0% found this document useful (0 votes)
349 views1 page

ASHRAE Duct Fitting Database V5.00

This document provides information about a round to rectangular transition duct fitting, including its inputs like diameter and length, and outputs like velocity and pressure loss. The fitting is for exhaust and return air systems, and references are made to Idelchik for more details.

Uploaded by

carte_blue
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
349 views1 page

ASHRAE Duct Fitting Database V5.00

This document provides information about a round to rectangular transition duct fitting, including its inputs like diameter and length, and outputs like velocity and pressure loss. The fitting is for exhaust and return air systems, and references are made to Idelchik for more details.

Uploaded by

carte_blue
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Tel: ASHRAE DUCT FITTING DATABASE

Fax: Version # 5. 00.00 Tuesday, July 12, 2022

(ED4-2) Transition, Round to Rectangular, Exhaust/Return Systems


(Idelchik 1986, Diagram 5-27)

INPUTS OUTPUTS

Diameter (Do, in.) 23.6 Angle (Theta1, deg.) 9


Height (H1, in.) 25.6 Angle (Theta2, deg.) 36
Width (W1, in.) 31.5 Velocity (Vo, fpm) 1807
Length (L, in.) 12.0 Velocity (V1, fpm) 983
Flow Rate (Q, cfm) 5500 Vel Pres at Vo (Pvo, in. wg) 0.20
Density (lbm/ft^3) 0.075 Vel Pres at V1 (Pv1, in. wg) 0.06
Loss Coefficient (Co) 0.29
Pressure Loss (in. wg) 0.06

07-12-2022 version: 5.00.00