Lecture 05 Power Transformers I-3
Lecture 05 Power Transformers I-3
POWER SYSTEMS 1
Lecture 5:
Power Transformers I
Textbook Reading: 3.1, 3.2, 3.3
Lecture Objectives
transformers.
2
Overview
• Transformers
• Core types
3
What is a Transformer?
4
Transformer Use
Practical voltages generated by available generators are around
25kV.
Therefore, transformers are required to step up the voltages for
transmission of power in a more economical way.
The main reason for doing so is that the power losses and
voltage drop associated with line resistances are reduced in
order to make the transfer of power over long distances more
economical.
Then transformers are also used to step down the voltages to
levels that are safe for customers to use.
Transformers are key elements not only in HVAC power
transmission but also in HVDC power transmission systems. 5
Transformer Operation
The AC current that flows in the primary winding of a transformer,
which is constantly changing with time (sinusoidal) produces a
magnetic field.
Through the flux paths, this will be induced across the secondary
winding of the transformer.
This way, electrical energy can be transferred from the primary side
of the transformer to the secondary one without any electrical
connection (isolation).
Power transformers have been loosely grouped into three market
segments based on size ranges:
• Small power transformers: 500 kVA to 7500 kVA
• Medium power transformers: 7500 kVA to 100 MVA
6
• Large power transformers: 100 MVA and above
Transformer Efficiency
The efficiency of the energy
transfer from the primary to
the secondary depends upon
the coupling of the magnetic
field between the two
windings. However, no
matter how good the
coupling is, certain magnetic
lines will not close through
the secondary resulting in
magnetic loss.
The transformer is one of the
most efficient devices of the
power system network. 7
Transformer Core Construction
In order to reduce the magnetic loss, the Laminated
iron core
transformer windings are wound around
an iron core. The reason being that iron
cores concentrate the flux so that better
coupling between the primary and
secondary windings occurs.
The cores are made of laminated iron to Secondary
reduce the effects of eddy currents,
Primary
which are induced into the core material.
The primary and secondary windings are
Laminated
placed next to each other for improved iron core
magnetic coupling as well.
There are two types of transformer: Secondary
Primary
• Closed-core
• Shell-core
The shell core type offers better magnetic
coupling, since the transformer windings
are surrounded by metal on both sides. 8
The Ideal Transformer
core reluctance
10
Ideal Transformer Voltage and Current Relationships (cont.)
Faraday’s law:
Lossless transformer:
13
Real Transformers
• Copper losses
• Hysteresis losses
• Eddy current losses
These losses use real power and therefore reduce transformer
efficiency levels.
14
Transformer Copper Losses
Proper sizing of the winding wire and proper cooling for the
15
B
Time
17
B
19
Transformer Efficiency
core loss.
20
Effect of Leakage Flux
22
Transformer Equivalent Circuit
Using the previous
relationships, we can derive
an equivalent circuit model
for the real transformer:
This model is further
simplified by referring all
impedances to the primary
side:
In power transformers, the
shunt branch draws very little
current when compared to
the load current and therefore
23
can be neglected:
Transformer Ratings
• short circuit test: with secondary shorted, apply voltage to primary to get
open; measure the primary current and losses (the test may also be
done with primary open, applying the rated voltage to the secondary,
measuring the values, then referring them back to the primary side).
25
Transformer Example
A single phase, 100 MVA, 200/80 kV transformer has the following test data:
20 A 200 kV
R jX jX
Gc e jBm e m 10 4 10, 000
S B X m 8
10 10,
625000
16 10 4 S
10
20 A m 26
200kV
27
The Per-Unit System
31
Per-Unit Equivalent Circuits of a Single-Phase
Two-Winding Transformer
32
Per-Unit Solution
2. Solve
equivalent impedance:
ZB = (VB)2/SB
33
Transformer Reactance Per-Unit Change of Base
Examples
A 54 MVA transformer has a leakage reactance or 3.69%. What is the
reactance on a 100 MVA base?
100
X e 0.0369 0.0683 p.u.
54
Transformer reactance is often specified as a percentage, say 10%. This is
a per unit value (divide by 100) on the power base of the transformer.
Example: A 350 MVA, 230/20 kV transformer has a leakage reactance of
10%. What is the p.u. value on a 100 MVA base? What is the value in
ohms (230 kV)?
100 actual quantity
X e 0.10 0.0286 p.u. quantity in per unit
base value of quantity
350
230 2 ZB = (VB)2/SB
0.0286 15.1 34
100
Per-Unit Example
Solve for the current, load voltage and load power in the circuit shown
below using per unit analysis with an SB of 100 MVA, and voltage bases of
8 kV, 80 kV and 16 kV.
ZB = (VB)2/SB Left 8kV 2
ZB 0.64
100 MVA
80kV 2
Z BMiddle 64
100 MVA
IB = VB/ZB = SB/VB 16kV 2 Original Circuit
Z BRight 2.56
100 MVA
To convert back to actual values SGActual 0.2230.8 100 MVA 22.030.8 MVA
just multiply the per unit values 100 MVA
I Middle
B 1250 Amps
by their per unit base: 80 kV
35
I Actual
Middle 0.22 30.8 Amps 275 30.8
actual quantity
quantity in per unit
base value of quantity
36
37
The Three-Phase Per-Unit System
Balanced three-phase circuits can be solved in per-unit on a per-phase
basis after converting ∆-load impedances to equivalent Y impedances.
Base values can be selected either on a per-phase basis or on a three-
phase basis.
Usually three-phase base complex power and line-to-line base voltage are
selected as base values.
3
1. Pick a 3f VA base for the entire system, B S
2. Pick a voltage base for each different voltage level, VB.
Voltages are line to line.
3. Calculate the impedance base:
VB2, LL ( 3 VB , LN ) 2 VB2, LN
Z B 3 1
1
SB 3S B SB
Exactly the same impedance bases as with single phase!
3 1 1
4. Calculate the current base, IB: I
3 S B 3 S B S B I1
B B
3 VB , LL 3 3 VB , LN VB , LN
Exactly the same current bases as with single phase! 38
Three-Phase Per-Unit Example
Solve for the current, load voltage and load power in the circuit of slide 36,
assuming a 3f power base of 300 MVA, and line-to-line voltage bases of
13.8 kV, 138 kV and 27.6 kV (√3 larger than the 1f example voltages). Also
assume the generator is Y-connected so its line-to-line voltage is 13.8 kV.
Convert to per unit as before. Note the system is exactly the same!
Now that the lecture has ended, you should have learned how to:
transformers
41