Chapter 4
Chapter 4
Supplying air at a proper flow rate and condition only would not let the occupants
comfortable as long as the distribution is improper.
Therefor For the comfort of occupants supplying air at a proper flow rate, proper
condition and distribution is a must.
Room Air Distribution
1. Temperature throughout the occupied zone of the room within 10C of the design
temperature is acceptable for the roof height of up to 1.8 meter and above this height greater
T0 fluctuations are permissible.
The T0 fluctuation greater than the set standard values usually result in discomfort.
2. Air Velocity throughout the occupied zone should be within the range of 0.125-
Duct work
Centrifugal fan with forward- curved blades is widely used in low-pressure air conditioning
systems.
The more efficient backward-curved and airfoil type fans are used in large capacity, high-
pressure systems.
Axial fans are classified into propeller, tube axial, and vane axial types
1. The axial flow fans are never used for duct air conditioning system?
Because they are incapable of developing high pressures. they are suitable for handling
large volumes of air relatively low pressures.
Ducts
2. It should be economical
The duct layout is made taking into account the space available and simplicity of
construction.
General rules for duct design:
1. Air should be conveyed as directly as possible to save space, power and material
2. Sudden changes in directions should be avoided.(When not possible to avoid sudden changes,
turning vanes should be used to reduce pressure loss)
4. Aspect ratio should be as close to 1.0 as possible. Normally, it should not exceed 4 (Aspect
Ratio is the ratio of the dimensions of the two adjacent sides of the duct)
5.Air velocities should be within permissible limits to reduce noise and vibration
in the figure, supply air from the fan is distributed to different outlets (1 to 5), which are located in
different conditioned zones.
The letters A to I denote the portions of the duct to different outlets. Thus A-B is the duct running
from the supply air fan to zone 1,
The duct run with the highest pressure drop is called index run.
The required supply airflow rates to each conditioned space can be known from load and
psychrometric calculations.
the length of duct run is known from the building layout and the location of the supply fan.
The purpose of the duct design is
to select suitable dimensions of duct and then
to select a fan, which can provide the required supply airflow rate to each conditioned zone.
the most common duct design methods are:
1. Velocity method
2. Equal Friction Method and
3. Static Regain method
Velocity method:
steps involved in this method are:
Find the diameters of main & branch ducts from airflow rates & velocities for circular ducts./For
rectangular ducts, find the cross-sectional area from flow rate & velocity, & then by fixing the
aspect ratio, find the two sides of the rectangular duct/ From the velocities & duct dimensions
obtained in the previous step, find the frictional pressure drop for main and branch ducts using
friction chart or equation.
From the duct layout, dimensions and airflow rates, find the dynamic pressure losses for all the bends and
fittings
Select a fan that can provide sufficient FTP for the index run
Balancing dampers have to be installed in each run. The damper in the index run is left completely open,
while the other dampers are throttled to reduce the flow rate to the required design values.
The velocity method is one of the simplest ways of designing the duct system for both supply and return air.
However, the application of this method requires selection of suitable velocities in different duct runs, which
requires experience.
Wrong selection of velocities can lead to very large ducts, which, occupy large building space and increases the
cost, or
very small ducts which lead to large pressure drop and hence necessitates the selection of a large fan leading to
higher fan cost and running cost.
Then the stepwise procedure for designing the duct system is as follows:
i. Select a suitable frictional pressure drop per unit length (Δp f/L) so that the combined initial
and running costs are minimized.
ii. Then the equivalent diameter of the main duct (A) is obtained from the selected value of
(Δpf/L) and the airflow rate. As shown in the above figure airflow rate in the main duct is equal to the
sum total of airflow rates to all the conditioned zones, i.e.,
From the airflow rate and (Δpf/L) the equivalent diameter of the main duct (D eq,A) can be
obtained either from the friction chart or using the frictional pressure drop equation, i.e.,
iii. Since the frictional pressure drop per unit length is same for all the duct runs, the equivalent
diameters of the other duct runs, B to I are obtained from the equation:
iv. If the ducts are rectangular, then the two sides of the rectangular duct of each run are obtained
from the equivalent diameter of that run and by fixing aspect ratio as explained earlier.
Thus the dimensions of the all the duct runs can be obtained. The velocity of air through each duct
is obtained from the volumetric flow rate and the cross-sectional area.
v. Next from the dimensions of the ducts in each run, the total frictional pressure drop of that run is
obtained by multiplying the frictional pressure drop per unit length and the length, i.e.,
vi. The dynamic pressure losses in each duct run are obtained based on the type of bends or fittings used in
that run.
vii. Next the total pressure drop in each duct run is obtained by summing up the frictional and dynamic losses
of that run, i.e.,
viii. Next the fan is selected to suit the index run with the highest pressure loss. Dampers
are installed in all the duct runs to balance the total pressure loss.
Equal friction method
yields a better design than the velocity method as most of the available pressure drop is dissipated as
friction in the duct runs, rather than in the balancing dampers.
suitable when the ducts are not too long, and used for both supply and return ducts.
However, similar to velocity method, the equal friction method also requires partial closure of dampers in all but
the index run, which may generate noise. If the ducts are too long then the total pressure drop will be high and
due to dampering, ducts near the fan get over-pressurized.
EXAMPLE: The following figure shows a typical duct layout. Design the duct system using a) Velocity method, and b)
Equal friction method. Take the velocity of air in the main duct (A) as 8 m/s for both the methods. Assume a dynamic
loss coefficient of 0.3 for upstream to downstream and 0.8 for upstream to branch and for the elbow. The dynamic loss
coefficients for the outlets may be taken as 1.0. Find the FTP(fan total pr.) required for each case and the amount of
dampering required.
Duct
Ducts convey the conditioned air from the air-handling unit out through the
building and return it back to be conditioned again (or exhausted from the
building).
They are usually constructed of sheet metal and are insulated.