1
Chapter Five
5. load calculations
03/14/2025
Outline
2
1. Load calculations – Solar heat gain – Heat transfer
through building structures
2. Internal heat gains – Occupancy, Lighting and
Appliances load, Process load, System heat gains and
Cooling loads.
3. Effective Sensible Heat Factor
03/14/2025
1. Load calculations
3
Need to calculate cooling & heating load
By carrying out cooling and heating load calculations
one can estimate the capacity that will be required for
various air conditioning equipment.
For carrying out load calculations it is essential to have
knowledge of various energy transfers that take place
across the conditioned space.
03/14/2025
Indoor and outdoor conditions
4
To estimate the required cooling or heating capacities, one has to
have information about design indoor and outdoor conditions,
Specifications of the building, Specifications of the conditioned
space (such as the occupancy, activity level, various appliances and
equipment used etc.) and any special requirements of the particular
application.
03/14/2025
Indoor Conditions
5
The required inside design conditions depend on the intended use of the
building.
For comfort applications, the required indoor conditions are fixed by the
criterion of thermal comfort (that condition of mind which expresses
satisfaction with the thermal environment )
Thermal comfort is affected by activity, clothing, air DBT, RH, air velocity
and surrounding temperature
For industrial or commercial applications the required indoor conditions
are fixed by the particular processes being performed or the products being
stored. 03/14/2025
Outdoor conditions
6
Outdoor conditions are chosen based on design dry bulb and
coincident wet bulb temperatures for peak summer or winter
months for cooling and heating load calculations, respectively.
Effective temperature (ET):
combines the effects of dry bulb temperature and air humidity
into a single factor
defined as the temperature of the environment at 50% RH
03/14/2025
7
The design outside conditions also depend on the following factors:
a) Type of the structure, i.e. Whether it is of heavy construction,
medium or light
b) Insulation characteristics of the building
c) Area of glass or other transparent surfaces
d) Type of usage
e) Nature of occupancy (action of occupying the space)
f) Daily range (difference between maximum and minimum
temperatures in a given day) 03/14/2025
ASHRAE comfort chart for a sedentary
person
8
•Based on the chart ASHARE makes the following recommendations
Inside design conditions for Winter: Inside design conditions for Summer:
T between 20.0 to 23.5 C at a RH of 60%
op o
Top between 22.5 to 26.0oC at a RH of 60%
Top between 20.5 to 24.5oC at a DPT of 2oC
Top between 23.5 to 27.0oC at a DPT of 2oC
ASHRAE 55 – 2004 Comfort Zone
• Air temperature –Typically 22-26 C
• Air velocity – 0.25 m/s
• Relative humidity – 30-70 % 03/14/2025
Heating versus cooling load calculations
9
Heating load calculations are carried out to estimate the
heat loss from the building in winter so as to arrive at
required heating capacities of various AC equipment.
Cooling load calculation is carried to estimate the heat
gained by the building in summer, and to estimate the
capacity that will be required by various AC equipment.
During winter months the peak heating load occurs before
sunrise and the outdoor conditions do not vary
significantly throughout the winter season.
03/14/2025
Cont’d
10
The heat load calculations are carried out assuming
I. Steady state conditions (no solar radiation and steady
outdoor conditions) and
II. neglecting internal heat sources
But for estimating cooling loads, one has to consider the
unsteady state processes, as the peak cooling load occurs
during the day time and the outside conditions also vary
significantly throughout the day due to solar radiation
03/14/2025
Solar radiation
11
For any building there exists a balance point at which the solar
radiation (Qsolar) and internal heat generation rate (Qint) exactly
balance the heat losses from the building. i.e.
UA =product of overall heat transfer coefficient and heat transfer area of the building
Tin =required indoor temperature
Tout =outdoor temperature
•From the above equation, the outside temperature at balanced condition (T out,bal)
•Hence (outdoor temperature is greater) cooling is needed.
heating is needed
no need of heating or cooling
•For residential buildings (with fewer internal heat sources), the balanced outdoor temperature may vary
from 10 to 18oC
•For commercial buildings with large internal loads and relatively smaller heat transfer areas, the
balanced outdoor temperature can be as low as 2oC,
03/14/2025
Example
12
A building has a U-value of 0.5 W/m2.K and a total exposed surface
area of 384 m2. The building is subjected to an external load (only
sensible) of 2 kW and an internal load of 1.2 kW (sensible). If the
required internal temperature is 25oC.
State whether a cooling system is required or a heating system is
required when the external temperature is 3oC.
How the results will change, if the U-value of the building is
reduced to 0.36 W/m.K?
03/14/2025
13
03/14/2025
Cooling Load
14
It is the thermal energy that must be removed from the space in
order to maintain the desired comfort conditions
HVAC systems are used to maintain thermal conditions in comfort
range.
The purpose of load calculation is to determine the size of the air
conditioning and refrigeration equipment required to maintain the
inside design conditions
The heat gain may be from solar radiation and/or internal gains
such as people, lights and business machines.
03/14/2025
Cooling load calculations methods
15
load calculations involve a systematic and stepwise procedure that
takes into account all the relevant building energy flows
variety of methods ranging from simple rules-of-thumb to complex
Transfer Function Methods are used in practice to arrive at the
building loads
More accurate load estimation methods involve a combination of
analytical methods and empirical results obtained from actual data
03/14/2025
Con’t…. 16
These methods include:
Cooling Load Temperature Difference (CLTD/CLF) &
Solar Heat Gain Factor (SHGF)
Transfer Function Method (TFM)
These are used large commercial or institutional buildings b/c
expensive and time consuming
Hence ASHRAE suggests different methods based on type
applications
03/14/2025
Space Characteristics for cooling load
17
Orientation
Size and shape
Construction material
Windows, doors, openings
Surrounding conditions
Ceiling
Occupants (activity, number, duration)
Appliances (power, usage)
Air leakage (infiltration or exfiltration)
Lighting (W/m2)
03/14/2025
Components of cooling load for AC system
18
1. Sensible heat gain:
Heat received from solar radiation: through glasses, windows, doors, or walls
Heat flow to rooms due to temp difference b/n inside and out side, by
conduction through envelops (exterior walls, floors, ceiling, doors, windows
and by infiltration air) called external load.
Heat conducted through interior partitions from rooms in the same buildings
w/h are not conditioned
Heat given off by lights, monitors, machineries, cooking operations,
industrial processes and heat gained from occupants are called internal
loads. 03/14/2025
19
2. Latent heat gain (addition of water vapor to space)
Heat gained due to moisture in outside by infiltration
Heat gained due to condensation of moisture from occupants
Heat gained from processes like cooking food
Heat gained due to moisture passing directly in to the
conditioned space
the total heat load to be removed by AC is the sum of sensible
and latent heat loads
03/14/2025
Components of Cooling Load
20
03/14/2025
Cooling Load Components
21
roof
lights partition
people equipment
infiltration wall
glass solar
glass
conduction
exterior
wall
floor
03/14/2025
Sensible and Latent Gains
22
cooling load components sensible latent
load load
conduction through roof, walls, windows,
and skylights
solar radiation through windows, skylights
conduction through ceiling, interior
partition walls, and floor
people
lights
equipment/appliances
infiltration
ventilation
system heat gains
03/14/2025
Assumptions behind design cooling load
23
1. Design outside conditions are selected from a long-term
statistical database
2. The load on the building due to solar radiation is estimated for
clear sky conditions
3. The building occupancy is assumed to be at full design capacity
4. All building equipment and appliances are considered to be
operating at a reasonably representative capacity.
03/14/2025
Cont…
24
• In some buildings it may be possible to maintain a comfortable
environment with mechanical ventilation.
• Since air conditioning is both expensive to install and maintain, it
can be reduced by careful building design and by utilising methods
such as:
o window blinds or shading methods
o heat reflecting glass
o Open able windows
o higher ceilings
o smaller windows (glasses) on solar facing direction
o Orientation of building
o alternative lighting schemes
03/14/2025
Cooling Load Reduction Techniques
03/14/2025
Cooling load Estimation
26
1.Estimation of External Loads
a) Heat transfer through opaque surfaces : sensible heat transfer
through opaque or envelopes surfaces such as walls, roof, floor,
doors etc
CLTD is the cooling load temperature difference, For sunlight
surfaces, it is to be obtained from the CLTD tables
For surfaces which are not sunlight ,CLTD value is simply equal
to the difference between the design outdoor and indoor dry bulb
temperatures, Tout-Tin
03/14/2025
Con’t…
27
b) Heat transfer through fenestration (orientation)
Where :
Aunshaded = the area exposed to solar radiation,
SHGFmax = the maximum Solar Heat Gain Factor
SC = Shading Coefficient, respectively and
CLF = Cooling Load Factor w/h can be given in table
03/14/2025
Cooling Load Factor (CLF) for glass with interior shading and
located in north latitudes (ASHRAE)
28
03/14/2025
Estimation of external loads…..
c) Heat transfer due to infiltration: consists of both sensible as
29
well as latent components w/h are given by
where ACH is the number of air changes per hour and V is the gross volume of
the conditioned space in m3. Normally the ACH value varies from 0.5 ACH for
tight and well-sealed buildings to about 2.0 for loose and poorly sealed buildings
or
where A is the effective leakage area of the cracks, C
is a flow coefficient,0.4 ≤ n ≤ 1.0, ΔP= (Po-Pi)
03/14/2025
d) Miscellaneous external loads
30
If the cooling coil has a positive by-pass factor (BPF > 0), then,
some amount of ventilation air directly enters the conditioned
space, in which case it becomes a part of the building cooling load.
In this case
in the following equation can be replaced by
BPF
Where
is the ventilation rate and BPF is the by-pass factor of the cooling
coil.
03/14/2025
2. Estimation of internal loads
31
The internal loads consist of load
due to occupants,
due to lighting,
due to equipment and appliances and
due to products stored or
processes being performed in the conditioned space.
03/14/2025
a) Load due to occupants
32
consists of both sensible and latent heat components
Total heat gain, sensible heat gain fraction from occupants
03/14/2025
b) Load due to lighting:
33
The usage factor accounts for any lamps that are installed but are
not switched on at the time at which load calculations are
performed.
The ballast factor takes into account the load imposed by ballasts
used in fluorescent lights. A typical ballast factor value of 1.25 is
taken for fluorescent lights, while it is equal to 1.0 for incandescent
lamps.
03/14/2025
c) Internal loads due to equipment & appliances:
34
May add both sensible as well as latent loads to the conditioned
space
03/14/2025
d)Load on the system due to ventilated air & leakage
35
sensible and latent loads due to ventilation, leakage losses in the
return air ducts and heat added due to return air fan should be
taken in to account to calculate cooling capacity (if any)
is the latent heat of vaporization of water &
X is the by-pass factor
03/14/2025
Cooling capacity of the system
36
Total sensible load on the coil
Total latent load on the coil
Required cooling capacity
03/14/2025
NB: 37
While determining the cooling capacity a suitable safety
factor is normally used in the end to account for uncertainties
in occupants, equipment, external infiltration, external
conditions etc.
03/14/2025
Heating load calculations
38
Assumptions
steady state conditions for estimating the building heating loads
the internal heat sources are neglected
Then the procedure for heating load calculations becomes fairly
simple
One has to estimate only the sensible and latent heat losses from
the building walls, roof, ground, windows, doors, due to
infiltration and ventilation.
03/14/2025
39
Example 2
An air conditioned room that stands on a well ventilated basement
measures 3 m wide, 3 m high and 6 m deep. One of the two 3 m walls
faces west and contains a double glazed glass window of size 1.5 m by
1.5 m, mounted flush with the wall with no external shading. There are
no heat gains through the walls other than the one facing west.
From the information given below Calculate
a. Sensible heat gain, on the room
b. Latent heat gain on the room
c. total heat gain on the room,
d. room sensible heat factor and
e. The required cooling capacity
03/14/2025
40
03/14/2025
41
03/14/2025
42
03/14/2025
43
03/14/2025
44
03/14/2025
45
Thank You….!!!