0% found this document useful (0 votes)
47 views116 pages

TRC 016 en

Uploaded by

ahmed abdoh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views116 pages

TRC 016 en

Uploaded by

ahmed abdoh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 116

Chilled-Water Systems

A Trane Air Conditioning Clinic

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chilled-Water Systems
period one
Types of Water Chillers

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


absorption
water chiller

centrifugal
water chiller
Driving Sources

compressor-driven heat-driven

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Vapor-Compression Cycle
reject heat

D C
condenser
compressor
expansion
device
energy in

evaporator
A B

absorb heat
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Compressor Types

scroll

reciprocating

helical-rotary centrifugal
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Variable-Speed Drives

variable-
speed
drive

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Condenser Types

air-cooled

water-cooled

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Air-Cooled or Water-Cooled

water-cooled
air-cooled

0 tons 500 tons 1,000 tons 1,500 tons 2,000 tons 2,500 tons 3,000 tons
[0 kW] [1,759 kW] [3,517 kW] [5,276 kW] [7,034 kW] [8,793 kW] [10,551 kW]

chiller capacity

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


air-cooled or water-cooled
Maintenance
 Water treatment
 Condenser tube brushing
 Tower maintenance
 Freeze protection
 Makeup water

cooling tower
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
air-cooled or water-cooled
Low-Ambient Operation

air-cooled
chiller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


air-cooled or water-cooled
Efficiency

dry bulb
outdoor temperature

wet bulb

12 12 12
midnight noon midnight
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
air-cooled or water-cooled
Comparison

air-cooled water-cooled
 Lower maintenance  Greater energy efficiency
 Longer equipment life
 Packaged system
 Better low-ambient
operation
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Packaged Air-Cooled Chiller

air-cooled chiller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Remote Evaporator Barrel

condensing unit

remote
evaporator

refrigerant
piping

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Remote Air-Cooled Condenser
air-cooled
condenser

refrigerant
piping

condenserless
chiller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Indoor Air-Cooled Condenser
indoor
air-cooled
condenser
refrigerant
piping

condenserless
chiller
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Absorption Refrigeration Cycle
reject heat
heat energy in
D C
condenser generator

expansion pump
device

evaporator absorber
A
B
absorb heat reject heat
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Absorption Chillers Offer Choice
 Avoid high electric
demand charges
 Minimal electricity
needed during
emergency situations
 Waste heat recovery
 Cogeneration

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Absorption Chiller Types

single-effect double-effect

direct-fired
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Equipment Rating Standards
 Air-Conditioning &
Refrigeration Institute (ARI)
 Standard 550/590–1998:
centrifugal and helical-rotary
water chillers
 Standard 560–1992:
absorption water chillers

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Part-Load Efficiency Rating
 Integrated Part-Load Value (IPLV)
 Weighted-average load curves
 Based on an “average” single-chiller installation
 Standard operating conditions
 Non-Standard Part-Load Value (NPLV)
 Weighted-average load curves
 Based on an “average” single-chiller installation
 Non-standard operating conditions

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Standard Rating Conditions
evaporator condenser rating
chiller type flow rate flow rate standard
vapor-compression
• reciprocating ARI
• scroll 2.4 gpm/ton 3.0 gpm/ton
550/590–1998
• helical-rotary [0.043 L/s/kW] [0.054 L/s/kW]
• centrifugal
absorption 2.4 gpm/ton 3.6 gpm/ton
• single-effect
[0.043 L/s/kW] [0.065 L/s/kW]
• double-effect, 4.0 gpm/ton ARI
indirect-fired
2.4 gpm/ton [0.072 L/s/kW] 560–1992
• double-effect, [0.043 L/s/kW]
4.5 gpm/ton
direct-fired [0.081 L/s/kW]
water leaving evaporator = 44°F [6.7°C]
© American Standard Inc. 2001
water entering condenser = 85°F [29.4°C] Air Conditioning Clinic TRG-TRC016-EN
Flow Rates and Temperatures

QBtu/hr = 500  flow rate  T

[ QW = 4,184  flow rate  T ]

© American Standard Inc. 2001


equation for water only Air Conditioning Clinic TRG-TRC016-EN
Flow Rates and Temperatures
95°F 44°F 100°F 41°F
[35°C] [37.8°C] [5°C]
[6.7°C]

85°F 85°F
[29.4°C] [29.4°C]

54°F 57°F
[12.2°C] [13.9°C]

ARI conditions low-flow conditions


evaporator 2.4 gpm/ton evaporator 1.5 gpm/ton
flow rate [0.043 L/s/kW] flow rate [0.027 L/s/kW]
condenser 3.0 gpm/ton condenser 2.0 gpm/ton
flow rate [0.054 L/s/kW] flow rate [0.036 L/s/kW]
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
ASHRAE/IESNA Standard 90.1–1999
 Energy standard
 Building design and
materials
 Minimum equipment
efficiencies
 HVAC system design

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


standard 90.1-1999 efficiency requirements
Electric Vapor-Compression Chillers
chiller type capacity minimum efficiency*
air-cooled all capacities 2.8 COP 3.05 IPLV

water-cooled
reciprocating all capacities 4.2 COP 5.05 IPLV

helical-rotary, scroll < 150 tons [528 kW] 4.45 COP 5.2 IPLV
150 to 300 tons [528 to 1,056 kW] 4.9 COP 5.6 IPLV
> 300 tons [1,056 kW] 5.5 COP 6.15 IPLV

centrifugal < 150 tons [528 kW] 5.0 COP 5.25 IPLV
150 to 300 tons [528 to 1,056 kW] 5.55 COP 5.9 IPLV
> 300 tons [1,056 kW] 6.1 COP 6.4 IPLV
* as of October 29, 2001
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
standard 90.1-1999 efficiency requirements
Water-Cooled Absorption Chillers

chiller type capacity minimum efficiency*


single-effect all capacities 0.7 COP

double-effect
indirect-fired all capacities 1.0 COP 1.05 IPLV

direct-fired all capacities 1.0 COP 1.0 IPLV

* as of October 29, 2001

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


ASHRAE Standard 15–1994
 Safety standard for
refrigerating systems
 Mechanical equipment
room
 Refrigerant monitors
 Alarms
 Mechanical ventilation
 Pressure-relief piping

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chilled-Water Systems
period two
Chilled-Water System Design

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chilled-Water System Components

cooling tower

cooling coil

chiller
pumps
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Chilled-Water System

air-cooled
chiller

coil
pump

control
valve

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Load-Terminal Control Options
 Three-way
modulating valve
 Two-way
modulating valve
 Face-and-bypass
dampers

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Three-Way Valve Control

airflow

three-way bypass
modulating pipe
valve

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Two-Way Valve Control

airflow

two-way
modulating valve

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Face-and-Bypass Damper Control

bypass
damper

airflow

face
damper
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Load-Terminal Control Options
 Three-way modulating valve
 Constant water flow
 Variable return-water temperature
 Two-way modulating valve
 Variable water flow (pump energy savings)
 Constant return-water temperature
 Face-and-bypass dampers
 Constant water flow
 Variable return-water temperature
 Enhanced dehumidification capability with “wild” coils
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Chiller Evaporator Flow
 Constant flow is most
common
 Variable flow is
possible
 Can reduce energy
consumption
 Use only with evaporator
advanced chiller and
system controls

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Single-Chiller System
air-cooled
chiller

coil
pump

© American Standard Inc. 2001


three-way valve Air Conditioning Clinic TRG-TRC016-EN
Multiple-Chiller Systems
 Redundancy
 Part-load efficiency

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


chillers piped in parallel
Single Pump
54°F
[12.2°C]
off

42°F 48°F
[5.6°C] [8.9°C]
on
54°F
[12.2°C]

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


chillers piped in parallel
Dedicated Pumps

off

42°F
[5.6°C]
on
54°F
[12.2°C] 60% to 70%
of system flow

coil starved for flow


© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
chillers piped in parallel
Dedicated Pumps

2 pumps

1 pump
head pressure

system
curve
65% 100%

percent flow
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Chillers Piped in Series
electric
chiller
absorption
chiller

three-way valve

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


chillers piped in series
Equal Set Points
set point = 42°F [5.6°C] set point = 42°F [5.6°C]

42°F
48°F [5.6°C]
[8.9°C]

54°F
[12.2°C]

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


chillers piped in series
Staggered Set Points
set point = 48°F [8.9°C] set point = 42°F [5.6°C]

42°F
48°F [5.6°C]
[8.9°C]

52°F
[11.1°C]

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Primary-Secondary Configuration

production
pumps

ip e distribution
ss p
bypa pump
production
loop

distribution
loop

© American Standard Inc. 2001


two-way valve Air Conditioning Clinic TRG-TRC016-EN
Primary-Secondary System Rules
 The bypass pipe should be free of restrictions
 Sized for minimal pressure drop
 Avoid random mixing of supply- and return-water
streams
 No check valve

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Production Loop

production
pumps
supply
tee

s pip e
s
bypa
return
tee
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Manifolded Production Pumps

production
pumps

s pip e
s
bypa
isolation
valves

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Distribution Loop
supply
tee
s pip e
s distribution
bypa
pump

return
tee

two-way valve
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Primary-Secondary System Rules
 The bypass pipe should be free of restrictions
 Load terminals should use two-way
modulating control valves

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Varying Distribution Flow

B
pump
curve

head pressure
A

pressure 0 50 100
difference percent flow
variable-speed control riding the pump curve
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Multiple Distribution Pumps

s pip e
s
bypa

distribution
pumps

return
from loads

supply
© American Standard Inc. 2001
to loads Air Conditioning Clinic TRG-TRC016-EN
Multiple Distribution Pumps

ss pipe
bypa
distribution
pumps
return
from loads
A
B
supply
C to loads
B C
A
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Tertiary Pumping

s pip e
s
bypa
distribution
pump

tertiary
pump

two-way
valve
bleed line
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Distribution Loop Characteristics
 Reduced pump
energy use
 Distribution loop
sized for system
diversity
 Higher return-water
temperatures

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Primary-Secondary System Rules
 The bypass pipe should be free of restrictions
 Load terminals should use two-way
modulating control valves
 All chillers should be selected for the same
leaving chilled-water temperature and T

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


System Operation
sup
ply
flow supply
tee
production
loop
dem
pipe flow and
ass
byp
distribution
loop
return
tee

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Deficit Flow
1,000 gpm at 42°F
[63 L/s at 5.6°C]

6 ° F
1,000 gpm at 56°F
mat 5 ]
°CC
[63 L/s at 13.3°C] p
g t 13.3 1,200 gpm at 44.3°F
00
2 L/s a [76 L/s at 6.8°C]
[13

1,200 gpm at 56°F


© American Standard Inc. 2001 [76 L/s at 13.3°C] Air Conditioning Clinic TRG-TRC016-EN
Excess Flow
2,000 gpm at 42°F
[126 L/s at 5.6°C]

2 ° F
2,000 gpm at
54.6°F at 4 ]
g pm 5.6°C 1,800 gpm at 42°F
[126 L/s at 12.6°C] 200 L/s at [114 L/s at 5.6°C]
[13

1,800 gpm at 56°F


© American Standard Inc. 2001 [114 L/s at 13.3°C] Air Conditioning Clinic TRG-TRC016-EN
Control of Primary-Secondary System
condition response

deficit flow for start another


specified period of chiller and pump
time

excess flow greater turn off next chiller


than 110% to 115% of and pump
next pump to turn off

neither do nothing
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Types of Fluid Flow Meters
 Pressure-based
 Pitot tube
 Venturi
 Orifice plate
 Differential pressure
 Turbine and impeller
 Vortex
 Magnetic
 Ultrasonic
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Temperature-Based Calculations
supply
tee

ipe
s p
pas
by

system-level
controller
return
tee

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chilled-Water Systems
period three
System Variations

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Electric Utility Deregulation

0.30
price of electricity, $/kWh

0.20

0.10

San Diego, CA
2000 May June July August September
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Fuel Choice Options

absorption
thermal storage
power

indirectly-coupled,
gas-engine
chillers
control interface
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Chiller Efficiency Improvements
0.9 8.0
COP
chiller efficiency (kW/ton)

chiller efficiency (COP)


0.8 7.0

0.7 6.0

0.6 5.0
kW/ton
0.5 4.0

1970 1980 1990 2000


year
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Greater Focus on System Efficiency

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Trend Toward Lower Flow Rates
electric-driven chiller yesterday today

evaporator 2.4 gpm/ton 1.5 gpm/ton


flow rate [0.043 L/s/kW] [0.027 L/s/kW]

leaving 44°F 41°F


chilled-water [6.7°C] [5°C]
temperature

condenser 3.0 gpm/ton 2.0 gpm/ton


flow rate [0.054 L/s/kW] [0.036 L/s/kW]

entering 85°F 85°F


condenser-water [29.4°C] [29.4°C]
temperature
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Low-Flow Systems

750,000
annual energy consumption, kWh

600,000
chiller
450,000

300,000

150,000 pumps
cooling tower fans
0
base case low flow
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Variable-Primary-Flow Systems

variable-flow
pumps

y pass
check b
valves
control
valve
two-way
valve
optional bypass
with three-way valve
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Critical VPF System Requirements
 Chillers must handle variable evaporator flow
 System must include a bypass
 System-level controls must limit the rate-of-
flow change
 Adequate time to design and commission
controls
 Operator must understand the system

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Preferential Chiller Loading

distribution
pump
pip e
equally ypass
b
loaded
absorption
chiller
preferentially
loaded

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Sidestream Configuration

distribution
ip e pump
ss p
bypa

heat-recovery
chiller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Heat-Recovery Chiller
heat-recovery
condenser

standard
condenser
evaporator

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Heat-Recovery Chiller Options
heat-recovery auxiliary
(dual) condenser condenser heat pump
 Second, full-size  Second, smaller-size  No extra condenser
condenser condenser  Large base-heating loads or
 Large heating loads  Preheating loads continuous operation
 High hot-water  Moderate hot-water  High hot-water temperatures
temperatures temperatures
  Controlled
Controlled  Uncontrolled
 Degrades chiller efficiency  Improves chiller efficiency  Good heating efficiency

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Heat-Recovery Chiller Efficiency
cooling heat-recovery
chiller type mode mode
cooling-only 0.57 kW/ton not
centrifugal chiller [6.2 COP] applicable

heat-recovery 0.60 kW/ton 0.69 kW/ton


centrifugal chiller [5.9 COP] [5.1 COP]

cooling mode conditions:


• evaporator T = 44°F to 54°F [6.7°C to 12.2°C]
• condenser T = 85°F to 95°F [29.4°C to 35.0°C]

heat-recovery mode conditions:


• evaporator T = 44°F to 54°F [6.7°C to 12.2°C]
• condenser T = 85°F to 105°F [29.4°C to 40.6°C]
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Control of a Heat-Recovery Chiller
120
percent maximum pressure differential

ble
100 s ta tion
un era ) B A
op urge
(s
unloading with
80 constant leaving hot-
C water temperature
unloading with
constant entering hot-
60 water temperature

0 50 100
© American Standard Inc. 2001
percent load Air Conditioning Clinic TRG-TRC016-EN
Asymmetric Design
 Different chiller
capacities 10,000
 Different chiller

annual operating hours


8,000
efficiencies
lag
6,000 chiller
4,000
lead
2,000
chiller
0
50% / 50% 60% / 40%
chiller split
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Swing Chiller
equal-capacity
large chillers
small-capacity
“swing” chiller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Swing Chiller
100
swing chiller
80
percent cooling load

swing chiller
60
chiller 2
40

20
swing chiller chiller 1
0
© American Standard Inc. 2001
chiller sequence Air Conditioning Clinic TRG-TRC016-EN
“Free” Cooling
 Airside economizer
 Waterside economizer
 Strainer cycle
 Plate-and-frame heat exchanger
 Refrigerant migration

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


waterside economizer
Plate-and-Frame Heat Exchanger

distribution
pump
pip e
ypass
b
condenser
water loop

plate-and-frame
© American Standard Inc. 2001
heat exchanger Air Conditioning Clinic TRG-TRC016-EN
waterside economizer
Refrigerant Migration
from
compressor

condenser
shutoff
valve
vapor
to migration
compressor
shutoff
valve evaporator
liquid
flow
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Application Outside Range of Chiller
240 gpm at 45°F
air-cooled
[15 L/s at 7.2°C]
chiller

240 gpm at 56.7°F


[15 L/s at 13.7°C]
a t 45°F 80 gpm at 45°F
gpm
160 7 .2 ° C] [5 L/s at 7.2°C]
at
/s
[10 L
80 gpm at 80°F
[5 L/s at 26.7°C]

process load

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chilled-Water Systems
period four
Chiller-Plant Control

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chiller Controls
 Start–stop
 Chilled-water
temperature
control
 Monitor and
protect
 Adapt to
unusual
conditions

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Key Issues for Chiller-Plant Control
 When to turn a chiller on or off
 Which chiller to turn on or off
 How to recover from an equipment failure
 How to optimize system efficiency
 How to communicate with the operator

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chiller Sequencing
 Turning on an additional chiller
 Turning off a chiller
 Which chiller to turn on or off?

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


load indicators
Temperature

supply-water
temperature

return-water
temperature

chiller-plant
controller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


load indicators
Flow

ss pipe
bypa
flow
meter
chiller-plant
controller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


load indicators
Capacity

supply-water
temperature
flow
meter

return-water
temperature

chiller-plant
controller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chiller Rotation

equal-capacity chillers

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Chiller Rotation

small electric
chiller large electric
chiller
absorption
chiller

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Heat Recovery

standard
electric chillers

preferentially-loaded
heat-recovery
chiller
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Variable-Primary-Flow Systems

variable-flow
pumps

y pass
check b
valves
control
valve
two-way
valve
optional bypass
with three-way valve
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
System Failure Recovery
 Maintain flow of chilled water
 Keep it simple
 Lock out failed equipment
 Turn on the next chiller in the sequence
 Notify the operator
 Allow the operator to intervene

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Contingency Planning

piping
stubouts

electrical
connections
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
System Timers
 Load-confirmation timer
 Avoids transient conditions
 Staging-interval timer
 Allows time for the system to
respond to turning a chiller on
 Minimum-cycle timer
 Prevents excessive cycling

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Unload Before Start

2 pumps

1 pump
head pressure

system
curve

system flow rate 610 gpm 870 gpm


© American Standard Inc. 2001 [38.5 L/s] [54.9 L/s] Air Conditioning Clinic TRG-TRC016-EN
Soft Loading
80°F
[26.7°C]
soft loading
supply-water temperature

(one chiller)

60°F
[15.6°C]

set point
40°F
[4.4°C] two chillers

0 30 60
© American Standard Inc. 2001
operating time, minutes Air Conditioning Clinic TRG-TRC016-EN
constant-volume pumping system
Chilled-Water Set Point Control
54°F
off [12.2°C]

37°F 45.5°F
[2.8°C] [7.5°C]
on
54°F
[12.2°C]

lowering operating
chiller set point
helps regain control
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
System Optimization
 Chiller
 Decrease condenser-water temperature
 Increase chilled-water temperature
 Chilled-water pump (variable-flow system)
 Increase chilled-water T
 Cooling tower
 Increase condenser-water temperature
 Condenser-water pump (variable-flow system)
 Increase condenser-water T
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Chilled Water Reset
 Pros  Cons
 Reduces chiller energy  Increases pump energy
 in variable-flow systems
Can work in constant-
flow systems  Can cause loss of
space humidity control
 Complicates chiller
sequencing control

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Condenser-Water Temperature
300,000
annual energy consumption, kWh

cooling
tower
200,000

chiller
100,000

85°F 70°F 55°F optimal


[29.4°C] [21.1°C] [12.8°C] control
© American Standard Inc. 2001 condenser-water temperature set point Air Conditioning Clinic TRG-TRC016-EN
Control of Condensing Pressure

condenser

control
panel
evaporator

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Operator Training and Support

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Operator Interface

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


chiller operating log
ASHRAE Guideline 3
 Chilled-water inlet and outlet  Compressor-refrigerant suction
temperatures and pressures and discharge temperatures
 Chilled water flow  Oil pressures, temperature, and
 Evaporator-refrigerant levels
temperature and pressures  Refrigerant level
 Evaporator approach  Vibration levels
temperature
 Condenser-water inlet and outlet  Addition of refrigerant or oil
temperatures and pressures
 Condenser water flow
 Condenser-refrigerant
temperature and pressures
 Condenser approach
temperature
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Chilled-Water Systems
period five
Review

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN


Review—Period One
 Vapor-compression
water chillers
 Air-cooled versus water-
cooled
 Absorption water
chillers
 Equipment rating
standards
 ASHRAE/IESNA
Standard 90.1-1999
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Review—Period Two
 Load-terminal control
 Three-way valve
 Two-way valve
 Face-and-bypass
dampers
 Parallel configuration
 Series configuration
 Primary-secondary
configuration primary-secondary system
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Review—Period Three
 Hybrid systems
 Low-flow systems
 Variable-primary-flow systems
 Preferential loading
 Heat recovery
 Asymmetric design
 “Free” (reduced-energy) cooling
 Application of a chiller outside its normal
operating range
© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN
Review—Period Four
 Chiller sequencing
 Failure recovery
 Contingency
planning
 System tuning
 System optimization
 Operator interface

© American Standard Inc. 2001 Air Conditioning Clinic TRG-TRC016-EN

You might also like