SG1818154
SG1818154
By Yik Yu Hock
21 November 2013
Fire Protection Services
Fire Sprinkler System
Wet/Dry Riser, Hosereel and Hydrant Design
Automatic and Manual Fire Alarm System
Sprinkler Design
Occupancy classification, CP 52
– Light Hazard Occupancy
– Ordinary Hazard Occupancy
– High Hazard Occupancy
Types of System
– Wet pipe conventional, pre-action, dry pipe, deluge.
Differences?
– In rack sprinklers
– ESFR (Early Suppression and Fast Response)
– Water monitor / cannon
Deluge / Pre-Action System
Water Monitors
ESFR Sprinkler
Warehouse
No need for in rack sprinklers
Caution in use
Not suitable for all types of storage (FM / NFPA)
Types of sprinkler
Types of sprinkler
Sprinkler Design
Sprinkler installation CV coverage
Sprinkler coverage
Sprinkler piping
– Pipe schedule for OH, LH
– Full hydraulic for HH
Typical Sprinkler Schematic
FS
drain
test line for FS
FS test line
drain
FS
drain
FM
to drain
to drain
2 main pumps
vortex
inhibitor & 1 jockey pump
Staged Zones
Bottom up / Top Down
Combination of top & bottom feed
Central feed – up & down
Word of Caution!!
– 10 bars max
– Full size tank
Combined Sprinkler / Wet Riser. Consult QP early.
Examples
Sprinkler Tank
Tank = Refer Table 16 for OH.
For HH full hydraulic cal, flow base on most
favourable area x time of storage
Consider gravity tank for high rise, flow & pressure
determined by hydraulic calculations
Water source – FSSD / PUB requirements
Sprinkler Pumps
Pumps – design point should fall within pump curve
with additional margin
Pump motor – 20% more for non-overloading
Appropriate listing
Positive suction
Plant Room/Services Space Allocation
Sprinkler tank
– Low level
– Less RL 125.000 (water inlet)
– Reinforced Concrete, save space
– U/g not preferred, hard to detect leak, got to use vert. turbine
pumps
– Overflow pipe preferably terminate to external drain than
within room sump.
Sprinkler pump room
– Next to tank, same level or lower than tank
– Flooding risk
Plant Room/Services Space Allocation
Control valve (Clause 9.1.2)
– Adjacent or near 1st sty FCC or fire fighting lobby
– Or in protected area accessible from common area
– Pre-consult FSSD
Breeching Inlet (Clause 5.4.3)
– Near to control valve, must be at ground level, within 18m
from fire engine access way, need to earth (architect to
indicate).
Sprinkler Exemption
Room exempted from sprinkler protection
– Protected Staircase (require only cut-off sprinkler)
– LV switchroom, HV switchroom, transformer room(oil type),
electric lift motor room, elect room, emergency lighting battery
room, MDF room, PABX room
– Provided the above are fire compartmented
– Refer to Fire Code table 6.4A & CP52 Clause 4.2.5.
– Not required above indoor swimming pool
– Coldroom < 30m2, no flammable storage
Note on Special Room / Protection
Computer room, may consider, pre-action system or
gas suppression
Fuel storage – foam system
Lift pit & shaft, escalator pit, services shaft,
Generator room
Fire Suppression System
Fire Suppression System
Concealed Sprinkler Required?
sprinkler buffer
baffle buffer
Sprinkler Layout
Area coverage per sprinkler = 12 m2
Max. dist apart = 4.2 m
Min. dist apart = 2.1 m
(prevent wetting adj. unactivated sprinkler)
Max. dist from wall/partition = 2.1 m
Min. dist from wall/partition = 100mm (NFPA 13)
Sprinkler closer than 600mm to
column, place another sprinkler
on the app. side within 2.1m from
column
Sprinkler under duct
– For circular duct more than 1000mm 0 adj. sprinkler
– For rectangular duct more than 800mm
m
m
00
within 2m
>6
0 sprinkler
Sprinkler Layout
Cut off sprinkler
– In Staircase
– Locate just above door
– Don’t block EXIT
distribution
>300mm
range
CV
Other Pipes Size
Pump Suction Pipe
Pump suction pipe = 150 - OH GP 1 & 2
= 200 - OH GP 3
CV Drain Pipe
Min. 50mm (clause 11.5), calculate size based on testing
flowrate (OH 3 = 1350 L/Min) and available pump head.
Automatic Fire Alarm System
Conventional vs Addressable Fire Alarm System
Manual & Automatic Fire Alarm System
Ref. Fire Code: Table 6.3A for provision of fire
alarms to building
Automatic Fire Alarm
- Conventional System
Automatic Fire Alarm
- Typical Schematic of
an Addressable System
Rising Mains and Hosereel System
Statutory requirements
Max flowrate for Non-residential bldg is 190l/s
and 130l/s for residential bldg. 45 mins
storage.
Max zone height 120m. Landing valve outlet
max 8 bar.
The landing valve & hosereel positioning is by
Architect.
Multi-outlet pumps – Consult QP early
Multi-stage Wet Riser Pump
Reflections Condominium
Reflections Condominium
Wet Riser Pump Selection
Fire Hydrant