PROTECTION RELAY
RUSTINA DEVY – ENGINERING DEPARTMENT – PT. WIKA
RDY
HV SUBSTATION PROTECTION RELAY
COMMON SCHEME IN PLN’s SUBSTATIONS (1)
FOR TRANSFORMER
COMMON
MAIN PROTECTION
PANEL
87T : Transformer Differential 87 CHECK
87N : Restricted Earth Fault ( ≥ 50 MVA) 87 BUS
25 : Synchro Check
METERING
BACK-UP PROTECTION
CONTROL
50/51 : Instataneous Over Current PANEL
CB
50N/51N : Time Over Current
50BF : Circuit Breaker Failure
SUPERVISION & AUXILIARY DS-2 DS-1
TCS : Trip Circuit Supervision
86 : Lockout Relay
PROTECTION PANEL DOUBLE BUSES SINGLE BREAKER
RDY
HV SUBSTATION PROTECTION RELAY
COMMON SCHEME IN PLN’s SUBSTATIONS (3)
MAIN PROTECTION
87A : Zone A Busbar Protection
METERING
87B : Zone B Busbar Protection
CONTROL
87C : Check Zone Busbar Protection PANEL
25 : Synchro Check
BACK-UP PROTECTION CB
50/51 : Instataneous Over Current
50N/51N : Time Over Current
DS-1 DS-2
50BF : Circuit Breaker Failure
SUPERVISION & AUXILIARY
TCS : Trip Circuit Supervision
86 : Lockout Relay DOUBLE BUSES SINGLE BREAKER
PROTECTION PANEL RDY
HV SUBSTATION PROTECTION RELAY
DISTANCE PROTECTION
X Y A B W Z
RDY
HV SUBSTATION PROTECTION RELAY
DISTANCE PRORECTION SCHEME
DIRECT INTERTRIP
21
Z1/Z2 Z3
S
+ to other end substation
t3 R
21 : Distance Protection
Z1 : Zone 1
TRIPPING CIRCUIT
Z2 : Zone 2
Z3 : Zone 3
RDY S : Send
R : Receive
HV SUBSTATION PROTECTION RELAY
DISTANCE PRORECTION SCHEME
21
Z1 Z2 Z3
S
t2 to other end substation
R
t3
21 : Distance Protection
Z1 : Zone 1
TRIPPING CIRCUIT Z2 : Zone 2
Z3 : Zone 3
S : Send
RDY R : Receive
HV SUBSTATION PROTECTION RELAY
DISTANCE PRORECTION SCHEME
21
Z1 Z3
S
t3
to other end substation
R
21 : Distance Protection
Z1 : Zone 1
TRIPPING CIRCUIT Z2 : Zone 2
Z3 : Zone 3
S : Send
RDY R : Receive
HV SUBSTATION PROTECTION RELAY
DIRECTIONAL OVER CURRENT / DIRECTIONAL EARTH FAULT
A B C
67/67N
BACWARD DIRECTION DIRECTION FORWARD DIRECTION
RDY
HV SUBSTATION PROTECTION RELAY
DIRECTIONAL OVER CURRENT / DIRECTIONAL EARTH FAULT
X
A C
Note:
RDY
HV SUBSTATION PROTECTION RELAY
CHECK SYNCHRO RELAY (25)
FUNCTIONS
VT or CVT LINE
VT BUS
DL- LB √
LB- LL √
RDY
HV SUBSTATION PROTECTION RELAY
BREAKER FAILURE (50BF)
PURPOSE
X
A
TRIP ORDER C TRIP ORDER
E
F
B D
RDY
HV SUBSTATION PROTECTION RELAY
BREAKER FAILURE (50BF)
OTHER SUBSTATION
G A B C
BACK-UP PROTECTION
+
67/67N
AUX A 50 BF 67 67N
INTERNAL TRIP
50BF
AUX B
TP TP
NOTE: EXTERNAL TRIP
RDY
HV SUBSTATION PROTECTION RELAY
TRANSFORMER DIFFERENTIAL (87T)
GENERATOR
GENERATOR TRANSFORMER
G A B
UNIT AUXULIARY
TRANSFORMER
87T
AUXULIARY
TRANSFORMER
TRIP SIGNAL
RDY
HV SUBSTATION PROTECTION RELAY
RESTRICTED EARTH FAULT (87N)
GENERATOR
GENERATOR TRANSFORMER
G A B
UNIT AUXULIARY
TRANSFORMER
87N
AUXULIARY
TRANSFORMER
TRIP SIGNAL
RDY
HV SUBSTATION PROTECTION RELAY
BUSBAR PROTECTION (87B)
SWITCHYARD
BUS-1
87C
BUS-2
IIN-A ≠ IOUT-A
IIN-B ≠ IOUT-B
TRUE FAULT
IIN-C ≠ IOUT-C
RDY
HV SUBSTATION PROTECTION RELAY
BUSBAR PROTECTION (87B)
SECONDARY WIRING
87A
AUX AUX AUX AUX
DS-2 DS-1 DS-2 DS-1
87B
87C
RDY
HV SUBSTATION PROTECTION RELAY
BUSBAR PROTECTION (87B)
TRIPPING ORDER
BUS WIRES
AUX DS-1
AUX CB
AUX DS-2
87B
ZONE B ZONE A
(87B) (87A)
87C
RDY
HV SUBSTATION PROTECTION RELAY
TRIP CIRCUIT SUPERVISION (TCS)
PROTECTION
CONTACT
A C A C
B D
B D
CB TRIP COIL #2
CB TRIP COIL #1 TO CLOSING CIRCUIT
-T1 -T2 -C
RDY
HV SUBSTATION PROTECTION RELAY
LOCKOUT RELAY (86)
LOCK-OUT RESET
CB TRIP COIL
-T1
RDY
HV SUBSTATION PROTECTION RELAY
PROTECTION RELAY HYSTORY
EVOLUTION
PROCECOR
INPUT/OUTPUT
SET