Section 1 - Introduction
WHAT IS VIGILOHM?
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 3
What is Vigilohm?
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 4
Vigilohm products and solutions
Level 1 Level 2 Level 3
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 5
Insulation monitoring device (IMD)
functions
● Level 1 : fault detection and signaling, manual fault location (all IMDs)
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 6
Section 2
EARTHING ARRANGEMENTS
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 7
The letters in earthing arrangements
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 8
TT earthing arrangements
MV LV
●The exposed conductive L1
parts of the installation L2
L3
N
are connected to an earth
electrode (Ra) which is
electrically separated from
the LV substation earth
electrode (Rb).
PE
R R
●Protection by RCDs B A
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 9
TN earthing arrangements
TN-C TN-S
L1 L1
L2 L2
L3 L3
PEN N
PE
RP
AB
RPA
B
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 10
IT earthing arrangements
PE
R
PAB
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 11
Earthing arrangement & applications
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 12
Earth fault consequence
230V Ph
●TN-C / TN-S : CB N
CB magnetic tripping
R1
< 10
●TT :
CB tripping with RCD
●IT :
First fault - No effect !!!
Second fault - CB magnetic tripping (like TN-C/TN-S)
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 13
Case of a second fault in IT system
●A short circuit means breaker trips!
L1
L2
L3
PE
R PAB
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 14
Earthing arrangement comparison
TT IT TN-C TN-S Observation
First Fault
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 15
Indirect contact and insulation fault (TT)
230V Ph
CB N
Ph
R1 RCD R2
30mA / 10mA 1K
< 10 < 10
Defect
UB
R2
U0 Ground
Hypothesis: R1 = R2 = 10 R1
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 16
Indirect contact & insulation fault (IT)
230V
Ph
CB N
R1 R2
< 10 1K
< 1 M
Hypothesis: R1 = 1 M
U body: : Ub = 230 V * R2/(R1+R2)=230*R2/R1 = 2.3 mV
Ph
I body: Ib= Ub /1 k = 2.3 mV / 1k = 2,3 µA
I body increases with R1 decrease Defect
Fault current IR1 = 230V / 1M = 0.2 mA
Ub
R2
U0
No risk after the first fault: no trip is needed. Ground
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 17
Limits for an IT earthing network
1 wire:
Ph
10 M / km
0.3 µF / km (10.6 K / Km @ 50 Hz) Defect
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 19
Section 3
IT EARTHING APPLICATIONS
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 20
Typical applications in IT arrangement
Some hospital areas
Off-shore
Ships
Availability Oil & Gaz
Fire
Explosion
Safety lighting
Industrial applications
with continuous or
Nuclear plants sensitive processes
( furnaces, industrial
robots…)
= mandatory Airports
= prescription / promotion (runway lighting, traffic supervision)
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 21
Hospital applications
•Key application driver : patient safety
•Product features for this environment
•AC internal impedance > 100 kOhms
•Test voltage (=injection voltage) <= 25 Vdc
•Injected current <= 1mA,
even under fault conditions
Hospital Anaesthetic room
•50 kOhms threshold
Hospital Operating theatre
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 22
Marine applications
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 23
Industry and infrastructure applications
Key application drivers : energy availability and safety
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 24
Section 4
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 25
How does Vigilohm work?
● IT earthing arrangement is used to guarantee supply
Protection threshold
continuity (energy availability) in an electrical
installation
Fault threshold
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 26
Operating diagram
L2 L2
V V
L3 L3
IMD V IMD
3 V
When the first fault occurs, When the first fault occurs,
the IMD detects the
E95484
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 28
What does Vigilohm measure & monitor?
●Insulation resistance
●If the resistance value is under the set-point, an alarm is triggered
●This resistance value is displayed on some modules
●For more advanced modules:
●Insulation resistance and 2 set-points (warning and alarm)
●Leakage capacitance
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 29
Why do we measure the network
capacitance?
● Monitoring the C value is essential on large networks since the
C-related impedance can cause these networks to drift towards
a TT arrangement. This configuration would generate a
dangerous voltage contact and a high fault current in case of
earth fault.
● Only Schneider Electric monitors these value.
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 30
Operating principle: DC Injection
Vi R network C network
Vi Vs
R network = - Rs and i =
Rs i Rs
Vs
E95476
Rs (Vi - Vs)
R network =
Vs
IMD Network
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 31
Operating principle: AC Injection
● The resistance and capacitance of the network are displayed by
measuring the insulation with an AC voltage injection IMD.
● Synchronous demodulation is used to indicate the real and imaginary
parts of Z and therefore to calculate the resistance R and capacitance
C of the network.
i RS
Vi R network C network
Z = R network // 1 ,
E95480
C network x
network complex impedance
IMD Network
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 32
Different injection methods, different IMDs
● There are two types of permanent insulation monitors that use different
injection methods:
●DC current injection IMD
IM9 / IM9OL
●AC current injection IMD (can be communicating)
CPI
CPI
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 34
Multiple configuration options
● Network type : AC / DC
● Injection type : AC / DC
● Injection type : permanent or non permanent
Network type
AC DC
type
Injection
AC Yes Yes
DC Yes
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 35
Section 5
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 36
Vigilohm offer
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 38
Vigilohm offer : Hospitals
Product features
Vigilohm IM10-H, IM20-H and HRP help ensure patient safety
IM10-H
●Fault detection and signaling
●Insulation resistance value display
IM20-H:
●Fault detection and signaling
●Insulation resistance value display
●Transformer monitoring (current and temperature)
●Modbus communication
●Alarm log IM10-H / IM20-H
HRP
●Insulation fault remote indicator (audible & visual)
●Electrical fault (transformer overload or circuit breaker tripping ) remote indicator
(audible & visual)
●Insulation daily test
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 39
Vigilohm offer : Hospitals
Key technical specifications
IM10-H / IM20-H
●Standards: IEC 60364-7-10, IEC 61557-8
●Network voltage: up to 230 V ac, 50 or 60 Hz
●Insulation resistance value reading: from 1 kOhm to 1
MOhm
●Minimal fault threshold: 50 kOhms
●Accuracy : 5%
●Auxiliary supply: AC or DC (generally the monitored HRP:
network) Hospital remote panel
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 40
Vigilohm offer : Marine, Industry, Infra.
Product features (Online insulation monitoring)
IM9, IM10 and IM20 help ensure process continuity, staff and process safety in IT earthing
network arrangements
IM9
●Fault detection and signaling without display (only for monitoring small AC networks)
●Pre-alarm threshold
IM10:
●Fault detection and signaling with large, intuitive multi-language display
●Insulation resistance value display
IM20:
●Same as IM10 plus
●Leakage capacitance measurement display
●Transformer monitoring (current and temperature)
●Modbus communication
●Alarm log
●Current injection inhibition feature
●Compatible with higher network nominal voltages with the HV subassembly
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 41
Vigilohm offer : Marine, Industry, Infra.
Specific standards for IM9, IM10 and IM20
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 42
Vigilohm offer : Marine, Industry, Infra.
IM9 key technical specifications
● Network voltage
●Up to 480 Vac L-L, 50, 60 or 400 Hz
● Two alarm thresholds
●Pre-alarm: from 2,5 to 500 kOhms
●Alarm: from 1 to 250 kOhms
● 1 changeover contact in case of earth fault
● Auxiliary supply:
●110 to 415 Vac (+/- 15%) IM9
●125 to 250 Vdc (+/-15%)
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 43
Vigilohm offer : Marine, Industry, Infra.
IM10 / IM20 key technical specifications
● Network voltage:
●Up to 480 Vac L-L, 50, 60 or 400 Hz
●Up to 345 Vdc
●Up to 1700 Vac L-L with subassembly (IM20)
● Range for leakage capacitance readings:
●0,1 – 40 µF (IM20) – Impedance display
● 2 thresholds
●Pre-alarm: from 1 kOhm to 1 Mohms
●Alarm: from 0,5 kOhm to 500 kOhms IM10 / IM20
● 1 changeover contact in case of earth fault
● Auxiliary supply:
●110 to 415 Vac (+/-15%) / 125 to 250 Vdc (+/-
15%)
● Multi-language support for English, French, Spanish,
Italian, Portuguese, Chinese, and Russian
● DNV approval for the Marine market
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 44
Vigilohm offer : Industry
IM9-OL Product features (Offline insulation monitoring)
IM9-OL for insulation monitoring of offline motors (i.e., motors that
are not normally powered, such smoke extractors)
●Functions
●Insulation monitoring with an adjustable threshold
●Motor start inhibition with a second threshold
●Ability to authorize start, even in case of low insulation
●Fault detection and signaling in all motor earthing
arrangements (TN, TT, IT)
●Standards
●Product: IEC 61557-8, Safety : 61010-1
●Features
●Motor nominal voltage : up to 690 V IM9-OL
●Pre-alarm threshold: from 0,5 to 10 Mohms
●Motor inhibition threshold: from 0,25 to 2 Mohms
●Suitable for 1 ph or 3 ph motors, including star/delta start
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 45
The Vigilohm Offer
LEVEL 2 SOLUTION
AUTOMATIC FAULT LOCATION
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 46
Vigilohm offer - automatic fault location
● Typical architecture
●XM200 IMD that displays global R and C
●XD312 / XD301 automatic fault locators
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 47
Automatic fault location – strong points
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 48
XM200 key technical features
● Network voltage:
●up to 760 Vac (injection connected to
neutral)
●up to 440 Vac (injection connected to
phase)
●up to 500 Vdc
●For higher voltages, please use XM300C.
● Range for insulation resistance readings:
●from 0,1 to 999 kOhms
● Range for leakage capacitance readings:
●from 0,1 to 199 µF
● 2 thresholds (pre-alarm and alarm) and 2
output contacts
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 49
XD301 / XD312 key technical features
●Network type:
●low voltage, AC (45 to 400 Hz) or DC
●Operating threshold:
●2,5 mA @ 2,5 Hz
●Polling time:
●20 s per channel
●1 output contact
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 50
The Vigilohm Offer
LEVEL 3 SOLUTION
FEEDER MEASUREMENT & COMMUNICATION
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 51
Vigilohm offer - measurement per feeder
and communication
● Ideal for medium or large network
monitoring, especially for control
networks with multiple incomers and
feeders
● R and C measurement per feeder is
prescribed
● The customer wants to monitor
insulation from the supervisory system
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 52
Level 3 solution - architecture overview
Vigilohm bus
XLI300/XTU300
Modbus /
Serial communication
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 53
Level 3 solution – typical architectures
● Typical architecture
● XML308 / XML316 IMDs for global network monitoring with feeder
measurement up to 8/16 feeders
● XL308 / XL316 automatic fault locators incl. feeder measurement
● XLI / XTU communication interfaces
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 54
Level 3 solution – strong points
● IT distribution networks
●AC, DC, mixed
●Non linear loads: rectifiers, static
converters, variable speed drives
XM300C
● Measurement and monitoring of network
insulation
●R and C measurement, globally and on
the most critical feeders
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 55
Level 3 solution – main technical features
● 2 settings:
●adjustable pre-alarm and alarm thresholds
●1 adjustable feeder threshold
● 2 output relays
● Measurement:
● from 0.1 to 999 k / from 0,1 to 1000 µF
● Network voltage :
●from 440 Vac to 1700 Vac depending on the
selected injection cable and a possible interface from
500 Vdc to 1200 Vdc
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 56
The Vigilohm Offer
ACCESSORIES
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 57
Toroids for automatic fault detection
● GA 300
● SA 200
● MA 120
● IA 80
● PA 50
● TA 30
●POA
● GOA
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 58
Cardew surge limiter
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 59
ZX impedance
● Impedance value:
●1,5 kΩ at 50 Hz
●1 MΩ at 2,5 Hz / DC
●U < 500 V AC
MV/
LV
IMD
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 60
HV-IM20-1.7 subassembly
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 61
PHT1000 subassembly
MV/LV
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 62
Mobile fault locating kit
● It includes:
●A 2.5 Hz generator: XGR
●a 2.5 Hz receiver: XRM
●Three probes: P15 - P50 - P100
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 63
Mobile fault locating kit
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 64
Section 6
STRONG POINTS
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 65
Strong points of the Vigilohm offer
Technical features
● The new offer re-uses Vigilohm injection principle and improves it
● Customer benefits: better accuracy and behavior with non linear loads
● Wide range of insulation resistance measurement and display
● Possibility of leakage capacitance measurement (IM20)
Implementation
● Very easy to install – Din rail or flush mount
Operation
● Very intuitive human man interface
● Multi-language LCD display
●Supports English, French, Spanish, Italian, German, Portuguese, Russian and
Chinese
Schneider Electric - Energy Management Solutions – Vigilohm offer presentation – Patrick Henry – January 2011 66