power system 1 unit 5
power system 1 unit 5
POWER SYSTEM 1
UNIT 5
Fault Analysis & Protection Systems
From:
Dr. Monika Vardia
Associate Professor
Method of Symmetrical Components
When the system is unbalanced the voltages, currents
and the phase impedances are in general unequal.
The method of symmetrical components simplified
the problems of the unbalanced three-phase system.
The balanced set of components can be given as a
positive sequence component, negative sequence
component, and zero phase sequence component.
The phase sequence of the positive component is Va,
Vb and Vc and the phase sequence of negative
components is Va, Vc, and Vb.
Cont....
The positive sequence component of the
unbalanced three phase system
• In positive phase sequence component, the set of three
phasors are equal in magnitude, spaced 120° apart from each
other and having the same phase sequence as the original
unbalanced phasors.
Negative Phase Sequence Component
In negative phase sequence component, the set of the
three phasors are equal in magnitude, spaced 120° apart
from each other and having the phase sequence opposite to
that of the original phasors. The negative phase sequence is
shown in the figure below
Zero Phase Sequence Components
• In zero phase sequence components, the set of three phasors
is equal in magnitude to zero phase displacement from each
other. The zero phase sequence component is shown in the
figure below.
• The three phase balanced system is a special case of a general
three-phase system in which zero and negative sequence
components are zero.
Symmetrical & Unsymmetrical Faults
• Normally, a power system operates under balanced
conditions. When the system becomes unbalanced
due to the failures of insulation at any point or due
to the contact of live wires, a short–circuit or fault,
is said to occur in the line.
• Faults may occur in the power system due to the
number of reasons like natural disturbances
(lightning, high-speed winds, earthquakes),
insulation breakdown, falling of a tree, bird
shorting, etc.
Cont....
Faults that occurs in transmission lines are
broadly classified as
Symmetrical faults
Unsymmetrical faults
Symmetrical faults
In such types of faults, all the phases are short-circuited to each
other and often to earth.
Such fault is balanced in the sense that the systems remain
symmetrical, or we can say the lines displaced by an equal angle (i.e.
120° in three phase line).
It is the most severe type of fault involving largest current, but it
occurs rarely.
Unsymmetrical faults
• Unsymmetrical faults involve only one or two
phases.
• In unsymmetrical faults the three phase lines
become unbalanced.
• Such types of faults occur between line-to-
ground or between lines.
• An unsymmetrical series fault is between
phases or between phase-to-ground.
fault in the three phase system can be
classified as;
• Single line-to-ground fault (LG).
• Line-to-line fault (LL).
• Double Line-to-ground fault (LLG).
• Three-phase short circuit fault (LLL).
• Three-phase-to-ground fault (LLLG).
Single Line-To-Ground Fault
Schematic Picture of A Single Line-To-Ground Fault
Sequence Connection For A Double-Line-To-
Ground Fault Line-Line Fault
Line to Line Fault
Cont....
Neutral Grounding
• In neutral grounding system, the neutral of the system or
rotating system or transformer is connected to the
ground.
• The neutral grounding is an important aspect of power
system design because the performance of the system
regarding short circuits, stability, protection, etc., is
greatly affected by the condition of the neutral.
A three phase system can be operated in two possible ways
• With ungrounded neutral
• With a grounded neutral
Ungrounded Neutral System
• In an ungrounded neutral system, the neutral is not
connected to the ground.
• In other words, the neutral is isolated from the ground.
• Therefore, this system is also known the isolated neutral
system or free neutral system .
Grounded System
• In neutral grounding system, the neutral of the
system is connected to the ground.
• Because of the problems associated with
ungrounded neutral systems, the neutrals are
grounded in most of the high-voltage systems.
Advantages of neutral grounding
• Voltages of phases are limited to the line-to-
ground voltages.
• Surge voltage due to arcing grounds is
eliminated.
• The overvoltages due to lightning discharged to
ground.
• It provides greater safety to personnel and
equipment.
• It provides improved service reliability.
Method Of Neutral Grounding
• The methods commonly used for grounding
the system neutral are