Bernal - Engineering Utilities 2
Bernal - Engineering Utilities 2
minimum required
size of distribution
lines of a building
plumbing system
LIMUEL ROY S. BERNAL
PLAN
ONE-STOREY RESISDENTIAL
PLAN
ONE-STOREY RESISDENTIAL
PLAN
ONE-STOREY RESISDENTIAL
1 WATER CLOSET
1 LAVATORY
1 KITCHEN SINK
LENGTH= 9m
Compute the total water demand
P= Pave. - Pstatic
6.895 kPA
40 psi x = 275.8 kPA
1 psi
P=Pave. - Pstatic
P= 275.8 kPa
Determine the Pipe size with the aid of
Table 6-6
1. Choose the table based on the pressure ranger where the net pressure at the
water meter will fall.
2. Select the length column which is equal to or greater than the required length
3. Follow down the column to a fixture unit value equal or greater than the total
number of fixture units required by the installation.
P= Pave. - Pstatic
6.895 kPA
40 psi x = 275.8 kPA
1 psi
P=Pave. - Pstatic
P= 275.8 kPa
EXAMPLE 1
Design the pipe size for 2-story commercial building having 5 water closet (Flush
Tank), 5 lavatories, 2 Bathtubs, 3 Kitchen sink, 10 urinals(Flush Tank). Story
height is 3 meters. Pressure in the water main is 320kPa. And the length of the
pipe is 27 meters.