Branch Circuit Calculations Feeders Services and Overcurrent Devices
Branch Circuit Calculations Feeders Services and Overcurrent Devices
CALCULATIONS
FEEDERS
SERVICES
And
OVERCURRENT DEVICES
1. OBJECTIVES
2. THEOREM
COMBINATION LOAD - SHALL NOT EXCEED 80% THE RATING OF THE CIRCUIT.
3 - W , (3Ø, 3w)
4 - W , (3Ø, 4w), 3W + N
5 – W , (3Ø, 5w), 3W + N + E
OBJECTIVES
To set standard in the working areas the required ampacity of the conductors for branch circuits,
sub-feeders, main feeders, service and service entrance as well as the required overcurrent devices that
will be helpful in our daily design and estimates work.
THEOREM
One of the most common fundamentals task facing everyone involved with electrical engineering
practice is establishing the ampacity, the maximum code – recognized current carrying
capacity of every circuit conductor. The selection of overcurrent devices (fuses and breakers ) is
based on the conductor ampacity.
APPLICATIONS AND ILLUSTRATION
DESIGN CALCULATION:
= 15.65 A
THE APPLIANCE BRANCH CIRCUITS
Based on kW nameplate or current nameplate
SAMPLE EXPLANATORY ILLUSTRATION
DESIGN CALCULATION:
= 15.65 A
THE INDIVIDUAL BRANCH CIRCUITS
THE (S. P. O.)
SAMPLE EXPLANATORY ILLUSTRATION
DESIGN CALCULATION:
DESIGN CALCULATION:
DESIGN CALCULATION
DESIGN CALCULATION
50 kW, 230v, 3Ø, 3W, INDUCTION MOTORS = [50 X 1000 / (230 X 1.732)(0.8 P.F)]
= 157 A
= 188 A
EXCEPTION: WHERE THE AMPACITY OF THE CONDUCTOR DOES NOT CORRESPOND WITH THEIR
AMPERE RATING OF A FUSE OR CIRCUIT BREAKER, THE NEXT HIGHER STANDARD DEVICE RATING
SHALL BE PERMITTED ONLY IF THIS DOES NOT EXCEED 800A.
A.) UNDERGROUNDED CONDUCTOR, SUCH PROTECTION SHALL BE PROVIDED BY AN OVERCURRENT
DEVICES IN SERIES WITH EACH UNGROUNDED SERVICE CONDUCTOR THAT HAS A RATING OR
SETTING NOT HIGHER THAN THE ALLOWABLE AMPACITY OF THE CONDUCTOR.
BASIC RULE
EXCEPTION
SINGLE PHASE
CHARACTERISTICS
CHARACTERISTICS
CHARACTERISTICS
OFTEN USED FOR MAIN POWER DISTRIBUTION IN LARGE INDUSTRIAL PLANT, WHERE THE
BREAKERS ARE ARRANGED IN DRAW-OUT ENCLOSURES FOR EASE OF MAINTENANCE
CHARACTERISTICS
CHARACTERISTICS
PHASE (LINE), NEUTRAL AND EARTH WIRE CONNECTED THROUGH ELCB
ELCB IS WORKING BASED ON EARTH LEAKAGE CURRENT
. PROTECTION MECHANISM
THERMAL OVERLOAD PROTECTION
- TO PREVENT THE ACCIDENTAL OVERLOADING OF THE CABLE IN A NO FAULT
SITUATION.
MAGNETIC FAULT PROTECTION
- TO OPERATE WHEN FAULT REACHES A PRE-DETERMINED LEVEL AND TO TRIP THE
BREAKER WITH ONE TENTH OF A SECOND.
MCCB AMPERE FRAME RATING (personal reference)
30 AT 400 AT
50 AT 600 AT
60 AT 630 AT
63 AT 800 AT
100 AT
125 AT
225 AT
250 AT
MCCB AMPERE TRIP RATING (PEC)
30 AT 125 AT 700 AT
50 AT 150 AT 800 AT
60 AT 175 AT
63 AT 200 AT
100 AT 225 AT
125 AT 250 AT
225 AT 300 AT
250 AT 350 AT
60 AT 400 AT
63 AT 500 AT
75 AT 600 AT
100 AT 630 AT
STANDARD INTERRUPTING CAPACITY ( JIS C 8201, IEC 60947-2)
30 2.5 1.5
50 7.5 5 2.5 2.5
60 7.5 5 2.5 2.5
63 7.5 5 2.5 2.5
100 30/15 10/5 10/5 7.5/4
125 30/15 10/5 10/5 7.5/4
225 35/18 18/9 15/8 10/5
250 35/18 18/9 15/8 10/5
400 50/25 36/18 25/13 15/8
600 50/25 36/18 36/18 18/9
630 50/25 36/18 36/18 18/9
800 50/25 36/18 36/18 18/9
SQUARE D - SCHNEIDER ELECTRIC
MITSUBISHI - EDISON
WESTINGHOUSE (WHSE) -
MCCB kAIC
USE 30AF
MCCC kAIC
BETWEEN INDIVIDUAL
2.0 1.46 1.45
USER
BETWEEN TRANSFORMERS 1.3 1.3 1.35 1.05
BETWEEB FEEDERS 1.15 1.15 1.15 1.05
BETWEEN SUBSTATION 1.10 1.10 1.10 1.10
ILLUSTRATION:
DESIGNING SIZE OF ELECTRICAL SWITCHGEAR APPLYING DEMAND FACTOR AND DIVERSITY FACTOR*
DIVERSITY FACTORS ARE USED BY UTILITIES FOR DISTRIBUTION TRANSFORMER SIZING LOAD PREDICTIONS
*DEMAND FACTORS ARE MORE CONSERVATIVE AND USED BY NEC FOR SERVICE AND FEEDER SIZING.
*DEMAND FACTORS AND DIVERSITY FACTORS ARE USED ON DESIGN.
*THE SUM OF THE CONNECTED LOADS SUPPLIED BY FEEDER IS MULTIPLIED BY THE DEMAND FACTOR TO DETERMINE
THE LOAD FOR WHICH THE FEEDER MUST BE SIZED. THIS LOAD IS TERMED AS THE MAXIMUM DEMAND OF
FEEDER. THE SUM OF THE MAXIMUM DEMAND LOADS FOR A NUMBER OF SUB-FEEDERS DIVIDED BY THE
DIVERSITY FACTOR FROM WHICH THE SUB FEEDERS ARE DERIVED.
EXAMPLE-1: SUPPOSE WE HAVE FOUR INDIVIDUAL FEEDER-CIRCUITS WITH CONNECTED LOADS OF 250 kVA, 200 Kva,
150 kVA and 400 kVA AND DEMAND FACTORS OF 90%, 80%, 75% AND 85% RESPECTIVELY. USE A
DIVERSITY FACTOR OF 1.5
BASIC RULE
A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED BY ONLY ONE (1) SET OF SERVICE
DROP OR SERVICE LATERAL CONDUCTOR (UNDERGROUND).
EXCEPTIONS :
4500 mm ………….OVER COMMMERCIAL AREAS, PARKING LOTS AGRICULTURAL AND OTHER AREAS SUBJECT
TO TRUCK TRAFFIC.
3600 mm ………….OVER RESIDENTIAL DRIVEWAYS AND COMMERCIAL AREAS SUCH AS PARKING LOTS AND
DRIVE – IN ESTABLISHMENT NOT SUBJECT TO TRUCK TRAFFIC.
3000 mm …………..ABOVE FINISHED GRADE SIDEWALKS OR FROM ANY FLATFORM OR PROJECTION FROM WHICH
THE CONDUCTOR MIGHT BE REACHED.
a. 5500
b. 4500
c. 3600
d. 3000
SERVICE LATERAL
SIZE AND RATING MAIN DISCONNECT
SERVICE ENTRANCE
SERVICE LATERAL
UNDERGROUND SERVICES
MINIMUM SIZE AND RATING
AMPACITY OF CONDUCTORS ………………….. 100% OF TOTAL POWER LOAD
CURRENT
OVERCURRENT PROTECTION …………………… 125% OF TOTAL POWER LOAD
…………… SHALL CONSIST OF NOT MORE THAN SIX (6) SWITCHES OR CIRCUIT BREAKERS
MOUNTED IN A SINGLE ENCLOSURE OR GROUP OF SEPARATE ENCLOSURE OR IN A
SWITCHBOARD.
SECONDARY SERVICE (M E R A L C O)
RADIAL DISTRIBUTION SYSTEM
…………………….. HAS ONE POWER SERVICE FOR A GROUP OF CUSTOMERS.
DISADVANTAGES
1. IF THERE IS A POWER FAILURE THE ENTIRE GROUP LOSSES POWER.
2. IF THERE IS CIRCUIT FAILURE SOMEWHERE IN THE SYSTEM COULD MEAN A POWER
INTERRUPTION IN THE WHOLE SYSTEM.
NETWORK DISTRIBUTION SYSTEM
……………………… MOST EXPENSIVE AND MOST RELIABLE IN TERMS OF CONTINUITY OF SERVICE.
THIS SYSTEM CONSIST OF A NUMBER OF INTERCONNECTING CIRCUIT OPERATING AT THE SAME
UTILIZATION VOLTAGES.
THE CUSTOMER IS CONNECTED TO TWO (2) OR MORE POWER SUPPLIES.
IF ONE POWER FAILS , THE CUSTOMER GETS POWER FROM THE OTHER SOURCES, WITHOUT
INTERRUPTION
SERVICE UTILITY STANDARD SECONDARY SYSTEM (M E R A L C O)