Chapter 3
Chapter 3
As stated earlier, due to the large current resulting from the voltage they
handle (typically 750V for DC traction and 200kV for HVDC systems) and
subsequently huge amount of energy dissipation in HVDC systems, the
requirements and concept of HVDC breaker is different from that of low voltage
DC breaker.
Protection algorithms for low
voltage DC systems
• In general, DC circuit breakers will rely on trip signals from relays in
order to operate. These relays rely on measured electrical quantities
(voltages and currents) on the system that indicates whether a fault
has occurred. Some existing protection algorithms used for DC
traction applications include:
3.3.1 Direct – acting (or instantaneous)
overcurrent protection
• This provides protection against overloads as well as high speed
operation during high current faults. However, the major draw-back of
this technique is that it cannot discriminate between normal load
conditions and low level or remote faults. For example, the train
starting current can be significantly larger than the fault current
resulting from a long distance remote fault. (Figure 3.4). This can
result in faulty relay discrimination, hence leading to spurious trips.
However, this situation is rare in practice, but measures must be taken
should they occur,
3.3.2 Rate of rise (di/dt) protection
the fault point and the relay by measuring the loop voltage and the current
to the line length, the distance to the fault, 𝑙𝑓 can be estimated. As shown in
formed following the occurrence of a fault. Since impedance is proportional
measured at the local terminal. Considering Figure 3.8, the arbitrary faults 𝐹𝑖1, 𝐹𝑖2 and 𝐹𝑖3 are
making it very fast in operation. The only information required are the voltage and current signals
R, 𝐹𝑒1, 𝐹𝑒2 are external faults. As per distance protection, the corresponding fault distances are
internal faults and hence falls within the protection zone of the relay, R. However, with respect to relay
reverse faults (𝐹𝑒1 as shown) while the concept of zoning is used to provide
utilising the reactive component is usually used to provide discrimination for
Figure 3.15, the 𝑑𝑖/𝑑𝑡 with respect to the relay is positive for fault F1
example, considering a section of a transmission network shown in
the ∆𝑽 protection, but a fault is detected when there is an incremental change in the
This is like
current and as such generally referred to as overcurrent protection. They are widely
used in low voltage DC systems such as DC traction systems in conjunction with di/dt.
Its application to DC grid has been proposed and is reported in[67]. A similar
approach utilising fault current limiter (FCL) has also been reported in [79
3.5.7 Travelling wave based protection
principle for HVDC systems
• The principle is the same as those used for HVAC systems. Proposals regarding travelling wave
based protection principles for HVDC systems is reported in[80]–[86]. A proposal regarding
the application of travelling wave protection for DC grids has been reported in [87], [88].
However, a major issue when adopted for the protection of DC grid is that it relies on
reflections (or multiple reflections) between the fault and the relay terminals thereby
incurring delay. These include the philosophies used in the traditional HVAC systems as well as
those proposed for HVDC systems including HVDC grids. However, the studies carried out
show that the reliance on successive reflection of the travelling wave components at the relay
terminal for fault identification imposed some limitations on its use for DC grid protection.
The reliance on complex DSP techniques would also imposed some computational burden as
well as incurring delays. This is because the wave propagation delay time may be longer than
the time required to detect and clear the fault. This is a major issue to be considered when
deploying travelling wave based protection principle for application to DC grids. Therefore,
new travelling wave based protection (TWBP) techniques are required to be designed and
developed for application to DC grids.
3.5.8 Boundary Protection
This is similar to that proposed for HVAC system where the frequency character of the fault generated
transient are extracted for fault identification. A two terminal HVDC line protection technique utilising
this concept has been reported in [60], [61]. However, none of such technique has been reported for DC
grid protection. 3.6 Options and Strategies for DC grid protection
3.6.1 “Unit” Versus “non-unit” based protection
principles Generally, the protection techniques discussed above fall under two categories
- unit and non-unit based. Protection schemes relying on information from the local end terminal are
referred to as non-unit protection scheme while those relying on information from both the local end
and remote end terminals are referred to as unit protection scheme. The information here referred to
the current and voltage superimposed signal recorded at the relaying terminal following fault inception.
Distance protection, overcurrent protection, under voltage, di/dt and dv/dt are examples of non-unit
type of protection. An advantage of the non-unit protection scheme is that they do not require
communication channel and as such no communication delay. Examples of unit protection are current
differential protection and polarity identification technique. For a protection to be reliable and fast in
operation and considering the time requirement for DC grid protection, the primary or main protection
must be a non-unit type protection technique. However, the secondary or back-up protection could be
unit – type protection.
3.6.2 Transient and steady-state based
protection principles
• Protection techniques and principles could also be classified as either steady state based or
transient based. Those protection techniques which are based on the character of the
transient components of the fault generated signal (voltage or/and current) are regarded as
transient based protection; whereas those based on the character of steady state
components of the fault generated signals are referred to as steady state based protection.
The traditional distance protection techniques applicable to AC systems is an example of
steady state based protection technique whereas travelling wave and polarity identification
technique, current and voltage derivative protection techniques are regarded as transient
based. Conventional HVAC systems uses the steady state based protection algorithm such as
the distance protection, thereby given the protection system enough time to detect the fault.
However, in DC system the fault must be detected and cleared during the transient state.
These parameters that vary with distance during the transient state such as the inductance
could be used, thereby paving the way for a distance protection strategy. An attempt was
made to relate the initial rate of rise of the fault current with the loop inductance, thereby
estimating the fault distance, the findings are presented in section 4
3.6.3 “Blocking” versus “non-blocking”
HVDC converters
• As discussed in section 2.5.3, MMC based HVDC are the most
preferred converter topology for application to DC grid due to its
technical advantages compared to other VSCs. The protection
principles for DC grid can either be archived using either of the two
MMC submodules configurations, the half bridge (or non-blocking
converter) or the full bridge (blocking converters) HVDC
converters[19], [68], [69]. Generally, the nonblocking converters are
not able to block fault currents whereas the blocking converter does.
• “Non-blocking” HVDC converters: In this technique, it has been
proposed to place DC circuit breakers at both ends of the DC overhead lines
or cables[69]. During DC side faults, the faulty segment is isolated without
interrupting the operation of the remaining converters connected to the
healthy section of the grid (Figure 3.19a). The major advantage of this
technique is that it does not require a total shut down of the entire grid.
Furthermore, active power transfer can be restored immediately following
fault clearance “Blocking”
HVDC converters: This involves blocking the converters using the full
bridge MMC HVDC model and thereafter isolating the faulty section using fast
mechanical switches during DC side faults in any of the sections (Figure
3.19b). An advantage of this technique is that the converters can provide
voltage support throughout the contingency. However, a major disadvantage
of this approach is that a considerable amount of time is taken to re-establish
the active power transfer on the healthy section of the DC grid [68].
3.6.4 Use of AC side Circuit Breakers
• This involves tripping the AC side circuit breakers at all converter stations and thereby
disconnecting the whole grid once a DC line /cable fault is detected. (Figure 3.20). The
converters are later connected to the grid when the faulty sections have been isolated
using fast DC switches or isolators. The major disadvantages with this method are that
the power flows in the healthy sections are disrupted. Furthermore, this technique
requires an extended period in re-establishing the reactive power of the converters
and the active power transfer on the healthy part of the DC network once the faulty
section is isolated. Clearly, the use of DC side circuit breakers is the most desirable for
the protection of DC grids and as such the protection technique adopted in this
research assumes a DC side breaker located at the ends of the lines/cables. Generally,
and in some cases fault current will be installed alongside DC breakers as part of the
protection strategies for the future DC grid. This will help to reduce the di/dt during
DC side short circuit conditions which will give the breaker time to operate