Transformer Protection
Transformer Protection
4. Core faults
Transformer Connections
Overcurrent Protection
Overfluxing Protection
Overload Protection
I A2 Ø
V EP
A1
I A2 a2
V EP ES
A1 a1
IP A2 a2 IS
V EP ES
A1 a1
A a a2
C1 A2
a1
c1 b
A1 b1 b2
C2
C B1 B2 B c2
c
Group 1 Yy0
Dd0
0 Phase displacement Zd0
Group 2 Yy6
Dd6
180 Phase displacement Dz6
Group 3 Yd1
Dy1
30 Lag phase displacement Yz1
Group 4 Yd11
Dy11
30 Lead phase displacement Yz11
Example 1 : Dy 11 Transformer
High Voltage Low Voltage
Windings Windings
A Phase
Windings
A2 A1 a1 a2
B Phase
Windings
B2 B1 b1 b2
C Phase
Windings
C2 C1 c1 c2
12
11
30°
A Line Designation a
30°
C B
c
A
a
C B c
A
a
a2
A2
a1
b
A
1
C B c
A
a
a2
C1 A2
a1
c1 b
b1 b2
C2 A
1
c2
B1 B2
C B
c
A a
A A a1 a2
2 1
B b
B2 B1 b1 b2
C c
C2 C1 c1 c2
1MVA
1500/5
3.3/0.44kV
51
N
64 1500/5
51 50
64
1000/5 5MVA
11/3.3kV
51
N
64 1000/5
3.3kV
9 > Transformer Protection
Overcurrent Protection
Requirements
HV
Source LV
50
51
Definition
I1 - I2
x 100
I2
I2 I1 = Steady state
rms
I1 D.C pick up
current
.
I2 = Fully offset
rms
pickup
current
3 > Transformer Protection
Instantaneous High Set Overcurrent
Relay Applied to a Transformer
51 51 51
HV HV L
2 1 V
HV2
HV1
Time
LV
Current
IF(LV) IF(HV)
1.2IF(LV)
4 > Transformer Protection
2-1-1 Distribution (1)
I3Ø I3Ø
0.866 I3Ø
I3Ø
HV relay
0.4 sec
LV relay
0.866 I3Ø I 3Ø
51
67
Grid supply
Feeders
51
67 51
51
51
51 Bus
Grid supply Section
Feeders
51
51 51
Grid supply
P1 67 67
S1
51
S2
P2
S2 S1
P2 P1
51
51 51
x
IP
PR
R IF
Protective
Relay
ResistorlimitsE/Fcurrentto fullloadvalues Thus,primarycurrent,P x .F.L.
3
2
For a fault at : Faultcurrent . F.L. . F.L.
3
If C.T. ratio (on primary side) is based on full
Effectiveturnsratio 3 : load current of transforme r, then C.T. secondary
2
circuit
3
1 > Transformer Protection
Overcurrent Relay Sensitivity
to Earth Faults (1)
If as multiple
of IF.L.
1.0
0.9
Star Side
0.8
IF
0.7
0.6
51
0.5
Overcurrent
Relay 0.4 Delta Side
0.3
0.2
0.1
p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
If as multiple
of IF.L.
10
9 Star Side
8
IF
7
6
51 5
Overcurrent 4
Relay Delta Side
3
2
1
p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
If as multiple
of IF.L.
10
9 IF
IF
8
7
6 IP
IP IN 5
4
3
2
IN
1
p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
2
I=
3
51N 51 51 51
51N 51 51 51
51N
Protected
Zone
RE
F
A B C N
LV restricted E/F
protection trips
both HV and LV breaker
A B C N
Source
Protected zone
REF
Protected
Circuit
Z RCT RCT Z
M M
RL IF RL
IS
VS
RST
R
RL RL
CT knee point
VKP = 2VS = 2IF (RCT + 2RL)
2 > Transformer Protection
Non-Linear Resistors (Metrosils)
IOP
RST
V VS
M
RR
Metrosil Characteristic
V = CI
1MVA
(5%) 1600/1
11000V 415V RCT = 4.9 Calculate :
1) Setting voltage (VS)
80MV
A 2) Value of stabilising
resistor required
3) Effective setting
4) Peak voltage
1600/1 RS developed by CT’s
MCAG14 for internal fault
RCT = 4.8
IS = 0.1 Amp
Sequence Diagram
1.6
(multiply by Kv to obtain RMS
Weber/m2 (Tesla)
1.2
secondary volts)
Kv Ki
T N A B C
1
Bus Section
T2
415 Volt
Switchboard
1 > Transformer Protection
Parallel Transformers
CT in Earth
N A BC
T1
51N
Bus Section
Open
T
2
51N
415 Volt
Switchboar
d
51N
Bus Section
Open
T
2
51N
415 Volt
Switchboar
d
T1 NA BC
F2
Bus section
F1
415 volt switchboard
No maloperation for fault at F2 (but setting must be
greater than load neutral current)
51 5
200/5 0
10MVA
33/11K 51
N 87
V 600/5
64
600/5
5/5A
Differential
Current
I1 - I2
BIAS BIAS I OPERATE
I1 2
I1 - I2
RESTRAIN
OPERATE
I1 + I2 Mean Through
2 Current
PROTECTED
ZONE
HV LV
P1 P2 A2 A1 a1 a2 P2 P1
A B C
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S2 S1
S2 S1 P1 P2
R
R
R
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
1 > Transformer Protection
Differential Protection
15MVA
150/5 66kV / 11kV 800/5
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S2 S1
Dy1
S1 S2 S2 S1
4.37A 4.92A
S1 S2 P1 P2
R (2.56) (5)
R
R
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S2 S1
S2 S1 P1 P2
R
R
R
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S2 S1
S2 S1 P1 P2
R
R
R
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S2 S1
S2 S1 P1 P2
R
R
R
P1 P2 A2 A1 a1 a2 P2 P1
S1 S2 S2 S1
S2 S1 P1 P2
R
R
R
S2 S1
S2 S1 T2 T1 P1 P2
S2 S1
S2 S1 P1 P2
300/1
EARTHING
TRANSF.
900/1
TO DIFFERENTIAL
RELAY
1 > Transformer Protection
In-Zone Earthing Transformer
Alternative (3)
300/1
EARTHING
TRANSF.
300/1
1/0.33
TO DIFFERENTIAL
RELAY
2 > Transformer Protection
Combined Differential and
Restricted Earth Fault Protection
A2 A1 a1 a2 P1 P2
S1 S2
P1
S1 P2
REF
S2 P1
P2
S1
S2
To differential relay
Restricted earth
fault relay
64
Bias windings
Differential relay
87 87 87
operating windings
PHASE b A
PHASE c A
N B
G G G
T1 BEF
T2
F
T3
J J J
T4
Rb
2 H H H
Rb
2
Rb
2
Ro Ro Ro
OVERALL DIFFERENTIAL
RELAY
5 > Transformer Protection
Three Winding Transformer
63MV 25MV
A A
300/5 132KV 11KV 1600/5
50MV
A
33KV
1000/5
Yd11(+30°)
R
R
R
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
Power transformer
Ratio
Numeric correction
Relay
Vectorial
correction
Differential
Virtual interposing CT element
Virtual interposing CT
Twice
Normal
Flux
Normal
Flux
Normal
No Load
Current
No Load Current
at Twice Normal
Flux
9 > Transformer Protection
Magnetising Inrush Current
Steady State
+ m V
Im
- m
Im
2 m
V
A
B
C
Bias
Differential Differential
comparator
Threshold
T1 = 5ms T2 = 22ms
Trip
Bias Trip
Differential Differential
T1 = 5ms T2 = 22ms
comparator
Threshold
Differential input
Comparator output
T1
Trip
T2
Reset
Bias Trip
Differential Differential
T1 = 5ms T2 = 22ms
comparator
Threshold
Differential input
Comparator output
T1
Trip
T2
Reset
High impedance
87
relay
a
b
c
87 87 87
CT
E
Load
Shorted
turn
100 10
20 2
0
5 10 15 20 25
Turn short-circuited (percentage of winding)
3 x internal pipe
Conservator
diameter (minimum)
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
Petcock
Mercury switch
Oil level
Trip bucket
Aperture adjuster
Generator transformers
Grid transformers
Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.
Flux V
f
Effects of overfluxing :
Increase in magnetising current
Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts (caused by stray
flux)
Protective relay responds to V/f ratio
Stage 1 - lower A.V.R.
Stage 2 - Trip field
2m
V = kf
m
CAUSES
Ie
Low frequency
High voltage
Geomagnetic disturbances
EFFECTS
Tripping of differential element (Transient overfluxing)
Damage to transformers (Prolonged overfluxing)
V K
f
Settings
t = 0.8 + 0.18 x K
(M - 1)2
1000
K = 63
100 K = 40
Operating K = 20
time (s) K=5
10
K=1
1
1 1.1 1.2 1.3 1.4 1.5 1.6
M = V Hz
Setting
Ex
G
VT
AVR R
L
Circuit breaker
position repeat relay
VAA relay
Inhibit AVR
raise
Alarm
RL2-1
100
With ambient of 20 C.
Hot spot rise of 78 C is
design normal.
A further rise of 6 C
doubles rate of
Relative 10 using life.
rate
of using
life
1.0
98
0.1
80 90 100 110 120 130 140
Hot spot temp C
05 > Transformer Protection
Overheating Protection
I load Trip
Alarm
TD
setting
On
Top oil of
I load Fan
power
control
transformer
Off
On
Pump
control
Off
Heater Temp. indication
Local
Thermal Temperature Remote
replica sensing resistor
Current
1000
Dual
100 characteristic
Single
10 characteristic:
1 2 3 4 5 6 = 5 mins
Current (multiple of thermal setting)
I 2
P
TripTime ln
IREF
2
I K
I REF TRIP
where = heating time constant
=I actual current measured by relay
IREF
= continuous current rating of protected plant
=P previous thermal state
TRIP
= trip threshold
K
= multiplier (for actual temperature)
Z OC OC Z
FTS FTS
REF REF
DP DP
Bh WT WT Bh
REF REF
SBEF SBEF
2 1 2 stage 2 stage 1 2
DOC OC OC DOC
Lower -
Load
Load voltage
11 > Transformer Protection
busbar
Protection of Transformer Feeders
CTs CTs HV LV
CTs CTs
TRIP
UNSTABILISE TRIP
TRIP
FEEDE
R
PILOT
PW P
S
W
Dy11
P1 P2 P2 P1
A I i A
S1 S2 S2 S1
B II ii B
C III iii C
23 MCTH
MCTH 23
24 17
17 24
25
25
26
27 26
19 27
28 19
28
23 17
17 23
24
24
25
MBCI PILOTS MBCI 25
26
18 18 17 18 26
27
19 27
28 19
28
+ MVTW
27 MFAC 1 02
28 14 13
3 14
-
Power transformer
Ratio
P540 correction
Scheme
Vectorial
correction