PURGE PERMISSIVES
All HFO nozzle valves closed All pulverisers OFF All feeders OFF No MFT condition present All scanners senses no flame All Auxiliary Air dampers modulating Both PA fans OFF All Mill HAGs closed Air flow more than 30% and less than 50% HFO trip valve is closed
19 January 2012
TO FSSS
Both FD fans OFF Both ID fans OFF. Inadequate water wall circulation for more than 5 seconds. Loss of Reheat Protection for greater than 10 seconds. All BFPs tripped. Drum level very high for more than 10 seconds (2/3 logic) Drum level very low for more than 10 seconds (2/3 logic) Furnace pressure very high (2/3 logic) Furnace pressure very low (2/3 logic) Loss of all fuel. All feeders OFF and loss of AC Supply to the elevation in service. Unit flame failure. Loss of Unit Critical Power for more than 2 seconds Both Secondary APHs OFF. Loss of 220 V DC Supply for more than 2 seconds. Air flow less than 30% and boiler load not greater than 30%. Manual Emergency trip.
19 January 2012 PMI Revision 00 3
Both FD fans OFF Both ID fans OFF Inadequate water wall circulation for more than 5 seconds Loss of Reheat Protection for greater than 10 seconds All BFPs tripped Drum level very high for more than 10 seconds (2/3 logic) Drum level very low for more than 10 seconds (2/3 logic) Furnace pressure very high (2/3 logic) Furnace pressure very low (2/3 logic) Loss of all fuel All feeders OFF and loss of AC Supply to the elevation in service Unit flame failure Loss of Unit Critical Power for more than 2 seconds Both Secondary APHs OFF Loss of 220 V DC Supply for more than 2 seconds Manual Emergency PB trip Air flow less than 30% and boiler load not greater than 30%
19 January 2012 PMI Revision 00 4
MFT RELAY
Purpose:
Protection Delay:
0 sec INSTANT.
Protection Check:
19 January 2012
PMI Revision 00
Purpose:
Protection Delay:
0 sec INSTANT.
Protection Check:
Simulate the signals from FD Fans Electrical Switchgear
19 January 2012
PMI Revision 00
Purpose:
Backup protection to trip remaining equipment (eg. PA Fans) 0 sec INSTANT.
Protection Check:
Keep oil manual isolating valves in any one elevation any one corner (done by OPN), simulate status of manual valve (done by C&I), then give sequence start command to that corner Revision 00 19 January 2012 PMI
Protection Delay:
0 sec INSTANT.
All Elevations A to K voted NO Flame Eg. Elevation A voted no flame means (AA 3/4 fireball scanners sense no flame AND AB 3/4 fireball scanners sense no flame AND AB 2/4 oil guns not proven in service) OR Feeder A Not Proven for 2 sec Stop firing under unstable flame fireball conditions
Protection Check:
19 January 2012
Purpose:
Purpose:
19 January 2012
PMI Revision 00
10
19 January 2012
PMI Revision 00
11
Purpose:
Protection Delay:
Protection Check:
Actual (decrease feed water flow slowly until level reaches trip limit).
19 January 2012
PMI Revision 00
12
Purpose:
Anticipatory protection for Drum Level Very Low To prevent economizer tubes starvation
19 January 2012
PMI Revision 00
13
Purpose:
Protection Delay:
5 sec.
Protection Check:
Actual.
19 January 2012 PMI Revision 00 14
Logic:
All BCW OFF (OR) 2/3 running BCW DP < 0.68 ksc
Purpose:
Preventing damage to waterwall tubes due to insufficient cooling flow/circulation
Protection Delay:
5 sec.
Protection Check:
Equalizing DP transmitters to simulate DP low.
19 January 2012
PMI Revision 00
15
19 January 2012
PMI Revision 00
16
Logic:
Total Air Flow (Primary Air + Secondary Air) < 30% of full load air flow (30% of 1800 Tph = 540 Tph)
Purpose:
Ensuring absolute minimum required quantity of air flow even during startup Preventing localized accumulation of unburnt oil during startup
Protection Delay:
0 sec - INSTANT.
Protection Check:
Actual.
19 January 2012
PMI Revision 00
17
19 January 2012
PMI Revision 00
18
Purpose:
Protection Delay:
PMI Revision 00
19
19 January 2012
PMI Revision 00
20
19 January 2012
PMI Revision 00
21
Purpose:
If 24V fails, the processors cannot execute any logic, leading to unsafe condition
Protection Delay:
0 sec INSTANT.
Protection Check:
By 24V breaker simulation in MFT panel.
19 January 2012
PMI Revision 00
22
Purpose:
If 220V fails, backup protection for 24V failure will be unavailable.
Protection Delay:
2 sec.
Protection Check:
By 220V breaker in MFT panel.
19 January 2012
PMI Revision 00
23
Logic:
If any 2 MFT processors out of 3 go into failed state, or if any 2 MFT processors go into frozen output state, it will initiate MFT protection. This ensures that at least 2 processors are in healthy condition at any point of time when boiler is in service. Failure of processors leads to unsafe condition 0 sec - INSTANT.
Purpose:
19 January 2012
PMI Revision 00
24
Logic:
If any 2 MFT processors out of 3 stop communicating with the Ethernet network (redundant net-A and net-B), they will initiate MFT protection This ensures that at least 2 processors are communicating properly at any point of time when boiler is in service. Failure of communication leads to malfunction of protection circuit 0 sec - INSTANT.
Purpose:
Protection Delay:
Protection Check:
By actually isolating network connections of the processors.
19 January 2012 PMI Revision 00 25
Purpose:
This facility allows the operation desk engineer to directly trip the boiler in case of any operational emergency eg. Boiler Tube Leakage, Furnace excessive Clinkering, HFO oil leakage during startup, turbine related emergencies etc.
0 sec - INSTANT.
Boiler not firing fuel for 5 min (MFT may or may not be reset) If furnace pressure very high > 150 mmwc OR very low < -175 mmwc (AND) Air Flow > 30% THEN TRIP all ID Fans and FD Fans This protection safeguards furnace against furnace pressure very high OR very low when boiler is NOT firing.
Protection Check:
19 January 2012 PMI Revision 00 27
Purpose:
Protection Delay:
Protection Check:
19 January 2012
19 January 2012
PMI Revision 00
29
19 January 2012
PMI Revision 00
30
Blade pitch position minimum. Discharge damper fully closed. Lube oil pressure adequate. Control oil pressure adequate. Oil tank level normal. Bearing temperature not high. One ID Fan running AND other FD fan not running. OR Both ID Fan running
19 January 2012
PMI Revision 00
31
TRIPS
Fan bearing temperature very high Post purge furnace pressure very high/ very low Outlet damper fail to open in set time (3 min) No ID fan running or one ID fan and one FD fan already in service.
19 January 2012
PMI Revision 00
32
PA FAN
START PERMISSIVES Blade pitch minimum Lube oil pressure adequate Control oil pressure adequate Bearing temp. not high Discharge damper closed. Lube oil tank level adequate No MFT & Cold air damper closed At least one FD fan is running and PAPH A/B in service & respective air inlet/ outlet dampers are open 19 January 2012 PMI Revision 00 33
TRIPS Fan bearing temperature very high. Trip from FSSS (MFT). Discharge damper fails to open.
19 January 2012
PMI Revision 00
34
ID FAN
START PERMISSIVES Hyd. coupling Scoop position minimum. Inlet guide vane position minimum. Bearing temperature not high. Oil temp. and oil level in Hyd. coupling OK. Lube oil pressure adequate. Both inlet and outlet dampers closed. Other ID fan not running or Any FD fan running.
19 January 2012
PMI Revision 00
35
TRIP CONDITION Fan/Motor bearing temperature very high. Lube oil pressure very low. Post purge furnace pressure Hi/Low from FSSS. Discharge dampers/ suction damper fail to open within specified time (3 min.) Hydraulic coupling bearing temp. very high Hydraulic coupling oil temp. very high.
19 January 2012
PMI Revision 00
36
PERMISSIVES Discharge valve 1 open. Discharge valve 2 open. Motor cavity temp. not high. Pump cavity suction manifold differential temp. not high. Motor cooling water flow adequate.
19 January 2012 PMI Revision 00 37
TRIPS
Any of the discharge valves not fully open. Motor cavity temp. high (60 deg. C) for more than 5 Sec. Electrical protection trip/ EPB pressed.
19 January 2012
PMI Revision 00
38
19 January 2012
PMI Revision 00
39
19 January 2012
PMI Revision 00
40