L4 Air Handling Unit
L4 Air Handling Unit
HVAC DISTRIBUTION
SYSTEMS
Capital cost;
Operating cost;
Maintenance cost;
Replacement costs;
Upgrading costs;
Equipment failure costs;
Return of investment (ROI)/Life cycle
analysis.
Each of these concerns has a different
priority depending on the customer’s
goals.
Most customers may not understand
HVAC design aspects nor their benefits
and limitations.
It is the responsibility of the Architect
and the HVAC Engineer to guide and
advise the customer on the best option.
For an HVAC Engineer, the customer
may be an Architect whose customer
HVAC DISTRIBUTION
SYSTEMS
Based on the fluid media used in the thermal distribution system,
air conditioning systems can be classified as:
1. Single duct;
The single duct systems can provide either cooling
or heating using the same duct, but not both
heating and cooling simultaneously
Expensive to operate.
These systems are energy inefficient as
the system involve simultaneous use of
cooling and reheat. For this reason, use
of reheat systems is strictly regulated by
most energy codes and standards. Many
state and local regulations restrict the
use of reheat (see ASHRAE Standard
90.1)
DUAL DUCT SYSTEMS
Advantages of Dual Duct Systems:
In a room, a fan coil unit is usually ceiling mounted on a plenum space at the
entrance corridor between the wardrobe and the bathroom. Typically 50 to 80 cfm
of treated fresh air is supplied to a room while 30 to 50 cfm is constantly exhausted
from the bathroom. This keeps the room ventilated and pressurized.
• Lower operating cost due to smaller fans, lower reheat requirements, energy and
moisture recovery
PART 4 ALL WATER (HYDRONIC)
SYSTEM
Terminal units are 100% recirculation
units. System ventilation is usually
accommodated by opening windows, by
infiltration, or installing outside wall
openings.
Water Systems only control temperature.
Filtering of the air is normally carried out
through the indoor fan coil terminal
units.
All - Water System
Advantages:
1. Water is an effective heat transfer medium; therefore,
distribution pipes generally are of relatively small volume
compared to air ducts.
2. Recirculation of air is unnecessary, so comingling of
odors and contaminants, or concerns over fire and smoke
spreading from one zone to another, are minimized.
3. First cost is often less than for other central systems.
4. Less building space is required.
5. More suitable for retrofit applications.
6. Off-hour conditioning does not require central air
system operation.
7. Cooling can be easily shut off in
unoccupied areas.
8. Quieter than unitary systems.
9. Minimal space needed for air handling
rooms and duct clearances.
10. Individual zone temperature control.
11. Variable speed secondary pumps can be
used to improve comfort control and reduce
operating costs.
12. Can use heat recovery techniques.
13. Flexible and readily adaptable to many
building module requirements.
14. Provides individual room control.
15. Prevents cross contamination of
recirculated air from one room to another.
All – Water System Disadvantages:
1. All the three HVAC distribution systems share one common objective
as a system. It is to control the environment of an interior space.
2. All three systems use heating coils to heat the air and cooling coils to
cool it. The location of the coils varies from system to system. In the
all-air system the heating/cooling coils are located in the central air-
handler. In the air-water system the coils are located in the air-handler
as well the terminal units. In the in all-water system the coils are
located in the multiple terminal units located in the indoor spaces.