Lecture 9 BASIC-LINE-PROTECTION
Lecture 9 BASIC-LINE-PROTECTION
PROTECTIO
N
INTRODUCTION
0 Line is a general term applied in a power network for any
• Auto reclose relay suitable for 1 ph/3ph (with deadline charging and
• Distance Protection.
0Requirements of distance protection:
• Shall be non switched type with separate measurement for both earth
• Accuracy of better than 5% of reach setting for Zone 1, 10% for Zone-2 &3.
E ZS ZL
X X X X X
If
If = E/(ZS+ZL)
Z3
Z2
Z1 Load
R Area
MHO relay characteristic
The characteristic of a mho impedance element , when plotted
on a R/X diagram, is a circle whose circumference pass through
the origin .
X
R
= relay characteristic angle
OFF set MHO characteristic
Under close up faults, when the voltage is near to zero then
MHO will not operate. The mho characteristic can be shifted
towards origin for operation of close up faults. This is know
as OFF set MHO.
X
R
= relay characteristic angle
Mho positive-sequence R-X operating
characteristic of a distance Relay.
Region of
Line Q non-operation
120%
B outside the circle
80%
Zone 2
Line P
Z RS
Load
Region of region
operation
Zone 1
A R
Zones of Distance Protection:
Zone-3
Zone-2
Zone-1
A
B C
80%
150%
ZAB + 120%
BASIC SETTING PHILOSOPHY
Time setting:
Zone-1 : Instantaneous
Zone-2 : 0.3 to 0.5 sec
(For long line followed by short line)
Zone-3 : 1.0 sec.
Terms associated with distance protection
Reach:
Reach is the impedance of the tr. line up to which the
distance relay protects the line from the faults.
over reach
Under reach
Relay measured impedance is more than actual impedance.
i.e. Effective reach of the relay decreases
ZONE - I CHARACTERISTICS
Should isolate the faulted section instantaneously
Should cover protected circuit &fault resistance with some
margin to take care of errors in measurement
Selective phase tripping for 1ph to ground faults for
auto reclose of the breaker.
Fast operation with secured directional discrimination.
Should be stable in the presence of:
1. Fault resistance, arc resistance and tower footing resistance
2. Power swings
3. Heavily loaded condition
4. In feed condition
5. Errors in CT, CVT and CT saturation
6. Transients in CT & CVT
ZONE-II CHARACTERISTICS
Delayed tripping and non selective phase tripping.
Provide back up protection for part of adjacent line.
Trip the faulty line instantaneously using carrier aided tripping.
Time delay is normally 500ms
ZONE-III CHARACTERISTICS
This provides back up protection for the adjacent lines or
transformer
Time delay is normally 1500ms
ZONE –IV CHARACTERISTICS
This provides back up protection for the station faults
It is normally in the reverse direction
Time delay is normally 1500ms
PILOT PROTECTION
0 Pilot protection as the name implies means that pilots or
separate channels are used at either ends of a line to compare
the system parameters sent out over a line.
0 These include either comparing the voltages, currents or the
phase angle between the voltages and currents at the two ends
of a line.
0 The pilots used could be separate control cables or wire pilots
run between the two ends of a line. It could also be a channel of
the power-line carrier coupling between the two ends of a line.
0 Power Line Carrier Coupling (PLCC) pilots are mostly used
on lines where PLCC equipment has been installed for
other purpose such as telecommunication, tele-metering,
etc.
0 These pilots are called carrier protection pilots and are
used at no extra cost and they are used where
instantaneous tripping of both ends of a faulted line is
desired.
OVER CURRENT AND EARTH FAULT
PROTECTION FOR SINGLE LINES
0 Over-current and Earth Fault Protection is provided on
feeders either by a combination of three over-current
relays and a single earth fault relay or by two over-
current relays and a single earth fault relay as shown.
0 The E.F.R is also similar to the O.C.R but with low current settings.
For example if a 5A, O.C.R has current taps from 2.5 to 10A, (50 to
200%), then the current taps on the E.F.R will be from 0.5 to 2A
(10 to 40%).
0 Also if a 1A O.C.R has current taps from 0.5 to 2.0A (50 to 200%),
then the current taps on E.F.R will be from 0.1 to 0.4 A.
0 Operation of the O.C and E.F relays on successive line sections is
coordinated by the proper selection of current and time settings
during “Co-ordination of relays and relay settings”.
0 The relay pick up should be so chosen so that:
1. It will provide primary protection for all short circuits on
the section it is protecting.
2. It will provide back up protection for short-circuits on an
adjoining section immediately beyond the protected
section.
3. It will not pick up on instantaneous maximum or
emergency overloads.
4. It will be positive for minimum fault current condition so as
to enable the use of the most inverse portion of the relay
time current characteristic.
SELECTION OF THE INVERSENESS OF A
RELAY CHARACTERISTIC
0 The lesser the effect of the magnitude of short circuit
currents for a fault at a given location, the more
inverse time current characteristic should be used to
take advantage of the reduced time of fault clearing
for faults near the relay location. Accordingly
I.D.M.T., Very Inverse or Extremely inverse in order
of increased inverseness can be applied.
0 In systems where the magnitude of the ground fault
current is severely limited by the neutral grounding
impedance and arc plus ground resistance, little or no
advantage can be taken of the inverseness of an E.F.R
characteristic as the fault current does not change much
with the fault location. In such cases a relay with I.D.M.T
characteristic may as well be used.
0 In cases where O.C relays have to be coordinated with
fuses very closely, then very inverse or extremely inverse
characteristic relays are well suited.
PROTECTION FOR PARALLEL LINES
0 In the normal course, when the fault is isolated from one source only,
then the fault current will also be fed from the other source. Hence
non-directional relays have to be installed at both ends. The co-
ordination of the relays should be such that they operate
simultaneously.
ADJUSTMENTS FOR LOOP AND INTERCONNECTED
CIRCUITS
arrows indicate, the fault currents for which the relays should
act. Thus at all relay locations except at (5) and (e), fault
currents can flow in one direction. Hence at all relay locations
except at (5) and (e), the relays installed are directional
relays.
0 Relays at locations (1), (2), (3) and (4) are to operate for one
TYPES OF FAULTS
1. TRANSIENT FAULTS
2. SEMI PERMANENT FAULTS
3. PERMANENT FAULTS
TRANSIENT FAULTS -CHARACTERISTIC
X
Z3
Z2 Power
swing
detection
Z1 zones
0Stage-I:
0Setting: 110%
0Time delay: 5 Sec.
0Stage –II
0Setting: 140%
0Time delay: Instantaneous.