Module 5 Carrier
Module 5 Carrier
Carrier Setup
Non-CAT Carrier
OUT
Test Purposes:
• Verify flow at operating pressure IN
Work Tool Program must be properly programed to prevent Work Tool failure and
provide satisfactory production.
1. Two Pump Flow Combine needs to be enabled if required flow to Work Tool
approaches or exceeds capacity of One Pump on the Carrier.
2. One Way/Two Way Valve Mode depends on the Work Tool. One Way brings return
flow directly back to tank while Two Way sends it back through the Main Valve.
3. Line Relief Pressures can be programmed through the Work Tool Program if the Reliefs
are Electronic. (Pressure Setting is At Main Pumps)
4. Attachment Valve #1 Flow Setting is programed with the required Flow to the Work
Tool. Recommend 80% of Max for Rental Programs.
5. Attachment Valve #1 Multi-Oper. Additional Flow sends extra Flow to the Work Tool if
another function is activated by the Operator.
a. 580 psi setting will give Full Flow Priority to the Work Tool
b. 300 psi setting will start to cause the Carrier to take Priority over the
Work Tool.
c. 200 psi setting and lower will give full Priority to the Carrier and
cause Performance issues with the Work Tool.
d. D-Series Excavators usually default with Carrier Priority while E-
Series Excavators are usually default with Work Tool Priority.
e. Most operators prefer Work Tool Priority over Carrier Priority.
f. Very important Setting for Demolition Tools.
HEX Work Tool Program
7. Attachment Valve #1 and #2 Open and Close Times are default set around 0.20
seconds. This is the time it takes to Open the Valve after pressing the button and Close
the Valve after releasing the button.
a. For almost all cases this should be left at the default value.
b. For demolition tools such as a Shear, Close Times can be lowered to 0.05-0.10
seconds if the operator needs better reaction time to prevent jams.
HEX Work Tool Program
8. Attachment Valve #3 Extend and Retract Pressures are to control Flow from a Fixed
Displacement Medium Pressure Pump for Rotate Functions.
a. For a 336 sized Excavator, the Medium Pressure Pump will output around 11
GPM Max.
b. 580 psi setting in the Program, which is the max allowable setting, will cause
the Pump to output 11 GPM.
c. 250 psi setting in the Program will cause the Pump to output around 5 GPM.
d. E-Series Excavators program by Flow Setting, not Pressures as in this D-Series
example.
Carrier Calibrations
Calibration Order
1.Engine Speed (C&D Series)
2.PRV – Power Shift Pressure
3.Modulation Input Calibration
4.PRV – Attachment Valve Pressure
5.PRV – Variable Relief Pressure
6.PRV – Main Pump Flow Limitation
Calibrations – Monitor
Attachment Valves:
1.Close the Return Ball Valve and read the Pump Pressures in the Monitor.
2.Use a Load Sensing Flow Meter and close the circuit and read the Pressure Gauge on
the Flow Meter. (Best Method since Flow Meter will usually be installed.)
If Pressure does not Match Work Tool Program for Electronic Reliefs, Perform the Line
Relief Calibration.
Flow @ Pressure
Set Flow @ Pressure
Horsepower = Flow @ Pressure
Example: H160DS = 75 gpm @ 2300 psi
Follow
Steps for
Calibration
C Series Monitor
100
95 Aux - 10
Aux - 9
90
85 Aux - 8
80 Aux - 7
75 Aux - 6
70
Aux - 5
65
60
Aux - 4
Flow (gpm)
55 Aux - 3
50
45 Aux - 2
40
35
Aux - 1
30
25
20
15
10
D & E Series Monitor
5
0
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000
Pressure (psi)
Monitor
100 95
95 90 Aux - Aux
10 – 2 …Shear Application
Aux - 9
90 85
85 80 Aux - 8
80 75 Aux - 7
75
70 Aux - 6
70
65 Aux - 5
65
60
60
Aux - 4
55 Aux – 1…..H130S Application
Flow (gpm)
Flow (gpm)
55 Aux - 3
50
50
45
Aux - 2
Set Non-used Modes to Zero gpm
45
40
40
35
35
Aux - 1
30
25
30
25
Eliminate Possible Problems from Selection Process
20
20
15 15
10 10
5 5
0 0
10001000 12001200 14001400 16001600 18001800 20002000 22002200 24002400 26002600 28002800 30003000 32003200 34003400 36003600 38003800 40004000
Pressure
Pressure (psi)(psi)
Monitor
120
Incorrect Mode
100
80
Over
flow
60 H140DS mode
H140DS 60 gpm
Flow range
40
42 gpm
20
2. Hydraulic Kit
Quick coupler failure
Damaged or pinched hose
Ball valve closed
3. Work Tool
Carrier and Work Tool Inspection
Inspect
Auxiliary Circuit (Restrictions or Small Lines)
Ball valves fully opened
Damaged hoses
Missing or loose bolts
1
Test
Relief valve setting
Operating pressure set correctly
Record
Service Meter Hours (smu)
Work Tool Auxiliary Hours
Is Correct Tool Selected
4 Take a Product Status Report
Inspect
Grease fittings (Missing or Worn)?
Adequate amount of Grease seen on Work Tool? 2
Work Tool Wear Part Condition?
General Work Tool Condition?
Correct Grease Used? Verify
Auto-lube function correctly
Observe Grease canister is full
Correct Operating Practices Correct grease is being used
Carrier Setup
Questions?