Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker
Whether for medium voltage distribution networks or industrial
applications, if you’re looking for outdoor circuit breakers
PM 104398
from a name you can trust, look to Schneider Electric and
the PCOB-36. Backed by decades of experience, and with
over 100,000 circuit breakers in operation all round the world,
Schneider Electric is the recognised market leader in the field
of medium voltage switchgear.
Over 30 years experience in the field
First manufactured in the 1980’s, Schneider’s Porcelain Clad
Outdoor Breaker (PCOB) quickly gained acceptance amongst
network designers, public utilities and private industries world-
wide. The PCOB-36 circuit breaker incorporates a minimum
of moving parts, ensuring a high degree of reliability – the
mechanism has undergone exhaustive mechanical, laboratory
and field-endurance testing.
Applications
PCOB-36 is particularly suitable where a reliable power supply is needed
in distribution networks such as:
• Short-circuit protection
• Transformer switching
• Cable switching
Benefits • Over head line switching
• Capacitor bank Switching
• Simple to install and to operate • Load transfer and auto reclosing
• Robust construction Reliability Installation
The low energy requirements and To ensure safe transportation and
• Reliable conception makes it for unique design of the vacuum facilitate installation, the PCOB-36
interrupters make the PCOB-36 is despatched to customers with
long time of service extremely reliable in service. the mounting structure packed
separately to the Circuit Breaker
• Up-to-date vacuum interrupters Quality assembly & operating mechanism.
technology As an option arrangement for
Rigorous quality and service
Current Transformer / Power
standards are maintained
Transformer mounting support
• Maintenance reduced at the throughout the production
process, structure if needed.
minimum
Increased creepage and strength
are provided by the high quality Low maintenance
operating rod. Minimal maintenance requirements
and proven long service life deliver
Out of phase Duty reduced lifecycle costs.
The PCOB-36 is suitable for out-of
phase duty. Environment
The PCOB-36 is designed to
be suitable for heavily polluted
Moisture resistance environments,
Double lip sealing gaskets
The PCOB-36 has been designed
significantly reduce the possibility
in order to be environment-friendly
of moisture ingress.
it does not contain toxic materials.
NRJED315626EN - PCOB 36 - 21-01-2015 [Link] 1 19/02/2015 [Link]
Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker
Features Pole Assembly
PM 104399
The inclusion of high-performance, robust vacuum interrupters make Top Terminal
the unit suitable for all switching duties in medium voltage electrical
distribution networks. Capable of interrupting over 100 full short-circuit
operations, and more than 30,000 close-open operations at normal load Porcelain Insulator
current, the PCOB-36 is a field-proven solution with broad international
industry acceptance. Vacuum Interrupter
Bottom Terminal
Construction
• Vacuum Interrupters are housed inside hollow porcelain insulators
• Three single-phase assemblies are mounted on a common base frame Insulating Rod
that also supports a mechanical drive linkage
• The main drive rod is actuated by the drive mechanism, rotating the
bell crank which actuates the insulated drive rod assembly and closes
the breaker
• Each vacuum interrupter is connected to a top terminal plate which is
fixed to the porcelain insulator
Reliable operating mechanism Operating mechanism
The robust and reliable PCOB-36 operating mechanism offers the
PM 104400
following features:
• Motor-driven, spring charged
• Automatically charged after each closing operation
• O-C-O operation without recharging
• Mechanical / electrical anti-pumping
• Provision for manual charging
• Manual closing and tripping arrangement
• Mechanical ON-OFF, operation counter and spring-charged indication
NRJED315626EN - PCOB 36 - 21-01-2015 [Link] 2 19/02/2015 [Link]
Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker
Operating conditions
Ambient conditions in accordance with Standards IEC 62271-1/ IEC 62271-100
Temperature class ≤ 40°C
Minimum / Maximum ambient temperature -10°C/ *55°C degree °C
Average value over 24 hours 35 degree °C
Average relative humidity: 24 hours / 1 month ≤ 95% / ≤ 90%
Installation altitude above sea-level ≤ **1000 m
* De rating of rated continuous current applicable at 55°C
** Please contact Schneider electric
Technical characteristics
Rated Voltage 36 kV
Rated power frequency withstand voltage 70 kV
Rated lightning impulse withstand voltage 170 kV peak
Rated frequency 50 Hz
Rated short time withstand current 25 kA - 3 s
Rated peak withstand current 62 kA peak
Rated continuous current 1250 A / 2000 A
Degree of protection IP55
Standards IEC-62271-100/IS-13118
Operating sequence O-0.3s-CO-3min-CO
Weight (Breaker/HDG structure) 320 Kg / 60 Kg (Aprox.)
Pole Material Porcelain
PM 104401
NRJED315626EN - PCOB 36 - 21-01-2015 [Link] 3 19/02/2015 [Link]
Medium
Voltage PCOB-36
Switchgear Outdoor Vacuum Circuit Breaker
Installation
SM 100749
AL Top terminal 1686
700 700
Top insulator
AL bottom
terminal
Bottom insulator
Lifting huck 463
Earth pad
Operating handle for
Arrangement manual charging
for pad lock
3895
3408
Operating height
1497
Operation platform
1871
548
Plinth Plinth
545
300
Ground level
1350
Leg
M16 x 500 «J» Bolt 4-Ø14 Holes
150
Plinth level
300 Plinth
ground level
Grouting material
895
containing M20 or
100
40
above grade concrete
sand & cement mixture
30
Section on «A-A»
4-Ø18 Holes for
© Schneider Electric Industries SAS - All rights reserved
foundation fixing with
M16 «J» foundation bolts 40 30
545 150
Foundation plan Detail of terminal
Schneider Electric Industries SAS As the standards, specifications and designs change from time to time, please ask for
35, rue Joseph Monier confirmation of the information given in this publication.
CS30323
F - 92505 Rueil-Malmaison cedex (France) This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Share capital: €896,313,776 Conception: Schneider Electric Industries SAS
[Link] Photos: Schneider Electric Industries SAS
Printing: Altavia
NRJED315626EN 01/2015
NRJED315626EN - PCOB 36 - 21-01-2015 [Link] 4 19/02/2015 [Link]