Expansion Loop Design
Expansion Loop Design
Suyog S. Bhamare
Thermal Expansion
All pipes will be installed at ambient temperature. Pipes carrying hot fluids such
as water or steam operate at higher temperatures. It follows that they expand,
especially in length, with an increase from ambient to working temperatures.
This will create stress upon certain areas within the distribution system, such as
pipe joints, which, in the extreme, could fracture. The amount of the expansion
is readily calculated using Equation 1 or read from an appropriate chart such as
Figure.
Expansion (mm)=LΔTα ----------------------1
Where:
L = Length of pipe between anchors (m)
DT = Temperature difference between ambient temperature and operating
temperatures (°C)
a = Expansion coefficient (mm/m °C) x 10-3
What is an Expansion Loop?
Bend (usually in the form of a horseshoe or ω which is inserted
in a pipe run to provide for the expansion of the pipe resulting
from a temperature change or A complete loop installed in a
pipeline to mitigate the effect of expansion or contraction of the
line.
Types of loop
• U-Loop.
• Omega Loop.
• 3D-Loop
• O -Loop
7. Move the anchors of these lines (one line at a time) closer to the
corners.
(The line will now have two anchors).
1.Use of loops shall be considered, as a rule, when a piping, whose temperature difference
between operating (including steam purging, etc.) and normal temperature conditions is
100°C or more, is running a long distance (as a rough rule, when the expansion of piping at
one side is larger than 40mm), on pipe racks or on sleepers. The use of loops shall also be
considered, when it is necessary to have a least amount of movement of the piping, even
though the temperature difference of the piping is 100°C or lower.
2. The shape of loop shall be, as a rule, horizontal loop, as far as there is no problem from
the view point of piping route. If horizontal loop cannot be arranged due to any problem,
such as the space, existing obstacles, etc., three dimensional loop shall be selected. The
height of loop (H) shall be about 0.75 - 2.5m, where the size of such obstacles, etc., shall be
taken into consideration.
3 The allowable maximum distance between loops is different, depending upon the
temperature and size of the piping, length of the loop, etc. However, in order to utilize
the space effectively, it is preferable, as a rule, to provide each of parallel running
piping with loops, in such a way that the position of loops is the same for each piping
and the distance between loops is 50m.
4 The expansion loop is usually located on the side of the hottest line.
5. The expansion loop, as a rule, should be located in the center of the distance between
two anchors.
6. The height of the expansion loop is normally twice the width. The exception to this
rule occurs when more than one line runs parallel in a common trench. The dimensions
of the loops for the additional line must be increased to allow nesting of the loops.
Case Study on loop Calculation by using Nomograph:
Find the size of loop to absorbs expansion in 200 Ft of 12” Carbon steel pipe at
4000F.Assume width to height ratio.
Using the nomograph & assuming a straight line starting from 12 inch diameter &
through a 5.4 inch in expansion, read bend length L as 50 ft. Assume H=W ,then L= 2H
+W=50 ft.Thus H=W=17 Ft .