This document discusses different types of power system substation configurations, including single bus, double bus-double breaker, main and transfer bus, double bus-single breaker, ring bus, and breaker-and-a-half. It focuses on describing the key characteristics, advantages, disadvantages, and applications of the single bus, double bus-double breaker, and main and transfer bus arrangements.
Download as PPTX, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
37 views
Lecture 10
This document discusses different types of power system substation configurations, including single bus, double bus-double breaker, main and transfer bus, double bus-single breaker, ring bus, and breaker-and-a-half. It focuses on describing the key characteristics, advantages, disadvantages, and applications of the single bus, double bus-double breaker, and main and transfer bus arrangements.
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 42
Power System
Circuit Breakers and
Substations Lecture No. 10 Engr. Raheel Muzzammel Department of Electrical Engineering University of Lahore
Engr. Raheel Muzzammel 1
Air-Insulated Substations
Engr. Raheel Muzzammel 2
Bus/Switching Configurations • The following are the six types of arrangements commonly used: • Single bus
• Double bus–double breaker
• Main and transfer (inspection) bus
• Double bus–single breaker
• Ring bus
• Breaker-and-a-half
Engr. Raheel Muzzammel 3
Single Bus Arrangement • This is the simplest bus arrangement, a single bus and all connections directly to one bus (Figure). • Reliability of the single bus configuration is low: even with proper relay protection, a single bus failure on the main bus or between the main bus and circuit breakers will cause an outage of the entire facility. • With respect to maintenance of switching devices, an outage of the line they are connected to is required. • Furthermore, for a bus outage the entire facility must be de-energized. • This requires standby generation or switching loads to adjacent substations, if available, to minimize outages of loads supplied from this type of facility. Engr. Raheel Muzzammel 4 Single Bus Arrangement • Cost of a single bus arrangement is relatively low, but also is the operational flexibility; for example, • transfer of loads from one circuit to another would require additional switching devices outside the substation. • Line connections to a single bus arrangement are normally straight forward, since all lines are connected to the same main bus. • Therefore, lines can be connected on the main bus in areas closest to the direction of the departing line, thus mitigating lines crossing outside the substation.
Engr. Raheel Muzzammel 5
Single Bus Arrangement • Due to the low reliability, significant efforts when performing maintenance, and low operational flexibility, application of the single bus configuration should be limited to facilities with low load levels and low availability requirements. • Since single bus arrangement is normally just the initial stage of a substation development, when laying out the substation a designer should consider the ultimate configuration of the substation, such as where future supply lines, transformers, and bus sections will be added. • As loads increase, substation reliability and operational abilities can be improved with step additions to the facility, for example, a bus tie breaker to minimize load dropped due to bus outages. Engr. Raheel Muzzammel 6 Double Bus–Double Breaker Arrangement • The double bus–double breaker arrangement involves two breakers and two buses for each circuit (Figure). • With two breakers and two buses per circuit, a single bus failure can be isolated without interrupting any circuits or loads. • Furthermore, a circuit failure of one circuit will not interrupt other circuits or buses. • Therefore, reliability of this arrangement is extremely high. Engr. Raheel Muzzammel 7 Double Bus–Double Breaker Arrangement • Maintenance of switching devices in this arrangement is very easy, since switching devices can be taken out-of-service as needed and circuits can continue to operate with partial line relay protection and some line switching devices in-service, i.e., one of the two circuit breakers. • Obviously, with double the amount of switching devices and buses, cost will be substantially increased relative to other more simple bus configurations. • In addition, relaying is more complicated and more land is required, especially for low-profile substation configurations. • External line connections to a double breaker–double bus substation normally do not cause conflicts with each other, but may require substantial land area adjacent to the facility as this type of station expands. Engr. Raheel Muzzammel 8 Double Bus–Double Breaker Arrangement • This arrangement allows for operational flexibility; certain lines could be fed from one bus section by switching existing devices. • This bus configuration is applicable for loads requiring a high degree of reliability and minimum interruption time. • The double breaker–double bus configuration is expandable to various configurations, for example, a ring bus or breaker-and-a-half configurations.
Engr. Raheel Muzzammel 9
Main and Transfer Bus Arrangement • The main and transfer bus configuration connects all circuits between the main bus and a transfer bus (sometimes referred to as an inspection bus). • Some arrangements include a bus tie breaker and others simply utilize switches for the tie between the two buses (Figure). • This configuration is similar to the single bus arrangement; in that during normal operations, all circuits are connected to the main bus. • So the operating reliability is low; a main bus fault will de-energize all circuits. Engr. Raheel Muzzammel 10 Main and Transfer Bus Arrangement • However, the transfer bus is used to improve the maintenance process by moving the line of the circuit breaker to be maintained to the transfer bus. • Some systems are operated with the transfer bus normally de-energized. • When a circuit breaker needs to be maintained, the transfer bus is energized through the tie breaker. • Then the switch, nearest the transfer bus, on the circuit to be maintained is closed and its breaker and associated isolation switches are opened. • Thus transferring the line of the circuit breaker to be maintained to the bus tie breaker and avoiding interruption to the circuit load. Engr. Raheel Muzzammel 11 Main and Transfer Bus Arrangement • Without a bus tie breaker and only bus tie switches, there are two options. • The first option is by transferring the circuit to be maintained to one of the remaining circuits by closing that circuit’s switch (nearest to the transfer bus) and carrying both circuit loads on the one breaker. • This arrangement most likely will require special relay settings for the circuit breaker to carry the transferred load. • The second option is by transferring the circuit to be maintained directly to the main bus with no relay protection from the substation.
Engr. Raheel Muzzammel 12
Main and Transfer Bus Arrangement • Obviously in the latter arrangement, relay protection (recloser or fuse) immediately outside the substation should be considered to minimize faults on the maintained line circuit from causing extensive station outages. • The cost of the main and transfer bus arrangement is more than the single bus arrangement because of the added transfer bus and switching devices. • In addition, if a low-profile configuration is used, land requirements are substantially more.
Engr. Raheel Muzzammel 13
Main and Transfer Bus Arrangement • Connections of lines to the station should not be very complicated. • If a bus tie breaker is not installed, consideration as to normal line loading is important for transfers during maintenance. • If lines are normally operated at or close to their capability, loads will need to be transferred or temporary generators provided similar to the single bus arrangement maintenance scenario. • The main and transfer bus arrangement is an initial stage configuration, since a single main bus failure can cause an outage of the entire station. • As load levels at the station rise, consideration of a main bus tie breaker should be made to minimize the amount of load dropped for a single contingency. Engr. Raheel Muzzammel 14 Main and Transfer Bus Arrangement • Another operational capability of this configuration is that the main bus can be taken out-of-service without an outage to the circuits by supplying from the transfer bus, but obviously, relay protection (recloser or fuse) immediately outside the substation should be considered to minimize faults on any of the line circuit from causing station outages. • Application of this type of configuration should be limited to low reliability requirement situations.
Engr. Raheel Muzzammel 15
Double Bus–Single Breaker Arrangement • The double bus–single breaker arrangement connects each circuit to two buses, and there is a tie breaker between the buses. • With the tie breaker operated normally closed, it allows each circuit to be supplied from either bus via its switches. • Thus providing increased operating flexibility and improved reliability. • For example, a fault on one bus will not impact the other bus. • Operating the bus tie breaker normally open eliminates the advantages of the system and changes the configuration to a two single bus arrangement (Figure).
Engr. Raheel Muzzammel 16
Double Bus–Single Breaker Arrangement • Relay protection for this arrangement will be complex with the flexibility of transferring each circuit to either bus. • Operating procedures would need to be detailed to allow for various operating arrangements, with checks to ensure the in-service arrangements are correct. • A bus tie breaker failure will cause an outage of the entire station. • The double bus–single breaker arrangement with two buses and a tie breaker provides for some ease in maintenance, especially for bus maintenance, but maintenance of the line circuit breakers would still require switching and outages as described above for the single bus arrangement circuits. Engr. Raheel Muzzammel 17 Double Bus–Single Breaker Arrangement • The cost of this arrangement would be more than the single bus arrangement with the added bus and switching devices. • Once again, low-profile configuration of this arrangement would require more area. • In addition, bus and circuit crossings within the substation are more likely. • Application of this arrangement is best suited where load transfer and improved operating reliability are important. Though adding a transfer bus to improve maintenance could be considered, it would involve additional area and switching devices, which could increase the cost of the station.
Engr. Raheel Muzzammel 18
Ring Bus Arrangement • All breakers are arranged in a ring with circuits connected between two breakers. • From a reliability standpoint, this arrangement affords increased reliability to the circuits, since with properly operating relay protection, a fault on one bus section will only interrupt the circuit on that bus section and a fault on a circuit will not affect any other device (Figure). Engr. Raheel Muzzammel 19 Ring Bus Arrangement • Protective relaying for a ring bus will involve more complicated design and, potentially, more relays to protect a single circuit. • Keep in mind that bus and switching devices in a ring bus must all have the same ampacity, since current flow will change depending on the switching device’s operating position. • From a maintenance point of view, the ring bus provides good flexibility. • A breaker can be maintained without transferring or dropping load, since one of the two breakers can remain in-service and provide line protection while the other is being maintained. Engr. Raheel Muzzammel 20 Ring Bus Arrangement • Similarly, operating a ring bus facility gives the operator good flexibility since one circuit or bus section can be isolated without impacting the loads on another circuit. • Cost of the ring bus arrangement can be more expensive than a single bus, main bus and transfer, and the double bus–single breaker schemes since two breakers are required for each circuit, even though one is shared. • The ring bus arrangement is applicable to loads where reliability and availability of the circuit is a high priority.
Engr. Raheel Muzzammel 21
Ring Bus Arrangement • There are some disadvantages of this arrangement: • a “stuck breaker” event could cause an outage of the entire substation depending on the number of breakers in the ring, • expansion of the ring bus configuration can be limited due to the number of circuits that are physically feasible in this arrangement, and, • circuits into a ring bus to maintain a reliable configuration can cause extensive bus and line work. • For example, to ensure service reliability, a source circuit and a load circuit should always be next to one another. • Two source circuits adjacent to each other in a stuck breaker event could eliminate all sources to the station. • Therefore, a low-profile ring bus can command a lot of area. Engr. Raheel Muzzammel 22 Breaker-and-a-Half Arrangement • The breaker-and-a-half scheme is configured with a circuit between two breakers in a three-breaker line-up with two buses; thus, one-and-a-half breakers per circuit. In many cases, this is the next development stage of a ring bus arrangement (Figure). • Similar to the ring bus, this configuration provides good reliability; with proper operating relay protection, a single circuit failure will not interrupt any other circuits. • Furthermore, a bus section fault, unlike the ring bus, will not interrupt any circuit loads.
Engr. Raheel Muzzammel 23
Breaker-and-a-Half Arrangement • Maintenance as well is facilitated by this arrangement, since an entire bus and adjacent breakers can be maintained without transferring or dropping loads. • Relay protection is similar to the ring bus, and due to the additional devices, is more complex and costly than most of the previously reviewed arrangements. • The breaker-and-a-half arrangement can be expanded as needed. • By detailed planning of the ultimate substation expansion with this configuration, line conflicts outside the substation can be minimized.
Engr. Raheel Muzzammel 24
Breaker-and-a-Half Arrangement • Cost of this configuration is commensurate with the number of circuits, but based on the good reliability, operating flexibility, and ease of maintenance, the price can be justified. • Obviously, the area required for this type of arrangement is significant. • The higher the voltage, the more clearances required and area needed.
Engr. Raheel Muzzammel 25
Bus/Switching Configuration Comparison Table
Engr. Raheel Muzzammel 26
High-Voltage Switching Equipment
Engr. Raheel Muzzammel 27
Disconnect Switches • A disconnect switch is a mechanical device that conducts electrical current and provides an open point in a circuit for isolation of one of the following devices: • Circuit breakers • Circuit switchers • Power transformers • Capacitor banks • Reactors • Other substation equipment • They are designed for no-load switching, opening or closing circuits where negligible currents are made or interrupted (including capacitive current [line charging current] and resistive or inductive current [magnetizing current]), or when there is no significant voltage across the open terminals of the switch (loop splitting [parallel switching]). Engr. Raheel Muzzammel 28 Disconnect Switches • Disconnect switches are also installed to bypass breakers or other equipment for maintenance and can be used for bus sectionalizing. • Interlocking equipment is available to prevent operating sequence errors, which could cause substation equipment damage, by inhibiting operation of the disconnect switch until the load current has been Horizontally upright mounted disconnect switch interrupted by the appropriate equipment. Engr. Raheel Muzzammel 29 Disconnect Switches Vertical break switches are the most widely used disconnect switch design, are the most versatile disconnect switch design, can be installed on minimum phase spacing, are excellent for applications in ice environments due to their rotating blade design, and are excellent for installations in high fault current locations due to their contact design
Vertically mounted disconnect switch
Vertical break disconnect switch Engr. Raheel Muzzammel 30 Load Break Switches • A load break switch is a disconnect switch that has been equipped to provide breaking and making of specified currents. • This is accomplished by the addition of equipment that changes what the last points of metal-to-metal contact upon opening and the first points of metal-to-metal contact upon closing are, that increases the switching speed at which the last points of metal-to-metal contact part in air, or that confines the arcing to a chamber which contains a dielectric medium capable of interrupting the arc safely and reliably. • Arcing horns are the equipment added to disconnect switches to allow them to interrupt very small amounts of charging or magnetizing current.
Engr. Raheel Muzzammel 31
Load Break Switches
High-speed arcing horns on a vertical break switch.
Arcing horns on a vertical break switch.
Engr. Raheel Muzzammel 32
Load Break Switches • If the need for interrupting loop currents, load currents, or large amounts of line charging current exists, then a disconnect switch can be outfitted with an interrupter (using either sulfur hexafluoride [SF6] gas or vacuum as the interrupting medium) capable of performing these interrupting duties. Load break switch with SF6 interrupters.
Engr. Raheel Muzzammel 33
High-Speed Grounding Switches • Automatic high-speed grounding switches are applied for protection of power transformers when: • the cost of supplying other protective equipment is deemed unjustifiable and • the amount of system disturbance that the high-speed grounding switch creates is judged acceptable. • The switches are generally actuated by discharging a spring mechanism to provide the “high-speed” operation. • The grounding switch operates to provide a deliberate ground fault on one phase of the high-voltage bus supplying the power transformer, disrupting the normally balanced 120° phase shifted three-phase system by effectively removing one phase and causing the other two phases to become 180° phase shifted relative to each other. Engr. Raheel Muzzammel 34 High-Speed Grounding Switches • This system imbalance is remotely detected by protective relaying equipment that operates the transmission line breakers at the remote end of the line supplying the power transformer, tripping the circuit open to clear the fault. • This scheme also imposes a voltage interruption to all other loads connected between the remote circuit breakers and the power transformer as well as a transient spike to the protected power transformer, effectively shortening the transformer’s useful life. • The grounding switch scheme is dependent on the ability of the source transmission line relay protection scheme to recognize and clear the fault by opening the remote circuit breaker. • Clearing times are necessarily longer since the fault levels are not normally within the levels appropriate for an instantaneous trip response. • High-speed grounding switches are usually considered when relative fault levels are low.
Engr. Raheel Muzzammel 35
Power Fuses • Power fuses are a generally accepted means of protecting small power transformers (i.e., power transformers of 15 MVA and smaller), capacitor banks, potential transformers, and/or station service transformers. • The primary purpose of a power fuse is to provide interruption of permanent faults. • Power fuses are an economical alternative to circuit switcher or circuit breaker protection. • Fuse protection is generally limited to voltages from 15 to 69 kV but has been applied for the protection of equipment as large as 161 kV. Engr. Raheel Muzzammel 36 Power Fuses • To provide the greatest protective margin, it is necessary to use the smallest fuse rating possible. • The advantage of close fusing is the ability of the fuse unit to provide backup protection for some secondary faults. • For the common delta-wye-connected transformer, a fusing ratio of 1.0 would provide backup protection for a phase-to-ground fault as low as 230% of the secondary full-load rating. • Fusing ratio is defined as the ratio of the fuse rating to the transformer full-load current rating. • With low fusing ratios, the fuse may also provide backup protection for line-to- ground faults remote to the substation on the distribution, sub-transmission, or transmission network. Engr. Raheel Muzzammel 37 Power Fuses • The concern of unbalanced voltages in a three-phase system must be considered when selecting fusing. • The possibility of one or two fuses blowing must be reviewed. • Unbalanced voltages can cause tank heating in three-phase power transformers and overheating and damage to three-phase motor loads. • The potential for ferroresonance must be considered for some transformer configurations when using fusing.
Engr. Raheel Muzzammel 38
Power Fuses • Fuses are available in a number of time-to-melt and time-to-clear curves (standard, fast, medium, slow, and very slow) to provide coordination with other system protective equipment. • Fuses are not voltage critical; they may be applied at any voltage equal to or less than their rated voltage. • Fuses may not require additional structures as they are generally mounted on the incoming line structure and result in space savings in the substation layout.
Engr. Raheel Muzzammel 39
Circuit Switchers • Circuit switchers using SF6 gas interrupters are designed to provide three- phase interruption (solving the unbalanced voltage considerations) and to provide protection for transient overvoltage and load current overloads at a competitive cost between the costs of power fuses and circuit breakers. • Additionally, they can provide protection from power transformer faults based on differential, sudden pressure, and overcurrent relay schemes as well as critical operating constraints such as for low oil level, high oil or winding temperature, pressure relief device operation, etc. • Different model types, configurations, and vintages have different interrupting ratings and interrupting speeds.
Engr. Raheel Muzzammel 40
Circuit Switchers • Circuit switchers have been furnished for applications involving protection of power transformers, lines, cables, capacitor banks, and line connected or tertiary connected shunt reactors. • Circuit switchers can also be employed in series capacitor bypassing and for load/line/loop interrupting applications where fault-closing capability is required.
Engr. Raheel Muzzammel 41
Circuit Breakers • A circuit breaker is defined as “a mechanical switching device capable of making, carrying, and breaking currents under normal circuit conditions and also making, carrying, and breaking for a specified time, and breaking currents under specified abnormal conditions such as a short circuit”. • Details of Circuit breakers have already been discussed before.