Electric Power
Distribution
Distribution of Electrical Energy
In north America, medium voltage networks
generally operate at voltages between 2.4 kV and
69 kV
In turn, they supply million of low-voltage systems
that function between 120 V and 600 V.
In Pakistan, distribution companies are responsible
to operate 132 kV and 11kV lines and feed million
of low voltage systems operating at 230/440 V.
500 kV/132 kV power transformers are rated
as160 MVA which are being replaced by 250 MVA
transformers (NTDC-Pakistan).
Distribution of Electrical Energy
The distribution involves substations where
high voltage transmission-line voltage is
reduced close to the power-consuming
centers.
Substation Equipment
Transformers
Circuit breakers
Horn-gap switches
Disconnecting switches
Grounding switches
Surge Arrestors
Current limit reactors
Instrument transformers
Relays and other protection devices
Transformers
At substations, the high voltage (500 kV or
220 kV) are reduced to 12 kV by means of HV
power transformers
These transformers may be rated as 160 MVA
or 250 MVA (Pakistan scenario)
The 132 kV power transformers at the
substations are protected by circuit breakers.
Circuit Breakers
Circuit breakers are designed to interrupt
normal or short-circuit currents.
These CBs could be operated or closed by
local push button or by distant
telecommunication signals emitted by the
system of protection.
The CB opens or closes wherever the line
current, line voltage, or frequency depart
from a preset limit.
Types of Circuit Breakers
Oil circuit Breakers
Air-blast circuit breakers
SF6 CBS
Vacuum CBs
Important Nameplate Data of a CB
The max. steady-state current it can carry
The max. interrupting current
The max. line voltage
The interrupting time (3 to 8 cycle)
Triggering action of a CB
the triggering action is usually produced by
means of an overhead relay that can detect
abnormal line conditions.
Here, the relay coil is connected to the
secondary of a current transformer.
The primary carries the line current of the
phase that has to be protected.
When line current exceeds a preset value, the
secondary current will cause relay contacts
C1 and C2 to close.
This will energize the trip coil by an auxiliary
dc source.
This will cause the three main line contacts to
open, thus interrupting the circuit.
Oil circuit breaker
Composed of a steel tank filled with
insulating oil
Three porcelain bushings channel the 3-
phase line currents to a set of fixed contacts.
Three movable contacts, actuated by an
insulated rod, open and close the circuit.
When the CB is closed, the line current
penetrates the tank by way of the porcelain
bushing, flows through the first fixed contact,
the movable contact, the second fixed
contact and then out by a second bushing.
Introduction
The electrical energy produced at the
generating stations is conveyed to consumers
through a network of transmission and
distribution systems.
In this lecture we shall study various
distribution systems.
Oil circuit breaker
When overload occurs, the tripping coil
releases a powerful spring that pulls the
insulated rod, causing the contacts to open.
As soon as the contacts separate, a violent
arc is created which volatilizes the
surrounding oil.
The pressure of the hot gases creates
turbulence around the contacts.
This causes cool oil to swirl around the arc,
thus extinguishing it shown below.
Other circuit breakers work on the same
principle except that the medium of
insulation is provided by other means such as
SF6, vacuum, compressed air etc.
Air-Break Switches
This switch is used to interrupt the exciting
current of transformers or moderate
capacitive currents of unloaded transmission
lines. They can not interrupt normal load
current.
Disconnecting Switches
these switches are unable to interrupt any
current. They must only be opened or closed
when the current is zero.
They are basically insulating switches,
enabling us to isolate CB, transformers,
transmission lines etc from a live network.
Surge Arresters
The surge arresters are used to limit the over-voltages
that occur across transformers and other electrical
apparatus due either to lightning or switching surges.
The upper end of the arrester is connected to the line
terminal that has to be protected, while the lower end is
solidly connected to the ground.
A surge arrester clips any voltage in excess of a
specified maximum by permitting a large current to get
diverted to ground and hence absorbs energy from
incoming surge.
The V-I characteristics of ideal surge arrester is therefor,
horizontal line whose level corresponds to the maximum
permissible surge voltage.
Surge Arresters
in practice, the V-I characteristics slopes
upward, but it is still considered to be
reasonably flat.
Surge Arresters
The earlier version of surge arresters are
composed of:
External porcelain shell (tube) containing
stacked discs made of silicon carbide, Air gaps,
Ionizers and coils.
Under normal conditions, air gaps prevent any
current from flowing through the tuber column.
When overvoltage occurs, the spark gaps break
down and surge discharges to ground.
Surge Arresters
The 50 Hz follow-through current is limited by
the resistance of the discs and the arc is
simultaneously stretched and cooled in a series of
arc chambers.
The arcs are extinguished and the arrester is
ready to protect the next voltage surge.
The discharge period is very short, rarely lasting
more than a fraction of a millisecond.
More modem type of surge arresters use ZnO
blocks without any gap or other auxiliary devices.
These metal-oxide arresters are largely used now.
Current limiting reactors
The MV bus in a substation usually energizes
several feeders, which carry power to regional
load centers surrounding the substation.
The output impedance of the MV bus is usually
very low.
If a short circuit occurs on one of the feeders,
the resulting short-circuit current could be very
high and disastrous. To prevent this from
happening, a current limiting reactor is
connected in series with each phase of the
feeder.
Current limiting reactors
The reactance must be high enough to keep
the current below the interrupting capacity of
the circuit breaker but not so high as to
produce a large voltage drop under normal
full-load conditions.
Grounding Switches
These are safety switches that ensure a
transmission line is definitely grounded while
any repair work is carried out.
The grounding switches are opened or closed
only when the lines are de-energized .
Distribution system
Definition- That part of a power system
which distributes electric power for local use
is known as distribution system.
Some Important Terms
Feeders: A conductor which connects the
sub-station to the area where power is to be
distributed.
Distributor: A conductor from which tapings
are taken to supply to the consumers.
Service mains: A service mains is generally a
small cable which connects the distributor to
the consumer’s terminals.
Classification of Distribution
Systems
Nature of current i.e. AC Distribution System
and DC Distribution System.
Scheme of connection:
a) Radial
b) Ring main
c) Inter-connected
Type of Construction: Overhead and under-
ground.
A.C. Distribution
Power is generated as 3-Phase AC.
Widely used throughout the world.
Preferred because voltage magnitude can
conveniently be changed using transformer.
DC Distribution
AC Power is converted to DC using rectifiers.
Changing voltage magnitude in DC Requires
expensive equipment.
Less common
Only used for specialized requirements e.g.
Electrochemical Processes.
DC Power can be stored in batteries.
DC Distribution
2-Wire DC Distribution 3-Wire DC Distribution
Connection Schemes
Radial System
Ring Main System
Interconnected System
Radial System
In this system, separate feeders radiate from
a single substation and feed the distributors
at one end only.
The radial system is employed only when
power is generated at low voltage and the
substation is located at the center of load.
Radial System
Radial System
Radial system is the simplest and cheapest
distribution circuit.
It has following drawbacks:
Uneven loading on the conductor.
Single power source, hence whole system
suffers in case of a fault.
Far end consumers suffer low voltage
problem due to voltage drop in the
conductor.
Ring Main System
In this system, the distributor forms a loop.
The circuit starts from the substation bus-
bars, makes a loop through the area to be
served, and returns to the substation.
Ring Main System
Ring Main System
Ring Main System has following advantages:
Less Voltage fluctuations.
More reliable because it has 2 current paths.
Less Losses.
Interconnected system
When the feeder is energized by 2 or more
generating stations, the system is called an
interconnected system.
Interconnected System
Interconnected System
Advantages:
It increases reliability.
Any area far from one generating station
during peak load hours can be fed from the
other generating station.
Reduces reserve capacity requirement.
Types of Distributors
Distributors fed at one end
Distributors fed at both ends
Distributors fed at the centre
Ring Distributors
Distributors fed at one end
In this type, the distributor is connected to
supply at one end and loads are taken at
different points along its length.
Distributors fed at one end
Distributors fed at one end
The current in various sections of the
distributors away from the feeding point goes
on decreasing.
The voltage across the loads away from the
feeding point goes on decreasing.
In case of fault, whole distributor needs to be
disconnected.
Distributors fed at both ends
In this type, the distributor is connected to
supply at both ends and loads are taken at
different points along its length.
The voltage at feeding points may or may not
be equal.
Distributors fed at both ends
Advantages
If fault occurs at one point, the supply from
other end can be continued.
Voltage regulation is improved
Ring Main Distributor
The distributor forms a loop in the area to be
served.
It is equivalent to straight distributor fed
from both ends with equal voltages.
Ring Main Distributor
Distributors fed at centre
In this type, the centre of the distributor is
connected to supply.
It is equivalent to 2 singly fed distributors
having a common feeding point.
Distributor fed at centre
Food For Thought
Why is power distributed at low voltages?
Why DC distribution is not widely used?
What is “ an AC system” and why use it?
Which distribution system is the best in
your opinion ?
Solved Examples