7.3 Three Phase Short Circuit
7.3 Three Phase Short Circuit
Symmetrical Faults
Page 379
In order to calculate the sub-transient fault current for a three-
phase short circuit in a power system, we make the following
assumptions:
1. Transformers are represented by their leakage reactances.
Winding resistances, shunt admittances, and -Y phase shifts are
neglected.
2. Transmission lines are represented by their equivalent series
reactances. Series resistances and shunt admittances are
neglected.
3. Synchronous machines are represented by constant-voltage
sources behind sub-transient reactances. Armature resistance,
saliency, and saturation are neglected.
4. All non-rotating impedance loads are neglected.
5. Induction motors are either neglected (especially for small
motors rated less than 50 hp) or represented in the same manner
as synchronous machines.
FIGURE 7.3 Single-line diagram of a synchronous generator
feeding a synchronous motor
• For purposes of calculating the subtransient fault current, Eg// and Em// are
assumed to be constant-voltage sources.
Eg// and Em// are the prefault internal voltages behind the sub-transient
reactances of the machines, the fault is represented by two opposing
voltage sources with equal phasor values VF.
Using superposition, the fault current can then be calculated from
the two circuits shown in Figure 7.4(c). However, if VF equals the
prefault voltage at the fault, then the second circuit in Figure 7.4(c)
represents the system before the fault occurs.
As such, I//F2 = 0 and VF ,which has no effect, can be removed from the second
circuit, as shown in Figure(d) The sub-transient fault current is then determined
from the first circuit in Figure(d), I//F = I//F1. The contribution to the fault from the
generator is, Ig//=Ig1//+Ig2//=Ig1//+IL , where IL is the prefault generator current.
Similarly, Im//=Im1//-IL
SOLUTION
a. Using a 100-MVA base, impedance in the zone of the transmission line is
From the circuit, the The´venin impedance as viewed from the fault is