« MITSUBISHI
Page 1/2
ovmuee MITSUBISHI ELECTRIC CO.
[CONTRACT No: Touenr: (Site:
IME/EWICI3485- MINISTRY OF ELECTRICITY & WATER, _|KIFAN ‘W' 300/132kV
|2006/2007 KUWAIT [Substation
[PLANT ITEM:
STS No. 3-20 ‘AREVA MBCI Translay Differential Protection Relay -
Secondary Injection
CIRCUIT: _300 kV UGC TOWN W Feeder Panel: _A3_RP
1. Relay Data Preliminary Check
Model Number: _ MBCIO{V1AB02018 Visual inspection [_ OK _| Insulation resistance [Ma] [ >1000
Serial Number: __2627191/01/08 Relay earthed OK | Output relay tests OK
Relay Rating: 1A Output contacts [OK | RSTAB=120
‘Aux. Supply (Vil: __140/220VDC LED test OK
3. Calculated Operating Current at N=3
Phase RN Y-N BN RY YB BR
Formula | 0.19°Ks"In | 0.25°Ks*in | 0.33°Ks%in_| 0.8°Ks%in | 1.0°Ks*In _| 0.44°Ks"In
‘Note:- With pilot Open relay operating at approximately 50% times the current setting
4. Secondary Injection
44 Settings
Parameter N Rp Pilot Circuit
Setting 3 470 Ohm Open
4.2 Pickup test
Ks=0.5 Ks=0.75 Ks=1.0
Phase |p [mA] | PilotOP. | lop[mA] | PilotOP. | lop [mA] | PilotOP
alc. | Meas. | Volt [V]| Calc. | Meas. | Volt [VJ | Calc. | Meas. | Volt [VJ
RN | 475 [55 Sa 71.25 | 75 729 | 95 | 95 | 9.46
YN | 625 | 70 494 | 93.75 | 95 702 | 125 | 125 | 949
BN | 625 | 95 505 | 123.75 | 425 | 691 | 165 | 165 | 9.40
RY | 200 | 195 | 5015 300 | 292 70 | 400 | 300 | 9.46
ye | 250 | 245 | 5.076 375 | 365 | 695 | 500 | 490 | 9.18
BR | 110 | 110 5.29 165 | 165 | 7.20 | 220 | 220 | 9.10
KS=1.5 Ks=2.0 Ks=~ Relay NOT TRIP
Phase |_/0PImA] | PilotOP. | lop[mA] | Pilot OP. | lop [mA] | Pilot OP
Calc. | Meas. | Volt_[V]|~Calc. | Meas. | Volt [V]| Calc. | Meas. | Volt [V]
RN | 425 | 135 13.8 190 | 175 | 1806 | © | 2000| 704
YN | 487.5 | 175 | 13.62 250 | 230 | 1809 | = | 2000 | 55.83
BN | 247.5 | 230 | 13.43 330_| 305 | 1802 | = | 2000| 40.65
Ry | 600 | 585 | 13.35 soo | 730 | 18.16 | = | 2000 | 650
ye | 750 | 735 | 1363 | 1000 | 970 | 1803 | = | 2000 | 50.16
BR | 330 | 325 | 13.35 | 440 | 430 | 1803 | © | 2000| 65.59
‘Accuracy: Current 210% of setting valve
DATE TESTEDBY. WITNESSED BY: "APPROVED BY:( ?
wes uercoF7 fa [mew MEWPage 2/2
“““ MITSUBISHI ELECTRIC CO.
% MITSUBISHI
[CONTRACT No: [ouienr: Site:
ME/EWICI3485- MINISTRY OF ELECTRICITY & WATER, _|kIFAN ‘W' 300/132kV
‘2006/2007 KUWAIT \Substation
[PLANT ITEM:
STS No. 3-20 ‘AREVA MBCI Translay Differential Protection Relay -
‘Secondary Injection
5. Calculated Operating Current at N=6
Phase RN YN BN RY ¥B BR
Formula | 0.12°Ks*In | 0.14°Ks"In_| 0.17°Ks'In_| 0.8°Ks'In__| 1.0°Ks"In__| 0.44°Ks*In
‘Note:- With pilot Open relay operating at approximately 50% times the current setting
5.1 Settings
Parameter N Rp Pilot Circuit
Setting 6 470 Ohm ‘Open
5.2 Pickup test
Ks=0.5 Ks=0.75 KS=1.0
Phase |_op [mA] | Pilot OF. lop[mA] | PilotOP. | lop [mA] | Pilot OP
Calc. | Meas. | Volt [V1 |" Calc. | Meas. | Volt {VJ | Galc. | Meas. | Volt [V]
RN | 30 | 35 5.12 45 50 7.74 60 | 60 9.30
YN | 35 | 40 4.94 52.5 | 55 7.43 70_\_70 9.73
BN | 425 | 50 5.34 63.75 | 65 7.24 a5 | 85 95
RY | 200 | 195 5.52 300_| 280 742 | 400 | 375 | 9.44
¥B | 250 | 245 5.22 375 360 | 7.32 | 500 | 490 | 9.33
BR | 110 | 105 5.26 165 | 160 767 | 220 | 215 | 9.89
Ks=1.5 KS=2.0 Ks== Relay NOT TRIP
Phase |p [mA] | PilotOP. | lop[mA] | PilotOP. | lop [mA] | Pilot OP
Calc. | Meas. | Volt [V] |" Calc. | Meas. | Volt [VJ | Calc. | Meas. | Volt [V]
RN | 90 85 13.69 wo | 15 | 1787 | = | 2000| 69.1
Yn [105 | 400 | 13.62 14o_| 135 | 1788 | = | 2000 | 60.54
BN | 427.5 | 120 | 13.42 1o_| 155 | 17.68 | = | 2000 | 51.67,
RY | 600 | 585 | 14.24 300 | 760 | 1091 | = | 2000| 652
ye | 750 | 735 | 14.04 | 1000 | 970 | 1801 = | 2000 | 65.21
BR | 330 | 320 13.69 440_| 430 | 1018 | = | 2000 | 658
‘Accuracy: Current #10% of setting value
6. Timing test
Injected Current 5 times Pickup Current
Setting Kte40 Kt=20 Ke=t4. Kré Kees
Phase Calc. [ Meas. | Calc. | Meas. | Calc. | Meas. | Calc. | Meas. | Calc. | Meas.
Rim sec] 30.7 48.2 60.2 79.2 257.2
¥ [msec] 30 | 285 | 50 | 467 | 65 | 584 | 90 | 77.5 | 300 | 255.9
B Im sec] 34.5 49.3 64.4 80.2 255.4
7. Secondary injection with pilot Cable Shorted
Phase RN _1A injected Y-N_1A injected BN 1A injected
Relay Status ‘Not Tripping ‘Not Tripping ‘Not Tripping
DATE: TESTEDEY. WITNESSED BY: APPROVED. Ko
0500 | weico 7, Mew MEW ZPage 1/2
ae MITSUBISHI MITSUBISHI ELECTRIC CO.
[CONTRACT No: [CuIENT: Site:
ME/EW/C/3485- MINISTRY OF ELECTRICITY & WATER, _|KIFAN 'W’ 300/132kV
'2006/2007 KUWAIT [Substation
IPLANT TEM
STS No. 3-20 ‘AREVA MBCI Translay Differential Protection Relay -
Secondary Injection
CIRCUIT: — _300 KV UGC JABRIEH W’ Feeder Panel: _A_RP
4. Relay Data 2. Preliminary Check
Model Number: _MBCIO1V1AB0261B Visual inspection [OK _ | Insulation resistance [Ma] [ >1000
Serial Number: 72827192/01/08 Relay earthed OK | Output relay tests ‘OK
Relay Rating: +A Output contacts [OK | RSTAB=120
‘Aux. Supply [Vi]: __ 140/220 VDE __ LED test ‘OK
3. Calculated Operating Current at N=3
[ Phase RN Y-N BN RY YB BR
[Formula | 0.19°Ks*In_| 0.25°Ks"In_| 0.33°Ks*in_| 0.8°Ks"In__| 1.0°Ks"In__| 0.44°Ks"In
‘Note:- With pilot Open relay operating at approximately 50% times the current setting
4. Secondary Injection
4.4 Settings
Parameter N Rop Pilot Circuit
Setting 3 420 Ohm Open
4.2 Pickup test
Ks=0.5 Ks=0.75 Ks=1.0
Phase |p [mA] | PilotOP. | lop[ma] | Pilot OP. | lop [mA] | PilotOP
Calc. [ Meas. | Volt [VJ |" Calc. | Meas. | Volt [V] | Calc. [ Meas. | Volt [VJ
RN | 47.5 | 55 SAT 71.25 | 75 7.36 95 | 95 9.58
YN | 625 | 70 5.08 93.75 | 95 7a | 125 | 125 | 9.65
BN | 825 | 95 5.13 | 123.75 | 125 705 | 165 | 160 | 9.25
RY | 200 | 195 5A2 300 | 290 7.08 | 400 | 390 | 9.54
yp | 250 | 245 5.19 375 | 365 707 | 500 | 490 | 9.29
BR | 10 | 105 54 165 | 165 732 | 220 | 215 | 9.26
Ks=1.5 Ks=2.0 Ks=© Relay NOT TRIP
Phase |—lP [mA] | PilotoP. | lopfmaj | PilotOP. | lop [mA] | Pilot OP
Calc. | Meas. | Volt_[V] |“ Calc. | Meas. | Volt {V1 | Calc. | Meas. | Volt [VJ
RN_| 1425 | 135 | 13.39 190 | 175 | 1806 | © | 2000| 71.2
YN | 167.5 | 180 13.79 250 | 230 | 1809 | = | 2000| 55.92
BN | 247.5 | 235 13.90 330 | 305 | 1802 | ~ | 2000| 404
600 | 590 13.51 300 | 730 | 1816 | ~ | 2000| 655
750 | 735 | 1379 | 1000 | 970 | 1803 | «© | 2000 | 50.11
330 | 325 | 13.52 440_| 430 | 18.03 = | 2000 | 66.7
Current 210% of setting value 1D)
DATE: TESTEDBY: WITNESSED BY: APPROVED BY: \_&
nse | werco P74 =f law i Zza. MITSUBISHI
mnt
Page 2/2
“““ MITSUBISHI ELECTRIC CO.
[CONTRACT No: [ouieNT: Site:
IME/EWICI3485- MINISTRY OF ELECTRICITY & WATER, _|KIFAN ‘W' 300/132kV
‘2006/2007 KUWAIT (Substation
(PLANT TTEW:
STS No. 3-20 ‘AREVA MBCI Translay Differential Protection Relay -
Secondary Injection
5. Calculated Operating Current at N=6
Phase RN YN BN RY. YB BR
Formula | 0.12°Ks"in_| 0.14°Ks"In_|0.17°Ks"in_| 0.8°Ks"In__| 1.0°Ks*in | 0.44°Ks*In
‘Note:- With pilot Open relay operating at approximately 50% times the current setting
5.1 Settings
Parameter N Rep Pilot Circuit
Setting 6 420 Ohm ‘Open
5.2 Pickup test
Ks=05, Ks=0.78 Ks-1.0
Phase |—lP [mA] | Pilot OP. | lop[mA] | PilotOP. | lop [mA] | Pilot OP
Calc. | Meas. | Volt_[V]| "Calc. | Meas. | Volt [VJ | Calc. | Meas. | Volt [VJ
RN | 30 | 35 5.29 ry 50 7.26 60 | 60 9.59
YN | 35 | 40 5.09 25 | 55 7.29 70 | 70 948
BN | 425 | 50 553 | 63.75 | 65 742 6 | 85 9.26
RY | 200 | 195 5.62 300_| 280 7.28 | 400 | 375 | 9.67
ye | 250 | 245 5.35 375 360 | 7.43 | 500 | 490 | 9.52
BR | 110 | 105 5.39 165 | 160 | 695 | 220 | 215 | 9.32
Ks=1.5 i Ks52.0 Ks=0 Relay NOT TRIP
phase |_op [mA] | PilotOP. | lopimA] | PilotOP. | lop [mA] | Pilot OP
Calc. [ Meas. | Volt [VJ |" Calc. | Meas. | Volt [V] | Calc. | Meas. | Volt [V]
RN | 90 85 13.87 120 | 110 | 1813 | © | 2000| 69.5
YN | 105 | 100 | 13.89 140_| 125 | 1750 | = | 2000 | 60.66
BN | 1275 | 115 | 13.67 170 | 155 18.0 =| 2000 | 51.57
Ry | 600 | 585 | 13.69 ‘goo | 760 | 17.67 | = | 2000| 654
ye | 750 | 735 | 13.62 | 1000 | 970 | 18.34 =| 2000 | 56.57
BR | 330 | 320 13.96 440_| 430 | 1777 | = | 2000| 664
‘Accuracy: Current #10% of setting value
6. Timing test
Injected Current 5 times Pickup Current
Setting Kit=20 Kiet Kee Kes
Phase Cale. | Meas. | Calc. | Meas. | Calc. | Meas. | Calc. | Meas.
Rim sec] 476 59.5 79.7 258.1
Y [m sec] 50 [456 | 65 [575 | 90 | 782 | 300 | 257.0
B [msec] 48.4 60.1 80.7 255.5
7. Secondary injection with pilot Cable Shorted
Phase RN _1A injected ¥N_1A injected BN 1A injected
Relay Status ‘Not Tripping ‘Not Tripping ‘Not Trippi
DATE: TESTEDBY: 7) WITNESSED BY: ‘APPROVED B)
20800 | werco-A7, Lf twen mew