Module-2
Module-2
i) Hysteresis loss :-
Hysteresis loss due to repeated magnetization and
demagnetization in transformer core. The energy is lost in each
hysteresis cycle.
During magnetization and demagnetization ,due to hysteresis
effect some energy losses in the core takes place called
hysteresis loss
ii) Eddy current losses():-
a phenomenon that occurs when a conductor is exposed to a varying magnetic field, resulting in
the generation of circulating currents within the conductor.
In transformer, the leakage magnetic flux linked with the conducting parts like steel core or iron
body of transformer, which will result in induced emf in those parts, causing small circulating
current in them.
This current is called eddy current, due to these eddy current some energy will be dissipated in
the form of heat
Efficiency of transformer:
Efficiency of transformer given by;
𝑊0
SC-Test
o As secondary is shorted, its resistance is very very small and
on rated voltage it may draw very large current. Such large
current can cause overheating and burning of the
transformer.
o To limit this short circuit current, primary is supplied with
low voltage which is just enough to cause rated current to
flow through primary which can be observed on an
ammeter.
o The low voltage can be adjusted with the help of variac.
Hence this test is also called low voltage test or reduced
voltage test. The wattmeter reading as well as voltmeter,
ammeter readings are recorded.
o Now the currents flowing through the windings are rated 𝑊 𝑠𝑐
currents hence the total copper loss is full load copper loss.
Now the voltage applied is low which is a small fraction of
the rated voltage. The iron losses are function of applied
voltage.
• It can be noted that there is a phase shift of 30 between the phase voltages and line
voltages on both primary and secondary side.
• The line voltages on both sides and the primary voltages are in phase with each other.
Advantages:
1. Due to star connection, phase voltage is 1/√3 times that of line voltage. Hence less number of turns
are required. Also the stress on insulation is less. This makes the connection economical for small
high voltage purposes.
2. phase current is same as line current. Hence windings have to carry high currents. This makes cross
section of the windings high. Thus the windings are mechanically strong and windings can bear
heavy loads and short circuit.
3. There is no phase shift between the primary and secondary voltages.
4. As neutral is available, it is suitable for three phase, four wire system.
Disadvantages:
5. If the load on the secondary side is unbalanced then the performance of this connection is not
satisfactory then the shifting of neutral point is possible. To prevent this, star point of the primary is
required to be connected to the star point of the generator.
6. Even though the star or neutral point of the primary is earthed, the third harmonic present in the
alternator voltage may appear on the secondary side. This causes distortion in the secondary phase
voltages.
2. Delta/Delta
1. In order to get secondary voltage as sinusoidal, the magnetizing current of transformer must
contain a third harmonic component. The delta connection provides a closed path for circulation of
third harmonic component of current. The flux remains sinusoidal which results in sinusoidal
voltages.
2. Due to delta connection, phase voltage is same as line voltage hence windings have more number
of turns. But phase current is 1/√3 times the line current. Hence the cross section of the windings
is very less. This makes the connection economical for low voltage transformers.
3. Even if the load is unbalanced the three phase voltages remain constant. Thus it allows unbalanced
loading also.
4. The important advantage with this type of connection is that if there is bank of single phase
transformers connected in delta-delta fashion and if one of the transformers is disabled then the
supply can be continued with remaining two transformers of course with reduced efficiency.
Disadvantages:
5. Due to absence of neutral point, this type is not suitable for three phase, four wire system.
3. Star/Delta
• In this type of connection, both the primary
connected in star fashion while secondary windings
are connected in delta fashion.
• This connection commonly employed at substation
end of the transmission line.
• The main use of this connection is to step down the
voltage.
• Neutral available on primary side is grounded.
• It can be seen that there is phase difference of 30
between primary and secondary voltages.
1. The primary side is star connected. Hence fewer number of turns are required. This makes the connection
economical for large high voltage step down power transformers.
2. The neutral available on the primary can be earthed to avoid distortion.
3. Large unbalanced loads can be handled satisfactorily.
Disadvantage
4. In this type of connection, the secondary voltage is not in phase with the primary. Hence it is not possible
to operate this connection in parallel with star-star or delta-delta connected transformer
zigzag connection
• The zigzag connection of tranformer is also called the
interconnected star connection. This connection has
some of the features of the Y and the ∆ connections,
combining the advantages of both.
• The zigzag transformer contains six coils on three cores.
The first coil on each core is connected contrariwise to
the second coil on the next core. The second coils are
then all tied together to form the neutral and the phases
are connected to the primary coils.
• One coil is the outer coil and the other is the inner coil.
Each coil has the same number of windings turns (Turns
ratio=1:1) but they are wound in opposite directions.
• Typical zig-zag transformers do not have a
secondary winding and exhibit useful winding
connections that only allow the flow of currents
that are in phase through the neutral. They may
be three-phase transformers or a bank of three
single-phase units.
• The zig-zag arrangement is the most common
because of its lower cost and the ability of the
iron core design to limit the flow of the triple-
harmonic fluxes. Zig-zag transformers are
smaller in size than wye-delta transformers for
the same zero-sequence impedance.
Thank you
1.23 1.24