Lecture - 6 - Axially Loaded Compression Members
Lecture - 6 - Axially Loaded Compression Members
Loaded Compression
Members
1
The Euler Formula
2
Example 5-1
a) A W10 x22 is used as a 15-ft long pin-connected column. Using the Euler
expression, determine the column’s critical load. Assume that the steel has
proportional limit of 36 ksi.
b) Repeat part (a) if the length is changed to 8 ft.
3
Example 5-1, cont.
4
Example 5-1, cont.
5
Example 5-1, cont.
6
End Restraint and Effective Length of Columns
7
Figure 5.4 Effective length (KL) for Columns
in braced frames (Sidesway prevented).
8
Figure 5.5
9
End Restraint and Effective Length of Columns,
cont.
See Table C-C2.2 of the AISC commentary for effective length factors.
10
Table 5.1 Approximate Values of Effective
Length Factor, K
11
TABLE 5.2: Width-to-Thickness Ratios: Compression Elements in
Members Subject to Axial Compression
12
TABLE 5.2: Width-to-Thickness Ratios: Compression Elements in Members
Subject to Axial Compression, cont.
13
TABLE 5.2: Width-to-Thickness Ratios: Compression Elements in Members
Subject to Axial Compression, cont.
14
TABLE 5.2: Width-to-Thickness Ratios: Compression Elements in Members
Subject to Axial Compression, cont.
15
Column Formulas
16
Column Formulas, cont.
17
Column Formulas, cont.
18
Example 5.2
a) Using the Column critical stress value in Table 4-22 of the manual,
determine the LRFD design strength cPn and the ASD allowable strength
Pn/c for the Column shown in Fig. 5.8, if a 50-ksi steel is used.
19
Figure 5.8
20
21
Example 5.2, cont.
22
Example 5.2, cont.
23
Example 5.2, cont.
24
Example 5.2, cont.
25
Example 5.2, cont.
26
Example 5.2, cont.
27
Example 5.2, cont.
28
Example 5.3
end supports.
29
Example 5.3, cont.
30
Example 5.3, cont.
31
Example 5.3, cont.
32
Example 5.3, cont.
33
Example 5.3, cont.
34
Example 5.3, cont.
35
Example 5.4
Determine the LRFD design strength cPn and the ASD allowable strength Pn/c
for the axially loaded Column shown in Fig. 5.9 if KL = 19 ft and 50 –ksi
Steel is used.
36
Figure 5.9
37
38
Example 5.4, cont.
39
Example 5.4, cont.
40
Example 5.4, cont.
41
Example 5.5
a) Determine the LRFD design strength cPn and the ASD allowable strength
Pn/c for 50 ksi axially loaded W14 x 90 shown in Fig. 5.10.
42
Example 5.5, cont.
The Shear centre is the point in the cross section of a member through which
the resultant of the transverse loads must pass so that no torsion will occur.
See Ch.10.
b) Repeat part (a), using the Column Table of Part 4 of the Manual.
43
Example 5.5, cont.
44
Example 5.5, cont.
45
Example 5.5, cont.
46
Example 5.5, cont.
47
Example 5.5, cont.
48
Example 5.5, cont.
49
Example 5.5, cont.
50
Example 5.5, cont.
51
Design of Axially Loaded
Compression Members
52
Example 6.1
Using Fy = 50 ksi, select the lightest W14 available for the service column
53
54
55
56
Example 6.2
Use the AISC column tables (both LRFD and ASD) for the designs to follow.
(a) Select the lightest W section available for the loads, steel, and KL of
Example 6-1. Fy = 50 ksi.
(b) Select the lightest satisfactory rectangular or square HSS sections for
the situation in part (a). Fy = 46 ksi.
(c) Select the lightest satisfactory round HSS section for the situation in
part (a). Fy = 42 ksi.
(d) Select the lightest satisfactory pipe section for the situation in part (a).
Fy = 35 ksi.
57
Solution
58
59
60
61
Columns Laterally Restrained in their Weaker Direction.
62
Figure 6.1 A column
laterally restrained at
mid-depth in its
weaker direction.
63
Example 6.3
Select the lightest available W12 section, using both LRFD and ASD methods
for the following conditions: Fy = 50 ksi, PD = 250 k, PL = 400 k. KXLX = 26
ft and Ky Ly = 13 ft.
64
Example 6.3, solution
65
66
67
Example 6.3, solution, cont.
68
69
Example 6.3, solution, cont.
70
Build-up Columns with Components in Contact
with Each Other
71
72
Figure 6.3 Column consisting
of two plates not connected to
each other.
73
Figure 6.4
Column
consisting
of two
plates fully
connected
to each
other.
74
Figure 6.5
Column
consisting of two
plates connected
at its ends only.
75
Figure 6.6
76
Example 6.4
You are to design a column for PD = 750 k and PL = 1000 k, using Fy = 50 ksi
and KL = 14 ft. A W12 x 120 (for which cPn = 1290 k and Pn/c = 856 k
from AISC manual, Table 4-1) is on hand. Design cover plates to be snug-
tight bolted at 6-in spacing to the W section, as shown in Fig. 6.7, to
enable the column to support the required load.
77
Figure 6.7 W section used as column with
cover plates.
78
Example 6.4, solution
79
Example 6.4, solution, cont.
80
Example 6.4, solution, cont.
81
Example 6.4, solution, cont.
82
Example 6.4, solution, cont.
83
Example 6.4, solution, cont.
84
Example 6.4, solution, cont.
85
86
Example 6.5
Select a pair of 12-in standard channels for the column shown in Fig. 6.8,
using Fy = 50 ksi. For connection purposes, the back-to-back distance of
the channels is to be 12 in. PD = 100 k and PL = 300 k. Consider both LRFD
and ASD procedures.
87
Figure 6.8
Column built up
from two
channels.
88
Example 6.5, solution
89
Example 6.5, solution, cont.
90
Example 6.5, solution, cont.
91
Example 6.5, solution, cont.
92
Example 6.5, solution, cont.
93
94
Example 6.5, solution, cont.
95
Single Angle Compression Members
To be used in 2D and the ends of the member are connected on the same side of
the gusset plates.
96
Example 6-7
Determine the Pn and the Pn/c values for a 10-ft long A36 angle 8 x 8 x
¾ with simple end connections, used in a planar truss. The other web
members meeting at the ends of this member are connected on the same
side of the gusset plates.
97
Example 6-7, solution
98
Example 6-7, solution, cont.
99
Base Plate for Concentrically
Loaded Columns
Plate Area
Design a base plate of A36 steel (Fy = 36 ksi) for a W12 x 65 column (Fy =
concrete has compressive strength f’c = 3 ksi, and the footing has the
dimensions 9 ft x 9 ft.
105
Example 7-5, solution
106
Example 7-5, solution, cont.
107
Example 7-5, solution, cont.
108
Example 7-5, solution, cont.
109
Example 7-5, solution, cont.
110
Fig. 7.15 simplifying the plate by making
it 16” x 16”
111
Example 7-5, solution, cont.
112
Example 7-5, solution, cont.
113
Example 7-5, solution, cont.
114
Example 7-6, base plate covers the entire footing
supports the loads PD = 200 k and PL = 450 k. Select an A36 plate (Fy =
36 ksi) to cover the entire area of the 3 ksi concrete pedestal
underneath.
115
Example 7-6, solution
116
Example 7-6, solution, cont.
117
Example 7-6, solution, cont.
118
Example 7-6, solution, cont.
119
Example 7-6, solution, cont.
120
Example 7-6, solution, cont.
121
Example 7-7, base plate smaller than the footing
with a specific amount.
122
Example 7-7, solution
123
Example 7-7, solution, cont.
124
125
Example 7-7, solution, cont.
126
Example 7-7, solution, cont.
127
Example 7-7, solution, cont.
128
Example 7-8, base plate for HSS column
0 in and consist of reinforced concrete with f’c = 4000 psi. Design a base
plate for this column with A36 steel (F y = 36 ksi and Fu = 58 ksi).
129
Example 7-8, solution
130
Example 7-8, solution
131
Example 7-8, solution, cont.
132
Example 7-8, solution, cont.
133
Example 7-8, solution, cont.
134