Electrical Machines & Power Utilization - Transformer - 6!01!2021
Electrical Machines & Power Utilization - Transformer - 6!01!2021
• Let
• ϕm be the maximum value of flux in Weber
• f be the supply frequency in Hz
• N1 is the number of turns in the primary winding
• N2 is the number of turns in the secondary winding
• Flux changes from + ϕm to – ϕm in half a cycle of 1/2f
seconds.
• By Faraday’s Law
• Let E1 be the emf induced in the primary winding
• Where Ψ = N1ϕ
• Peak Value
• The maximum value attained by an alternating
quantity during one cycle is called its Peak
value
• Average Value
• The average of all the instantaneous values of an alternating
voltage and currents over one complete cycle is
called Average Value.
• R.M.S Value
• That steady current which, when flows through a resistor of
known resistance for a given period of time than as a result
the same quantity of heat is produced by the alternating
current when flows through the same resistor for the same
period of time is called R.M.S.
• Let i1, i2, i3,………..in be the mid ordinates
• Then the heat produced in
Transformer on No Load Condition
• The phase difference between V1 and I1 gives the power factor angle
ϕ1 of the primary side of the transformer.
• The power factor of the secondary side depends upon the type of
load connected to the transformer.
• If the load is inductive, the power factor will be lagging, and if the
load is capacitive, the power factor will be leading. The total
primary current I1 is the vector sum of the currents I0 and I1’. i.e.
Steps to draw the phasor diagram
• Take flux ϕ,
• Induces emf E1 and E2 lags the
flux by 900.
• The component of the applied
voltage to the primary equal and
opposite to induced emf in the
primary winding. E1 is
represented by V1’.
• Current I0 lags the voltage V1’ by
900.
• The power factor of the load is
lagging. Therefore current I2 is
drawn lagging E2 by an angle ϕ2.
Steps to draw the phasor diagram
• The resistance and the leakage
reactance of the windings result in a
voltage drop, and hence secondary
terminal voltage V2 is the phase
difference of E2 and voltage drop.
• V2 = E2 – voltage drops
I2 R2 is in phase with I2 and I2X2 is
in quadrature with I2.
• The total current flowing in the
primary winding is the phasor sum
of I1’ and I0.
• Primary applied voltage V1 is the
phasor sum of V1’ and the voltage
drop in the primary winding.
Steps to draw the phasor diagram
• Current I1’ is drawn equal and opposite
to the current I2
• V1 = V1’ + voltage drop
I1R1 is in phase with I1 and I1XI is in
quadrature with I1.
• The phasor difference between V1 and
I1 gives the power factor angle ϕ1 of the
primary side of the transformer.
• If the load is inductive, the power factor
will be LAGGING, and if the load is
capacitive, the power factor will be
LEADING. Where I1R1 is the
resistive drop in the primary windings
I2X2 is the reactive drop in the
secondary winding
Equivalent Circuit of Transformer
Equivalent Circuit of Transformer
• helpful in the pre-determination of the behavior of the
device under the various condition of operation.
• This calculation requires equivalent circuit of transformer
referred to the primary or equivalent circuit of transformer
referred to secondary sides respectively.
• parameter during installing a transformer in an existing
electrical power system.
• Percentage impedance of different power transformers
should be properly matched during parallel operation of
power transformers
Equivalent Circuit When all the Quantities
are Referred to Primary side
• to draw the equivalent circuit
of the transformer all the
quantities are to be referred to
the primary as shown in the
figure
• the equivalent circuit of a
transformer having the
transformation ratio K = E2/E1
• Or 1/K=E1/E2
• The secondary
Equivalent Circuit When all the Quantities
are Referred to Primary side
• Secondary resistance referred
to the primary side is given as
•
Equivalent Circuit when all the quantities are
referred to Secondary side
• Primary resistance referred to
the secondary side is given as
• Points to be noted:
The value of the terminal voltage V2 is approximately
constant.
Thus, transformer efficiency depends upon the load current
I2.
transformer efficiency will be maximum if the denominator
with respect to the variable I2 is equal to zero.
Maximum Efficiency Condition of a Transformer
• The open circuit and short circuit test are performed for
determining the parameter of the transformer like their
efficiency, voltage regulation, etc.
• These tests are performed without the actual loading and
because of this reason the very less power is required for the
test.
• The open circuit and the short circuit test gives a very
accurate result as compared to the full load test.
Open Circuit Test Circuit diagram
Open circuit test
• The purpose of the open-circuit test
is to determine the no-load current
and losses of the transformer
• because of which their no-load
parameters are determined.
• This test is performed on the
primary winding of the
transformer.
• The wattmeter, ammeter and the
voltage are connected to their
primary winding.
• The nominal rated voltage is
supplied to their primary winding
with the help of the ac source.
Open circuit test
• The secondary winding of the
transformer is kept open, and the
voltmeter is connected to their
terminal.
• This voltmeter measures the
secondary induced voltage.
• The value of no-load current is very
small as compared to the full rated
current.
• The value of no-load current is very
small as compared to the full rated
current.
• The value of no-load current is very
small as compared to the full rated
current.
Calculation of open-circuit test
• Working component Iw is
Calculation of open-circuit test
• Magnetizing component is
Calculation of open-circuit test
• From phasor