Lecture 37 - Design of Two-Way Floor Slab System: April 19, 2001 CVEN 444
Lecture 37 - Design of Two-Way Floor Slab System: April 19, 2001 CVEN 444
lb 1 ft lb lb
DL 24 7.0 in * *150 111 .5
ft 2 12 in ft 3 ft 2
lb lb lb kips
wu 1.4 DL 1.7 LL 1.4115.5 1.7 80.0 292 0.292
2 2
ft ft ft 2 ft 2
Example 1
Vc 2 f c bd
1 kip
0.85 2 4000 12 in. 6 in.
1000 lb
7.74 k 3.16 k OK.
Example 1
Determine the strip sizes for the column and middle
strip. Use the smaller of l1 or l2 so l2 = 20 ft
l2 20 ft
l 5 ft
4 4
Therefore the column strip b = 2( 5 ft) = 10 ft (120 in)
The middle strips are
bl 20 ft 2 5 ft 10 ft 120 in
bs 24 ft 2 5 ft 14 ft 168 in
Example 1
Calculate the strip sizes
Example 1
Moment Mo for the two directions.
20 in 1 ft
long direction ln 24 ft 2 22.333 ft
2 12 in
wl2 ln12 0.292 k/ft 2 20 ft 22.333 ft
2
M ol 364.0 k - ft
8 8
short direction 20 in 1 ft
ln 20 ft 2 18.333 ft
2 12 in
wl2 ln12 0.292 k/ft 2 24 ft 18.333 ft
2
M ol 294.3 k - ft
8 8
Example 1
Interior panel
0.35Mo
0.65Mo
Example 1
Factor 0.9
0.9 0.75
0.8333 0.5
0.5 1.0
0.8
Example 1
Need to interpolate to
determine how the
positive moment is
distributed.
Factor 0.9
0.9 0.75
0.8333 0.5
0.5 1.0
0 .8
Example 1
Components on the beam (long).
Column Strip
Negative - Moment 0.80 236.6 k - ft 189.3 k - ft
Positive + Moment 0.80127.4 k - ft 101.9 k - ft
Middle Strip
Negative - Moment 0.20 236.6 k - ft 47.3 k - ft
Positive + Moment 0.20127.4 k - ft 25.5 k - ft
Example 1
When 1 (l2/l1) > 1.0, ACI Code Section 13.6.5 indicates
that 85 % of the moment in the column strip is assigned
to the beam and balance of 15 % is assigned to the slab
in the column strip.
Column Strip - Negative Moment (189.3 k-ft)
Beam Moment 0.85189.3 k - ft 160.9 k - ft
Slab Moment 0.15189.3 k - ft 28.4 k - ft
Example 1
When 1 (l2/l1) > 1.0, ACI Code Section 13.6.5 indicates
that 85 % of the moment in the column strip is assigned
to the beam and balance of 15 % is assigned to the slab
in the column strip.
Factor 0.75
0.75 0.45
1.2222 1.0
1.0 2.0
0.6833
Example 1
Need to interpolate to
determine how the
positive moment is
distributed.
Factor 0.75
0.75 0.45
1.2222 1.0
1.0 2.0
0.6833
Example 1
Components on the beam (short).
Column Strip
Negative - Moment 0.683191.3 k - ft 130.7 k - ft
Positive + Moment 0.683103 k - ft 70.4 k - ft
Middle Strip
Negative - Moment 0.317191.3 k - ft 60.6 k - ft
Positive + Moment 0.317103 k - ft 32.7 k - ft
Example 1
When 1 (l2/l1) > 1.0, ACI Code Section 13.6.5 indicates
that 85 % of the moment in the column strip is assigned
to the beam and balance of 15 % is assigned to the slab
in the column strip.
Column Strip - Negative Moment (130.7 k-ft)
Beam Moment 0.85130.7 k - ft 111 .1 k - ft
Slab Moment 0.15130.7 k - ft 19.6 k - ft
Example 1
When 1 (l2/l1) > 1.0, ACI Code Section 13.6.5 indicates
that 85 % of the moment in the column strip is assigned
to the beam and balance of 15 % is assigned to the slab
in the column strip.
Mu
Ru
bd 2
1.7 * R u
R u w f c 1 0.59 w w2 1.70 w 0
fc
1.7 * R
1.70 1.7 4 u
2
f c f y wf c
w w
2 fc fy
Example 1
Compute the reinforcement need for the negative moment
in long direction. Middle strip width b =120 in. (10 ft),
d =6 in. and Mu = 47.3 k-ft
12 in
47.3 k - ft
Mu
Ru ft 0.132 ksi
bd 2 120 in 6 in 2
1.7 * 0.132 ksi
w 1.70w
2
0
0.9 3 ksi
Example 1
Compute the reinforcement need for the negative moment
in long direction. Strip width b =120 in. (10 ft) d =7.9 in.
and Mu = 200.6 k-ft
As 1.52 in 2
# bars 7.56 Use 8 bars
Ab 0.20 in 2
120 in Maximum spacing is 2(h) or
s 15 in
18 in.
8
So 15 in < 14 in. Not OK!
Use #4
Example 1
The long direction
Example 1
The short direction
Example 2
Using the direct design method,
design the typical exterior flat-
slab panel with drop down
panels only. All panels are
supported on 20 in. square
columns, 12 ft long. The slab
carries a uniform service live
load of 80 psf and service dead
load that consists of 24 psf of
finished in addition to the slab
self-weight. Use fc = 4 ksi and
fy = 60 ksi
Example 2
The thickness of the slab is
found using
12 in
24 * 20 in
ln
ft 8.12 in No panels
33 33
12 in
24 * 20 in
ln
ft 7.44 in 8.0 in
36 36
Example 2
From the ACI Code limitation:
1. For panels with discontinuous edges, end beams
with a minimum equal to 0.8 must be used;
otherwise the minimum slab thickness calculated
by the equations must be increased by at least 10%.
2. When drop panels are used without beams, the
minimum slab thickness may be reduced by 10 %.
The drop panels should extend in each direction
from the centerline of support a distance not less
than one-sixth of the span length in that direction
between center to center of supports and also
project below the slab at least h/4.
Example 2
From the ACI Code limitation:
3. Regardless of the values obtained for the equations,
the thickness of two-way slabs shall not be less
than the following:
wu
2
310 lb/ft 345 lb/ft 322 lb/ft
2 1 2 2
3 3
Example 2
The punch out shear at center column is
d 10 in. 0.75 in. 0.5 in.
8.75 in.
Long
Mo
0.322 k/ft 2 20 ft 22.33 ft
2
401.4 k - ft
direction 8
Short
Mo
0.322 k/ft 2 24 ft 18.33 ft
2
324.6 k - ft
direction 8
Example 2
The column strip will be 10 ft. (20 ft /4 = 5ft),
therefore the middle strips for long section is 10 ft and
the middle strip for the short section will be 14 ft.
Column Strip
Negative - Moment 0.75 260.9 k - ft 195.7 k - ft
Positive + Moment 0.60140.5 k - ft 84.3 k - ft
Example 2
Components on the beam (long) interior.
Middle Strip
Negative - Moment 0.25 260.9 k - ft 65.2 k - ft
Positive + Moment 0.40140.5 k - ft 56.2 k - ft
Example 2
Computing the reinforcement uses:
Mu
Ru
bd 2
1.7 * R u
R u w f c 1 0.59 w w2 1.70 w 0
fc
1.7 * R
1.70 1.7 4 u
2
f c f y wf c
w w
2 fc fy
Example 2
Compute the reinforcement need for the internal moment
in long direction. Strip width b =120 in. (10 ft) d =8.5 in.
and Mu = 195.7 k-ft
12 in.
195.7 k - ft
Mu
Ru 1 ft 0.271 ksi
bd 2
120 in. 8.5 in. 2
1.70 1.7 2
4 0.1279
w 0.0789
2
wf c 0.0789 4 ksi
0.00526
fy 60 ksi
Example 2
The area of the steel reinforcement for a strip width
b =120 in. (10 ft), d = 8.5 in., and h = 10 in.