0% found this document useful (0 votes)
389 views3 pages

Electrical Distribution System Design

The document discusses the design of electrical distribution systems. It describes the primary distribution system which distributes power at high voltages to large consumers and substations using 33kV, 11kV, 6.6kV or 3.3kV three-phase systems. Primary distribution design considers choices of voltage, conductor size, distribution types, and voltage drop. Secondary distribution distributes power at lower voltages to small consumers using 400/230V three-phase systems. Secondary distribution is linked to primary distribution via substations which step down voltages. Substation design considers feeder ratings, fault current limiting, and underground versus overhead cable configurations.

Uploaded by

Kelvin Oo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
389 views3 pages

Electrical Distribution System Design

The document discusses the design of electrical distribution systems. It describes the primary distribution system which distributes power at high voltages to large consumers and substations using 33kV, 11kV, 6.6kV or 3.3kV three-phase systems. Primary distribution design considers choices of voltage, conductor size, distribution types, and voltage drop. Secondary distribution distributes power at lower voltages to small consumers using 400/230V three-phase systems. Secondary distribution is linked to primary distribution via substations which step down voltages. Substation design considers feeder ratings, fault current limiting, and underground versus overhead cable configurations.

Uploaded by

Kelvin Oo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd

The distribution may be subdivided mainly into primary distribution system,

distribution transformers, secondary distribution and consumer’s service connections. The


electrical design will involve choosing the distribution voltage for primaries, size and
location of distribution transformers, type of distribution system for primaries and secondary,
allowable voltage regulation on load, length of the lines and the size of conductors used for
the distribution system.
Addition of voltage regulation devices is sometimes necessary for control. The design
involves the correct choice and application of transformers and their accessories. The
expected operating characteristics should be determined and the necessary protection
provided. Protective equipment should be properly chosen. Arrestors, grounding methods,
spacing of wires and insulation levels to be used for the lines should be properly chosen.
2.7.1. Primary Distribution
The primary distribution would be the circuits supplying power at high voltage to
large consumes such as industrial consumers and to distribution substation. The voltages are
33kV, 11kV, 6.6kV, and 3.3kV. The three-phase, three wire system is adopted for primary
distribution.

2.7.2. Primary Distribution Design


The following points have to be considered in the design of primary distribution.
 Choice of voltage
 Conductor size
 Types of distribution systems
 Voltage drop
 Design of primary network
The design of primary network involves the determination of the followings:
 location, size and character of larger loads on the primary distribution system
 location, size and character of small loads on the primary distribution system
 anticipated load growth in the area
 location of power stations- generation stations or receiving stations
 capacity of transformers, substations, distribution circuits
 available sites for substations
 routes for distribution
 sub transmission supply circuits
 tie feeders if necessary and
 use of network transformer units

2.7.3. Secondary Distribution


The secondary distribution system would take the power to consumers such as
domestic consumers at distribution voltage. This is the low voltage distribution at the voltage
which is directly utilized by small and average consumers. Therefore, the 400/230V, 3 phase,
4 wire system is adopted for secondary distribution.
The advantages of the three phase, four wire systems are at a time, one gets two
voltages, 400V and 230V the three phase supply is given to factories, whereas, the single
phase supply is given to houses for light and fan loads.
2.7.4. Secondary Distribution Design
The link between the primary distribution and secondary distribution is a series of
substations suitable located to step-down the voltage of the primary distribution system to the
secondary distribution voltage. The following points have to be considered.
 Choice of voltage
 Conductor size
 Types of secondary distribution
 radial system
 loop radial or low voltage secondary network

2.8. Substation in Distribution


Substations are used throughout an electrical system. Starting with the generating
station a substation raises the medium-voltage generated by the synchronous generators to
high-voltage needed to transmit the energy economically. The high transmission-line voltage
is then reduced in those substation located close to the power consuming centers. The
electrical equipment is such distribution substation is similar to that found in substation
associated with generating plants.
A substation is fed by three separated lines all operating at 220 kV. It contains six 3-
phase transformers rated at 36/48/60 VA. The windings are connected in wye-delta(Y-∆) and
automatic tap-changers regulate the secondary voltage. A neutral is established on the
medium voltage side by means of 3-phase grounding transformers.
2.8.1. Medium Voltage Distribution
Thirty-six 3-phase feeders (30 active and 6 spares) rated at 24.9 kV, 400 A lead
outward from the substation. Each feeder is equipped with the current limiting reactors that
limit the line to ground short circuit currents to a maximum of 12 kA. Some feeders are
underground, other overhead and still others are underground or overhead.
Underground feeders are composed of three single-phase standard aluminum cables
insulated with polyethylene. The insulation is in turn surrounded by a spiral wrapping of
tinned copper conductors which act as the ground. The cable is pulled through underground
concrete duct of simply buried along with active cables to provide alternate service in case of
a fault.

You might also like