering
Contacts
ACB
33
6.2.3 Maintenance page
100
50
Metering Password
Enter New
Setup DataTime Enter Enter New Password
Password: Password: Again:
Maint State
XXXX XXXX XXXX
SysInfo
Test
ParaLock
Events
Password
Data
DataTime 18/01/03
State
Time
SysInfo
10:05:45
ParaLock
DataTime
Trips 0. 00%
State
SysInfo Reset
Operation
ParaLock
Trips
999 次
Operation
Contact Operation
Counter
Trips
999 次
Operation
Password Type:
AIC-
DataTime 1000HG
State Data:
180103
SysInfo
ParaLock
Password Parameter
Enter
DataTime Password: Lock
SysInfo Lock
No
ParaLock
ACB
34
6.2.4 Testing page
INSTRUCTIONS
0A
N A B C
150
100
50
Events
0A Language
N A B C
150 Comm 简 体
100 繁 体
50 English
0
Com.Para Mode
Mode Local
ACB
35
6.2.6 Record page
100
50
Trip 1/10
13- 09- 04
11:01:15
Alarm
ContactWear
Diagnosis 60%
Change
Trip 1/10
13- 09- 04
11:01:15
Alarm
Manual.Close
Diagnosis
Change
ACB
36
6.3 Factory setting
INSTRUCTIONS
Overload: On / Off
Thermal memory On
Short circuit: On / Off
Function
Short circuit: On / Off
ZSI Off
Ground fault: On / Off
Power direction P+ or P- P+
Contact 1 Instantaneous
Contact 26 status
Contact 2 Short circuit
1 2
L1
N
PE
2 4 6 8 10 12 14 16 18 22 24 26
DW
1 3 5 7 9 11 13 15 17 19 21 23 25
Major
Loop AIC Intelligent Controller
■1#,2#:
Working power supply input with DC24V, 1 # is positive and 2 # is negative.
■3#,4#,5#:
Fault tripping contact, passive output. When no fault tripping occurred, 3# and 4# is closing output, 4# and5# is open
output. Contact capacity is AC1/AC380V/2A, DC1/DC250V/0.3A.
■6#,7#:
Status auxiliary contact, passive output. Breaker at closing mode is closing output, open mode is open output.
Contact capacity is AC1/AC380V/2A, DC1/DC250V/0.3A.
■8#,9#:
Status auxiliary contact, passive output. Breaker at closing mode is closing output, open mode is open output.
Contact capacity is AC1/AC380V/2A, DC1/DC250V/0.3A.
■ 10 # , 11 # (for AIC-HC type) :
RS485communication outlet, 10 # is terminal A, 11 # is terminal B.
■ 12 # , 13 # (for AIC-H type):
First set of programmable contacts, passive output, normal open. Contact capacity is AC1/AC250V/2A, DC1/
DC30V/2A.
■ 14 # , 15 # (for AIC-H type):
Second set of programmable contacts, passive output, normal open. Contact capacity is AC1/AC250V/2A, DC1
DC30V/2A.
■ 16 # , 17 # (for AIC-H type):
ZSI output, Zo1, Zo2.
■ 18 # , 19 # (for AIC-H type):
ZSI input, Zi1, Zi2.
■ 21#, 22#, 23#, 24# (for AIC-H type):
3 phase voltage input, UN、U1、U2、U3.
Note: a. Phase sequence cannot be wrong.
b. 3 phase 4 wires system, UN must be connect.
c. 3 phase 3 wire system, UN and U2(B) must be shorted.
■ 25 # , 26 # ( for leakage protection or 3P+N):
input terminal for external transformer, N phase external CT or leakage ZCT
Note: a. for leakage protection, only use for ZCT input terminal.
ACB
b. for 3P+N, only use for external sensor for neutral input terminal.
39
7.2 Secondary Wiring Diagram
External
Transformer
S1 S2
SB3 SB2 SB1 Connect Testing Open
2 4 6 8 10 12 14 16 18 22 24 26 28 30 32 34 36 38 40 42 44 46 50 52 54
UVT SHT CC
DW
M
1 3 5 7 9 11 13 15 17 19 21 23 25
27 29 31 33 35 37 39 41 43 45 47 49 51 53
energy
storage
Power
Storage
Instructions
Major Position
Loop AIC Intelligent Controller UVT SHT CC Auxiliary contacts
Indications
Electric
Motor Operation
Device
2 4 6 8 10 12 14 16 18 22 24 26 28 30 32 34 36 38 40 42 44 46 50 52 54
UVT SHT CC
DW
M
1 3 5 7 9 11 13 15 17 19 21 23 25
27 29 31 33 35 37 39 41 43 45 47 49 51 53
energy
storage
Power
Storage
Instructions
Major Position
Loop AIC Intelligent Controller UVT SHT CC Auxiliary contacts
Indications
Electric
Motor Operation
Device
Note: (1) If CC, SHT and M are using different control voltage, they should connect to different power source.
(2) Terminal 35 and directly connect to power (automatic charging), or connect to a normally open button then connect to power
(manual charging)
ACB
40
7.2.3 Remote Control Secondary Wiring
INSTRUCTIONS
1 2
L1
N
PE
Main Circuit
Power Supply
RS485 Voltage External
Communication Ports ZSI Ports Input Transformer
Zo1 Zi1
A B Zo2 Zi2 UNU1U2U3 S1S2
SB3 SB2 SB1 Connect Testing Open
2 4 6 8 10 12 14 16 18 22 24 26 28 30 32 34 36 38 40 42 44 46 50 52 54
UVT SHT CC
DW
M
1 3 5 7 9 11 13 15 17 19 21 23 25
27 29 31 33 35 37 39 41 43 45 47 49 51 53
energy
storage
Power
Storage
Instructions
Major Position
Loop AIC Intelligent Controller UVT SHT CC Auxiliary contacts
Indications
Electric
Motor Operation
Device
Note: Set the first set of programmable contact (12 # , 13 # )"remote open" and pair with a SHT; set the second programmable contact
(14 # , 15 # ) to "remote close" and pair with a CC; then use the controller to send out signal for remote control.
ACB
41
8. Accessories and functions
■ 2 breakers
Backup Normal BW1600 1
ACB 1 ACB 2
0 0 BW1600 2
0 1
55 1 0
40 52
180
50
■ 3 breakers
Backup Normal Normal BW1600 1
600
52
■ 3 breakers
600
circuit breaker
cradle
0 0 1
ACB
42
8.2 Door Frame
INSTRUCTIONS
Fixed
Draw out
■ Use to interlock the breaker and the door, to prevent the door be open at"connected"position.
■ Right and left installation to choose from.
■ Break the breaker when the voltage is below 35%~70% of rated operation voltage.
■ Tripping time: Instantaneous, time delay 1, 3, 5s±10%
■ The coil cannot close the breaker without excitation, only reset when the voltage is back to 80%
of rated operation voltage.
■ Suction acid type and self-priming type to choose form.
ACB
43
8.5 Power Module
AC/DC 100~240
DC 24~60
2 1 PE + -
Input Output
35.5
135
Output Voltage:
DC24V/300mA
Power Supply
71.0 49.3
3
4.
Ø
It is used together with circuit breaker with three poles in the power distribution system of TN-S and
Installed on the neutral conductor with 2m at maximum far from the installation point. Connect to
secondary wiring terminal 25# and 26#.
S1-K S1-1
11
95.5
51
20
81
P1-K
40.5
124.5
ACB
44
8.7 Zero-phase sequence current sensor (ZCT)
INSTRUCTIONS
Rectangular sensor enables the detection of zero-phase sequence current which is required for the
earth-leakage protection. It is installed around the bus-bars (phases + neutral). Ratio: 30A:300mA.
D
S1
H
e
S2
a
M N
A E
M D
W N
Standard W H D a e M N
S1 S2 S3 S4
Input Output
External module of
35.5
135
transformer’s center
71 49.3
3
4.
Ø
ACB
46
9. Safety Distance
INSTRUCTIONS
A
B B
B B
To insulator To metal
A B A B
Draw out 0 0 0 0
Fixed 0 30 0 70
Continued
Inm:1600A 1In 0.96In 0.92In 0.87In 0.8In
capacity
Model BW1600-SN
Thickness mm 5 5 5 5 5 5 10
Width mm 20 50 40 50 40 40 50
ACB
47
12. Secondary Wiring Diagram
2-Ø8.5 2-8.5X10.5
95
Draw-out type
73
In a (mm)
72.5(3P) 630-1000A 10
142.5(4P) 72.5 1250, 1600A 18
Switchboard
Door Position
a
345
318
320
107
a
68
109 109 300
137.5(3P)
341(Disconnection)
207.5(4P) 137.5
258
220
10-Ø5
12-Ø11(3P)
70(4P) 70 70 16-Ø11(4P)
Normal
Type
15
32.5
120.5
321
357
25
50
70(4P) 70 70
161
ACB
Elongated
20 15
Bottom
52.5
Type
25 12-Ø11(3P)
ACB
48
12.2 Fixed type (Unit : mm)
INSTRUCTIONS
4-9X14
100
Fixed type
52
121(3P) In a (mm)
191(4P) 121 630-1000A 10
Switchboard
Door Position 1250, 1600A 18
312
a
107
a
30
109 109
132.5(3P) 201
202.5(4P) 132.5
257
8-Ø5 220
12-Ø11(3P)
70(4P) 70 70 16-Ø11(4P)
Normal
Type
15
32.5
25
50
143
ACB 70(4P) 70 70
Bottom Elongated
20 15
52.5
Type
25
ACB
49
13. Mounting, Usage, and Maintenance
■ Before mounting, check the specifications of the circuit breaker to make sure if they meet
the requirements.
■ Before mounting, check the insulator resistance with a 500V megger. The resistance should
not be less than 10MÙwhen the surrounding medium temperature is 20℃ +5℃ with a
relative humidity between 50% and 70%. If not, please dry it until the insulator resistance
satisfies the requirements.
■ The base of the breaker should be installed horizontally and ¬fixed by M10 screws.
■ Circuit breakers should have reliable ground fault, and the ground fault points should be
clearly marked. Fixed-type circuit breakers should strictly follow safe distance regulations.
■ After mounting a circuit breaker according to the wiring diagram, the circuit breaker should
be tested for the following matters before the main circuit is powered (for a drawer-type of
circuit breaker, follow the instructions on the cradle for testing).
A. Check if the under-voltage, shunt release and closing electromagnet have well matched electric motor
operation voltage (the breaker cannot be operated unless the under-voltage release is closed).
B. Energy-storage will be indicated after tripping the handle on the cover seven times. When hearing a click
sound, energy storing is completed. Press the closing button or turn o-the electromagnetic switch to securely
close the circuit breaker. Flip the handle again to start energy storage.
C. Turn on the power of electric motor energy storage device and"energy storage"will be displayed.
There will be a click sound when energy storage is completed. The motor will be turned o-automatically.
Press the"closing"button or closing the electromagnetic switch for closing the circuit breaker reliably.
D. When the breaker is closed in a tripping test (See 8.2.3d), the circuit breaker should be tripped by the tripping
button of under-voltage or the release shunt or the tripping button on the cover.
ACB
50
13.2 Commonly Problem and Trouble-shooting
INSTRUCTIONS
● Under voltage release is active. ● Check the wiring, and turn on the
● Intelligent controller has not been reset. power of under voltage release.
● Operation mechanical has no energy ● Press the reset button.
1 Circuit breaker can not be closed storage. ● Manual charging.
● Draw out type is not in"connect" ● Use the handle and operate the breaker
or "testing"position. to"connect"or"testing"position.
● "Open" lock is in lock. ● Use the key to unlock.
● Power of the electric operation machine ● Check the wiring, and turn on the power.
Circuit breaker cannot use
2 is not on. ● Check if the operating voltage is greater
automatic charging
● Insufficient power capacity. than 85%Us.
ACB
51
MEMO
MOTOR CONTROL (CONTACTOR/ MS/ MMS), CIRCUIT BREAKER (MCCB/ ELCB/ EMCCB/ MCB), AIR CIRCUIT BREAKER, AUTOMATIC
TRANSFER SWITCHES (Panel Board Type/ Residential Unit Use), SURGE PROTECTIVE DEVICE, LOW VOLTAGE POWER CAPACITORS,