Troubleshooting in Syngas Plant
Troubleshooting in Syngas Plant
SYNGAS PLANT
Presentation by
S.B.V.PRASADA RAO
1
Objective
The aim of this presentation is to explain troubleshooting in the following units in
SYNGAS PLANT
Sales gas from ARAMCO
Feed gas compressor
Hydrogenation and de-sulfurization
Reformer
Process gas cooling
AMDEA wash unit
CO2 compressor
Temperature swing Adsorption
Cold box
CO compressor
Pressure swing Adsorption
PCRU
Note: Consider instrument / equipment malfunction is one of the probable cause in all
cases. So it was not mentioned every case.
What is troubleshooting ?
Definition
Troubleshooting is a process of identifying, planning and
resolving a problem.
Steps in troubleshooting process
1. Verify that a problem is actually exits
2. Isolate the cause of the problem
3. Correct the cause of the problem
4. Verify that the problem has been corrected
5. Follow up to prevent future problems.
SYNGAS PLANT BLOCK FLOW DIAGRAM
SALES GAS
FROM ARAMCO
CO2
HYDROGEN HP STEAM CO2
COMP
NG DE - STEAM CO2
comp SULFURIZATION REFORMING REMOVAL
SYN GAS
COLD BOX TSA
RAW HYDROGEN
RH2
CO
COMP PSA
5
Troubleshooting in sales gas from ARAMCO
6
Troubleshooting in sales gas from ARAMCO
Potential cause
1. 2008PV-3006A/B hunting
2. Spillback valve hunting
3. Loader valves problem
4. Reformer feed valve (2015FV-1001)hunting
Consequence
1. feed flow and pressure fluctuations to reformer
Action
1. take feed valve 2015FV-1001 in to manual mode and check it, still it is
fluctuating then check spillback valve and 2008PV-3006A/B valves in
the field.
2.If 2008PV-3006A/B is hunting then take other valve in to service and
isolate problematic control valve.
3.if spillback valve is hunting then change over the compressor.
11
Troubleshooting in Feed compressor
Discharge temperature is high
Potential cause
1. sale gas temperature is high from ARAMCO
2. Bypass cooler fouling
3. Cooling water temperature is high
4. High nitrogen % in sales gas
Consequence
1. chance to damage of compressor pickings
2. Chance to trip of the compressor (due to high high temperature)
Action
1. check cooling water supply temperature from UTOS, if require increase
cooling water flow to bypass cooler.
2. If bypass cooler is fouling then change over the compressor and clean
it.
3. If % of nitrogen is very high also discharge temperature will increase
(due to density change), check with ARAMCO and fix it.
12
HYDROGENATION & DE-SULFURIZATION UNIT
Troubleshooting in hydrogenation & de-sulfurization
16
Troubleshooting in hydrogenation & de-sulfurization
Consequence
a)Sulfur sticks on the nickel surface and forms
nickel sulfide
b)Can totally deactivate a reforming catalyst.
c)Giraffe neck can observe on reformer tube
Action
a)Steaming the catalyst will slowly strips off the
sulfur (Sulfur poisoning is reversible but may
loose some catalyst activity permanently).
b)If Sulfur outlet of de-sulfurization unit is
>0.1ppm, replace zinc oxide catalyst.
21
Troubleshooting in Reformer
Flame impingement
Potential cause
a) Blockage of port in burners
b)Miss alignment of burner
c)Fuel header pressure is too high
d)Poor burner design
e)Burner block damaged
Consequence
a)Direct impingement of flame on tube. This is the
worst since the tube wall temperature will be raised
can lead to rapid tube failure
b)Impingement of hot flue gas on the tube. Normally
observed as shimmering on the tube surface, will
lead to premature failure in long term.
Action
a)clean the burners and align the burners properly
b)Always try to keep all HP and LP fuel burners are in
service to avoid high fuel header pressure.
Note: Design tube metal temperature = 976°C
22
Troubleshooting in Reformer
23
Troubleshooting in Reformer
24
Troubleshooting in Reformer
25
Troubleshooting in Reformer
26
Troubleshooting in Reformer
Action
a) Confirm and shutdown the reformer.
29
Troubleshooting in Reformer
Potential cause
a) BFW failure from UTOS
b) Steam drum level transmitter mal function
c) Issue with 2087P-8701
Consequence
a) If steam drum level is very low chance to starvation of 20E-
1506A/B/C/D exchangers.
b) Salts will not be removed properly from steam drum if the level is
lower than the CBD Sparger.
Action
a) compare the steam drum level indication with local level gauges,
if any deviation calibrate the transmitters.
Note: maintain steam drum level around 55%.
34
Troubleshooting in Reformer
Combustion air fan vibrations are high
Potential cause
1)Suction filter DP high
2)High combustion air flow ( more than design)
3)Back pressure from reformer box.
4)Back pressure due to combustion air distribution header valves throttled or closed
5)Lube oil header pressure low
6)Lube oil temperature high
7)Moisture in lube oil
8)Vibration probe/communication issue
9)Improper supports.
10)
Other mechanical problems
Consequence
1)Leads to trip of FD fan on high high vibrations.
2)Leads to damage of equipment.
35
Troubleshooting in Reformer
Combustion air fan vibrations are high
Action
1)If vibrations are high, first reduce combustion air flow
2)If suction filter (20F-1501) high DP, reduce plant load and replace the filter
elements during shutdown.
3)Check reformer box pressure and ID fan condition.
4)Check opening combustion air distribution valves, if any throttled condition
open it.
5)If lube heeder pressure is low, then check filter DP, pump discharge
pressure/PCV condition/lube oil console level.
6)If require change over lube oil filter/ change over the lube oil pump.
7)Check lube oil temperature, if require open cooling water to lube oil cooler.
8)Check lube oil heater malfunction if any.
9)Confirm vibrations by inspection team.
10)
If any problem with vibration probe/ communication ,fix it
11)
Check the supports and other mechanical problem
36
Troubleshooting in Reformer
Phosphate in steam drum CBD
Free Phosphate low Free Phosphate high
Potential cause Potential cause
• Low phosphate dosing High phosphate dosing
• CBD opening high Consequence
Consequence • high PH
• Salts will not be removed • caustic corrosion
properly. • high conductivity
• Scaling will deposit in Action
exchanger and turbine • Adjust phosphate pump
blades stroke and CBD opening
Action depends on CBD analysis.
• Adjust phosphate pump
stroke and CBD opening
depends on CBD analysis.
37
Troubleshooting in Process gas cooling
43
Troubleshooting in AMDEA wash unit
Regeneration gas over head separator level high
Potential cause
1)Poor pumping by 20P-2502A/B
2)Regenerator top temperature high
3)Regenerator flooding
4)Regenerator top temperature high
5)Regenerator pressure low
Consequence
1)Chace to trip CO2 compressor due to level 2025LAHH-2006
2)If the flooding too much then chance to go AMDEA in to CO2
compressor
Action
1)Check reflux pump condition, if require changer over the pump or run
both pumps till the level comes in to range
2)If regenerator temperature is high then reduce heat input for reboiler.
3)If regenerator DP is high, add antifoam.
4)If require reduce plant to control regenerator flooding.
44
CO2 COMPRESSOR
Troubleshooting in CO2 compressor
Suction pressure low 2025PI-3801
Potential cause
1)mal function of suction guide vane valve
2)suction strainer block
3)Suction Check valve at struck
Consequence
1) If the compressor suction pressure is low, compressor will surge.
Action
1) Check the opening of the suction guide vane in the field, if there is any
deviation in output or control valve is not operable then shut down and fix it.
2) If the compressor could not able to develop pressure / flow due to suction
strainer high DP (>0.1bar), stop the compressor and clean the strainer.
3) If there is no strainer DP, suction guide vane functioning is ok, CO2 is venting
in the suction through 2025PV-3021B but the suction pressure is low that
means compressor suction check is stuck. Stop the compressor and inspect
the check valve function.
46
Troubleshooting in CO2 compressor
Suction / Inter stage temperatures are high
Potential cause
1) Cooling water supply temperature is high
2) 20-2504 / Inter stage coolers exchangers fouling.
Consequence
1) If the suction temperature/inter stage temperatures are high then mass
flow through the compressor will come down which leads to surging of
the compressor.
Action
1) Check cooling water supply temperature and pressure from UTOS
2) If required open cooling water to inter stage coolers and 20E-2504.
3) If the temperatures are not come in to range then reduce the load on the
compressor
4) If the exchangers are fouling then check condition of the compressor and
if required shut down the compressor and clean the exchangers.
47
Troubleshooting in CO2 compressor
Discharge pressure is low (2025PI-3807)
Potential cause
1.Compressor suction pressure is low
2.CO2 density low ( due to 20E-2503 leak or 2030LV-2601 &2689 passing)
3.Mal functioning of guide vane opening/spill back valve/anti-surge valve
Consequence
1.Could not able to supply CO2 to reformer
2.Seal gas flows will come down which lead to damage of compressor seals.
Action
1.Check the suction pressure , if it is low take actions according to above mentioned trouble shooting
2.Check seal gas flows, if there is no seal gas flow to any stage , take shut down of the compressor.
3.Check all indications which are going to CCC, if any deviation, fix it.
4.Check the opening of anti-surge valve; spill back valves are matching with controllers outputs. If any
deviation fix it.
5.If 20E-2503 (re-boiler) leak then syngas will passing in to CO2. Confirm the passing by lab sample. If
the passing high then compressor could not able to develop the pressure due to low density. Shut
down AMINE unit and fix the passing.
6.Check 20V-3001 &3002 physical levels in the field, if any deviation fix it.
48
Troubleshooting in CO2 compressor
Discharge pressure is high (2025PI-3807)
Potential cause
1) Mal functioning of guide vane valve / anti-surge valve
2) Inter stage temperatures are too high
3) Sudden back pressure from reformer
Consequence
1) Leads to surging of the compressor
Action
1) Check opening of guide vane and anti surge valve, if any deviation fix
it.
2) If inter stage temperatures are high, take according to above
mentioned troubleshooting.
49
Troubleshooting in CO2 compressor
50
Troubleshooting in CO2 compressor
Consequence
1. Compressor surging will leads damaging of compressor internal
parts.
Action
1. according to root cause take actions as mentioned in related
trouble shootings.
2. Check all indications which are going to CCC, if any devication, fix it.
3. IF the compressor is surging it will trip automatically by CCC, if not
take immediate shutdown of compressor.
51
Troubleshooting in CO2 compressor
Low seal gas flow to primary seals
Potential cause
1) Seal gas filter DP high
2) Compressor discharge pressure low
3) High level in seal gas separator
4) Inter stage separator levels malfunction.
Consequence
1) Low seal gas flow leads to damaging of seals.
Action
1) If seal gas filter DP is >1.0 bar, change over the filter.
2) Check compressor discharge pressure, if it is low then take actions according to
above mentioned trouble shooting.
3) check seal gas separator level is high, if it is high, drain it.
4) If water is coming in the seal gas separator then check inter stage temperatures,
physical levels of inter stage secretors.
5) Adjust seal gas flows to individual seals.
52
Troubleshooting in CO2 compressor
Potential cause
1) Nitrogen header pressure low
Consequence
1) Low seal gas flow leads to damaging of seals.
2) Chace to enter lube oil in to seals
Action
1) Compressor will trip if nitrogen pressure is <0.1bar
2) Adjust seal gas flows to individual seals
3) Check seal leak off pressures.
53
Troubleshooting in CO2 compressor
Bearings temperature are high
Potential cause
1) Lube oil header pressure low
2) Lube oil header temperature is high
3) Moisture in lube oil
4) Fouling of lube coolers.
5) Lube oil quality (viscosity)
6) Other mechanical problems
Consequence
1) Leads to damage of bearings
2) Compressor vibrations will increase
Action
1) Check lube oil filter DP, if it is > 1.0bar, change over the filter.
2) Still header pressure is low , check PCV functioning.
3) If lube oil header temperature is high, increase cooling water to lube oil coolers or if require
change over lube oil cooler
4) Check if any lube oil heater mal function.
5) Check lube oil quality by lab ( moisture and viscosity)
6) If moisture is high, connect centrifuge to lube oil console.
7) If any other quality problems, replace the oil.
54
TEMPERATURE SWING ADSORPTION (TSA)
Troubleshooting in TSA
High CO2 at TSA outlet
Potential cause
1)TSA inlet CO2 slip (2030AI-5001A) high (>20ppm)
Consequence
1)CO2 will form dry ice ,it will clog the flow/reduced heat transfer/damage of Cold Box
internal equipment (Exchangers/Process Lines etc.,)
Action
1)Check and Confirm that TSA inlet CO2 Slip (2030AI-5001) is normal (< 20 PPM)
2)if CO2 slip exit TSA is increasing, Reduce Plant load,
3)Monitor Cold Box Process Gas Exchangers DP (2035PDI-3617A/B) in Syngas Path, if it
is increasing then immediately reduce load on the cold box
4)Reduce TSA operation factor/CO2 operation factor (2030HIC-6053/6055) by 0.01 in
small decrements.
5)Take Offline TSA inlet and Outlet samples and Compare with Online Analyzers
(2030AI-5001A/B)
6) Monitor TSA outlet CO2 slip (2030AI-5001B) continuously.
7)If CO2 slip is not decreasing exit TSA unit then stop TSA Unit & cold box and fix the
problem in AMDEA unit, then restart TSA safely.
56
Troubleshooting in TSA
High moisture at TSA outlet
Potential cause
1)TSA inlet temperature high.
2)2030V-3001 level high.
Consequence
1)moisture will form ice inside Cold Box Process Lines and it will clog the flow/reduced
heat transfer/damage of Cold Box internal equipment (Exchangers/Process Lines
etc.,)
Action
1)check 2030V-3001 level in filed level gauge, if any deviation fix it.
2)Check functioning of 2030LV-2601
3)If TSA inlet temperature is more than normal operating temperature then increase
cooling water flow to 20E-3001
4)Take TSA outlet sample and Compare with Online Analyzers .
5)Monitor Cold Box Process Gas Exchangers DP (2035PDI-3617A/B) across Syngas Path,
if it is increasing then immediately reduce load on the cold box.
57
Troubleshooting in TSA
Potential cause
• Mal functioning of any control valve in skid.
Consequence
• Regeneration sequence will step time out, leads to shutdown of TSA
unit.
Action
• Check and confirm the position of defected TSA skid valves status in
field and DCS are same. If not, call Maintenance immediately and fix it.
58
Troubleshooting in TSA
Potential cause
• Dust from TSA desiccant
• Indication mal function.
• TSA bed collapse
Consequence
• Cold box feed will come down.
Action
• Change over the filter.
• After change over filter also DP high with new filter then confirm the
bed collapse and shut down the plant.
60
COLD BOX
Troubleshooting in Cold Box
Potential cause
1) High moisture in TSA outlet syngas
2) High CO2 in TSA outlet syngas
Consequence
1) Ice / dry ice formation in 20E-3501A/B which leads blockage of syngas
stream.
Action
1) If moisture /CO2 is high in syngas to cold box, take actions as
mentioned in the respective troubleshooting.
2) If DP is >500 mbar, cutoff syngas to cold box and derime the cold box
62
Troubleshooting in Cold Box
Potential cause
• Extreme cooling in cold box
Consequence
• Methane will solidify If temperature is < -182°C
Action
• Control the cooling effect in cold box by reducing expander
speed, methane purge, liquid nitrogen.
• If methane solidifies , flow will be restricted ,then warm that
stream till get all temperatures normal.
63
Troubleshooting in Cold Box
Raw Hydrogen purity low (<95%)
Potential cause
1) Syngas temperature high at inlet to methane wash column (>-176°C)
2) Low Methane reflux flow to methane wash column (2035FIC-1679)
3) 3rd column bottom temperature low (<-145°C)
4) Liquid CO stand pipe level low
Consequence
1) Effect raw hydrogen purity.
2) Loss of CO production
Action
1) maintain syngas inlet temperature (2035TI-4627) to methane wash
column ~ -176°C to -178°C
2) If methane reflux is low then increase off set value 2000HIC-6298 in ALC.
3) maintain 3rd column bottom temperature ~ -144° to -145°C by adjusting
2035FIC1658/2035FIC1693/2035HIC2650A.
4) Maintain liquid CO stand pipe level to get 20E-2503 temperatures.
64
Troubleshooting in Cold Box
High CO in cold box tail gas (>20%)
Potential cause
1) Low Methane reflux flow to hydrogen stripper(2035FIC-1678)
2) Hydrogen stripper bottom temperate high (>-155°C)
3) 3rd column bottom temperature low (<-145°C)
4) Excess nitrogen purge flow
Consequence
1) Loss of CO production to tail gas
Action
1) Maintain hydrogen stripper temperature profile by 2035HIC-4639/2035FIC-
1657.
2) Maintain sufficient methane reflux flow to hydrogen stripper
3) maintain 3rd column bottom temperature ~ -144° to -145°C by adjusting
2035FIC1658/2035FIC1693/2035HIC2650A.
4) Adjust nitrogen purge from 20C-3504 according to 2035AI-5003C
5) If require reduce LP CO flow to 20C-3504.
65
Troubleshooting in Cold Box
Methane wash column DP high (2035PDI-3633)
Potential cause
1) 20C-3501 bottom level very high ( 2035LIC-2635A/2636A)
2) Excess methane reflux flow (2035FIC-1679)
Consequence
1) Liquid will carry over through raw hydrogen stream.
2) Chance to damage of beds in methane wash column)
Action
1) Check opening and flow of 2035FIC-1679), if it is high reduce it.
2) If bottom level transmitters are mal function, calibrate it.
66
Troubleshooting in Cold Box
Hydrogen stripping column DP high (2035PDI-3649)
Potential cause
1) 20C-3502 bottom level very high ( 2035LIC-2650)
2) Excess methane reflux flow (2035FIC-1678)
Consequence
1) Liquid will carry over through tail gas.
2) Chance to damage of beds in hydrogen stripping column)
Action
1) Check opening and flow of 2035FIC-1678), if it is high reduce it.
2) If bottom level transmitters are mal function, calibrate it.
67
Troubleshooting in Cold Box
Hydrogen stripping column bottom temp. low (<-160°C)
Potential cause
1) Less re-boiling flow (2035FIC-1657)
2) Stripper feed temperature low (2035TIC-4639)
Consequence
1) Dissolved hydrogen will escape to CO/CH4 column)
Action
1) Adjust CO re-boiling flow
2) Increase stripper feed temperature (2035TIC-4639)
68
Troubleshooting in Cold Box
CO/CH4 column DP high (2035PDI-3668)
Potential cause
1) 20C-3502 bottom level very high ( 2035LIC-2673A/B)
2) Hydrogen stripping column bottom temperature low
Consequence
1) Methane will carry over to CO/N2 column.
2) Chance to damage of beds in CO/CH4 column)
Action
1) If bottom level transmitters are mal function, calibrate it.
2) Maintain hydrogen stripping column bottom temperature ≈ -158°C
69
Troubleshooting in Cold Box
CO/CH4 column bottom temperature low (<-145°C)
Potential cause
1) Low CO re-boiling flow (2035FIC-1658)
2) High reflux flow (2035FIC-1693)
Consequence
1) Loss of production as CO will carry over to cold box tail gas.
2) Raw hydrogen purity will effect due to high CO in liquid methane.
Action
1) Adjust reflux flow through 2035FIC-1693.
2) Adjust re-boiling flow 2035FIC-1658)
3) Adjust feed ratio 2035HIC-2650A.
4) Maintain column bottom temperature around -144°C.
70
Troubleshooting in Cold Box
CO/N2 column pressure low
Potential cause
1) High nitrogen purge flow (2035FIC-1698)
2) Mal function of purge flow indication.
3) Mal function of pressure indication (2035PIC-3698)
4) %Nitrogen in sales gas is very low.
Consequence
1) Methane pump suction head will effect.
2) Methane will carry over to CO/N2 column.
3) CO/CH4 column bottom level come down
Action
1) Check nitrogen purge flow and column pressure.
2) If nitrogen in sales gas is very low and CO/N2 column pressure
3) Adjust 2035PDIC-3685.
4) could not able to control then inject required nitrogen to CO/N2 column through
2035FIC-1400.
71
Troubleshooting in Cold Box
CO/N2 column DP high
Potential cause
1) Column bottom level high (2035LIC-2690)
2) High LP CO re-boiling flow (2035FIC-1620)
3) Mal function of 2035PDV-3685.
Consequence
1) CO will carry over through nitrogen purge
2) Column beds will damage
Action
1) Check bottom level of the column 2035LIC-2690, if required calibrate
it.
2) Adjust LP CO re-boiling flow (2035FIC-1620)
72
Troubleshooting in Cold Box
Methane pump is not developing pressure
Potential cause
1) CO/CH4 column bottom level low / mal function
2) CO/CH4 column bottom temperature high
3) Suction strainer blockage.
4) Pump suction temperature high due to poor insulation.
5) Suction 2035XV-6674 mal function.
6) Vapor lock.
7) Minimum flow valve mal function.
8) Other mechanical problems.
Consequence
1) Cloud not able to pump liquid methane to 1st , 2nd columns & purge.
Action
1) Check CO/CH4 bottom level, if required calibrate it.
2) Check 2035XV-6674 and minimum flow control valve.
3) Check pump suction temperature, check column bottom temperature.
4) Bleed the vapor lock through pump discharge PSV bypass valve.
5) Change over the pump.
6) Identify other mechanical problems if any.
73
CO COMPRESSOR
Troubleshooting in CO compressor
Inter stage temperature are high
Potential cause
1) Cooling water supply temperature is high
2) Inter stage coolers exchangers fouling.
Consequence
1) inter stage temperatures are high then mass flow through the compressor
will come down which leads to surging of the compressor.
2) Leads to trip of compressor with high discharge temperatures
3) Chance to carbon formation if the temperature is >125°C
Action
1) Check cooling water supply temperature and pressure from UTOS
2) If required increase cooling water flow to inter stage coolers
3) If the temperatures are not come in to range then reduce the load on the
compressor
4) If the exchangers are fouling then check condition of the compressor and if
required shut down the compressor and clean the exchangers.
75
Troubleshooting in CO compressor
Discharge pressure low 2035PI-3809/12
Potential cause
1)Low suction pressure
2)Guide vane valves (2035PIC-3801/02/09/12) malfunction
3)Anti surge valves (2035FV-1801/02/03) malfunction
4)Mal function of parameters which are going to CCC
5)Suction strainers blockage (1st/ 3rd/6th stages)
6)Gas density low
7)3rd /6th suction check valves struck
Consequence
1)Could not able to supply CO to OXO gas
2)Insufficient seal gas flows to primary seals witch leads damage of seals.
76
Troubleshooting in CO compressor
Discharge pressure low 2035PI-3809/12
Action
1)Check suction pressure of the compressor, adjust anti-surge valves
opening according to surge deviation.
2)Check opening of all guide vanes and ASV n field, if any deviation, fix it.
3)Check all parameters which are going to CCC, if any deviation fix it.
4)Check suction strainers DP, if it is high and sufficient flow could not able
to establish thorough compressor then take shutdown and clean the
strainers.
5)If any hydrogen is passing to 1st suction of the compressor then gas
density will change, keep isolate 2035PV-3004A during normal operation.
6)If require check gas sample by lab to confirm any exchangers leaking in
cold box.
7)Check if any check valves are struck at 3rd and 6th suction by comparing
the upstream and down stream pressures.
77
Troubleshooting in CO compressor
CO compressor surging
Potential cause
1.High suction temperature
2.Low suction pressure
3.Inter stage temperatures are high
4.High discharge pressure
5.Less mass flow though compressor
6.CO density low
7. 2nd /5th /6th discharge flow transmitters wrong indication
8.Anti-surge valve malfunction
9.Guide vane valves (2035PIC-3801/02/09/12) malfunction
Consequence
1.Compressor surging will leads damaging of compressor internal parts.
Action
1.according to root cause take actions as mentioned in related troubleshooting.
2.IF the compressor is surging it will trip automatically by CCC, if not take
immediate shutdown of compressor.
Troubleshooting in CO compressor
Potential cause
1)Lube oil header pressure low
2)Lube oil header temperature is high
3)Moisture in lube oil
4)Fouling of lube coolers.
5)Lube oil quality (viscosity)
6)Mechanical problems
Consequence
1)Leads to damage of bearings
2)Compressor vibrations will increase
Troubleshooting in CO compressor
Action
1)Check lube oil filter DP, if it is > 1.0bar, change over the filter.
2)Still header pressure is low , check PCV functioning.
3)If lube oil header temperature is high, increase cooling water to
lube oil coolers or if required change over the cooler
4)Check if any lube oil heater is mal function.
5)Check lube oil quality by lab ( moisture and viscosity)
6)If moisture is high, connect centrifuge to lube oil console.
7)If any other quality problems, replace the oil.
Troubleshooting in CO compressor
87
Troubleshooting in PCRU
Consequences
• Vaporizer HH level leads to stop 2087P-8702 and closes 2087LV-2002
• Carry over of water to process steam
Action
• Check 2087LV-2002 opening in field, if any devotion, control the level by
throttling its upstream isolation valve.
• Check vaporizer level field, if any deviation fix it.
• Check HP steam flow valve 2087FV-1001, if any issue use its bypass valve.
89
Questions ?
PRASADA RAO