Fault Current Flow Through Earth Return Path
Fault Current Flow Through Earth Return Path
An earth fault occurs Fault current flow through earth return path.
path
Like most of the faults, Occurrence of earth fault reducing circuit Impedance to
a small value in addition of flow of current in earth return path.
path
1
Restricted Earth Fault: (Cont)
Over-current faults short-circuit faults
short winding close to neutral point + current flow in transformer’s earth return
path local overheating
2
Restricted Earth Fault Protection:
REF terminology IEC domain.
The net ground differential current earth fault relay feed detection of
internal winding to ground fault.
In transformers, Restricted Earth Fault relays are used to detect internal earth
faults in a given winding more sensitively than overall transformer differential
Protection is able to do.
3
Restricted Earth Fault: (Cont)
Question arises:
Answer is:
4
Restricted Earth Fault: (Cont)
Basic Concept: (Cont)
internal
Given isearth
the graph
fault
of a generic differential3
flow of very
low
relay.current in the transformer’s
earth return path. Operate
Fault in Operate region relay operation
2
o pe
I diff Sl
%
This kind of fault somewhere in K2
Restrain region of main diff protec 1
As shown,
Restrain
Basic Sensitivity
lope
K1% S
Internal faults Detection involving
earth need of REF protection. 0 1 2 3 4
I restraining
5
Restricted Earth Fault: (Cont)
Restricted Earth Fault is a type of earth fault in which
Protection is restricted to
by the CTs.
6
Restricted Earth Fault Protection:
Basic Concept:
Breaker Breaker
Fault
Suppose
REF relaytransformer
will detect these
comestypes
across
of internal
an internal
faults
earth
involving
fault near
earth
toifneutral
current
level is
point of more
WYE than
connected
the basic
winding,
sensitivity
whichlevel
causes
of relay.
a flow of fault current,
Based on
whose magnitude
the fault depends
level, transformer
on GND impedance
tripping canvalue
be taken.
and fault position
w.r.to neutral point.
7
Restricted Earth Fault: (Cont)
Basic Concept:
Winding
30%-35%
Rg
internal
Resultantearth
primary
fault current
close towill
neutral
be negligible
point of WYE
for faults
connected
on the lower winding
30% of theflow
winding
of fault current,
Resultant diff
current may be below the slope threshold of main
Magnitude
diff protection
of fault
fault
current
undetected.
depends on
1. GND impedance value
2. fault position w.r.to neutral point.
8
Restricted Earth Fault Protection:
9
Restricted Earth Fault Protection:
Low impedance REF Protection:
Low impedance differential relay Overcurrent differential element
Current Operated
Suppose
External Ph-Ph fault No neutral current + No GND current
If at this stage
One or more CTs saturate Relay mal operation
10
Restricted Earth Fault Protection:
Low impedance REF Protection:
That’s why……….
Low impedance differential relay More focus on relay settings
Ensures protection stability during
Required restraining signals
CT saturation conditions
11
Restricted Earth Fault Protection:
High Impedance REF Protection:
High Impedance relay Simple + fast + low relaying cost
Relay Settings:
Settings should contemplate the possibility of CT saturation conditions
12
Restricted Earth Fault Protection:
High Impedance REF Protection:
METROSIL:
13
Earth Fault Protection
And applications
x
IP
PR R
IF
IF 0.8
0.7
0.6
51 0.5
Over Current 0.4
Relay
0.3 Fault
Current
0.2
Delta Side
0.1
x p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
x p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
If as multiple
of IF.L.
10
IF
9 IF
8
7
6
IP IN 5 IP
4
3
2
1
IN
p.u..
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
51N 51 51 51
51N 51 51 51
51N
Can provide better sensitivity (C.T. ratio not related to full load
current Improved “effective” setting)
Provides back up protection for transformer and system
17th March 2007
Restricted Earth Fault Protection
Star Winding
Protected
Zone
REF
A B C N
LV restricted E/F
protection trips
both HV and LV breaker
A B C N
LV restricted E/F
protection trips
both HV and LV breaker
Source
Protected zone
REF
Protected
Circuit
ZM RCT RCT ZM
RL IF RL
IS
VS
RST
R
RL RL
RST = (VS/IS) – RR
1MVA
(5%) 1600/1
11000V 415V Calculate :
RCT = 4.9
1) Setting voltage (VS)
80MV
2) Value of stabilising
A
resistor required
3) Effective setting
4) Peak voltage developed
1600/1 RS by CT’s for internal fault
RCT = 4.8 IS = 0.1
Amp
2 Core 7/0.67mm
(7.41/km)
100m Long
1.6
(multiply by Kv to obtain rms
“B” Weber/m2 (Tesla)
Kv Ki
secondary volts)
1.2
0.4
“H” AT/mm
(multiply by Ki to obtain total
exciting current in Amps)
‘Earth’ CT
Flux density at 93.6V = 93.6/236 = 0.396 Tesla
From graph, mag. Force at 0.396 Tesla = 0.012 AT/mm
Mag. Current = 0.012 x 0.275 = 0.0033 Amps