WHAT IS FLOW ??
– Measure of the velocity of a fluid per unit
area in a closed conduit; ie: pipe or duct
– FLOW = VELOCITY (fluid) X Area of
Pipe or Duct or Stack
– FLOW = FPM X FT2 or IN2
– Q = AV (Area X velocity)
– Q = ρ AV (density x area x vel)
• Mass flow
FLOW - In our
everyday lives
Water flow meter at our home or
apartment
– used for billing purposes
– Mechanical flow meter with local rate and
total
– Relative accuracy
FLOW - In our
everyday lives
Gas Flow Meter - natural gas measurement of
gas used for cooking and heating
– Mechanical Meter - turbine type
Liquid flow meter - Gasoline - at the local gas
station where we pumped gas this morning
– Positive displacement type with output
signal to electronic counter for billing
7
Basic Flow Theory
Volumetric Flow
Mass Flow
Density - Liquid
Density - Steam
Actual vs. Standard Flow - Gas
Energy Flow - Water
Flow Profiles & Reynolds Number
Viscosity
Accuracy
Repeatability
Straight Run Requirements
Meter Installation
8
Volumetric Flow (all fluids)
Q = A *V
= ft ² * ft sec
= ft ³ sec
where:
9
Mass Flow
= Q = A V
m * * *
= ft ² * ft sec * lbs ft ³
= lbs sec
where:
m = mass flow ( lbs sec )
= density ( lbs ft ³ )
Q = average fluid velocity ( ft sec )
A = cross sectional area ( ft ² )
10
Density - Liquids
Liquids
The density of a liquid is inversely proportional to temperature:
WATER
Temperature Weight Density
1 T °F Lbs/gal
32 8.3436
40 8.3451
50 8.343
60 8.3378
70 8.329
80 8.3176
90 8.3037
100 8.2877
11
Density - Gases
Gases
The density of a gas varies proportionally with pressure and inversely with
temperature:
= a 1
T
Density of Gas:
2.7 a SG
where: = Density ( lbs ft 3 )
= a = absolute pressure (psia) = 14.7 + Pgage
Ta
SG =Specific Gravity
Ta = absolute temperature = F° + 460 = ° Rankin
12
Density - Steam
Saturated steam: Superheated steam:
13
Actual vs. Standard Flow - Gas
Actual Volume Flow:
Q = V * A (actual ft³ sec, ft³ min, etc)
(actual m³ sec,hr, m³ sec, etc)
where:
operating
Qstandard
= Qactual
standard conditions Qstandard = standard ft³ unit time or
standard m³ unit time
Qactual = actual volumetric flow (ACFM, ACFH, etc…)
SG = specific gravity ( gas air , at standard conditions )
operating = density of gas at operating pressure and temperature
standard = density of gas at standard conditions (at 14.7 psia, 60°F)
14
Energy Flow
Chilled/hot water energy (Btu) calculations require
(1) flow and
(2) temperature inputs.
Btu is defined as the amount of energy required to
raise the temperature of 1lb water at 39°F by 1°F.
= mass flow
m (lbs sec )
E = A V (h s - h r )
ft lbs Btu
A = cross sectional area (ft²)
E = ft² sec ft³ lbs
Btu V = average fluid velocity ( ft sec)
E=
= density ( lbs
sec
ft³ )
hs = Btu’s (heat content) of water at supply temperature (Btu lbs)
where:
hr = Btu’s (heat content) of water at return temperature (Btu lbs)
15
Flow Profiles & Reynolds Number
inertial forces
Re =
frictional forces
density velocity
diameter
Re =
viscosity
Re = V D
µ
16
Viscosity
Dynamic viscosity
cP (centipoise)
Kinematic Viscosity
cst (centistoke)
17
Viscosity
Viscosity can be highly temperature dependent in liquids.
Steam/gas – 0.01 cP
Water – 1.0 cP
Honey – 300 cP
18
Accuracy
ACCURACY +/-1%
% of Rate or Reading
% of Rate
Error = % of full scale full scale flow Min flow 100 lb/h = 110 (100 + 10) lb/h
to 90 (100 - 10) lb/h
19
Repeatability
Accurate & Repeatable
Repeatability:
Differs from Accuracy
Not accurate,
Measures the same all the time
or repeatable
Not accurate,
but repeatable
20
Installation – Straight Run
Straight run requirements
Minimum 10 pipe diameters upstream and 5 pipe diameters downstream required to get
proper flow profile
21
Installation – Meter Location
Install before valve to avoid air
22
Technologies
Technology Operating Advantages Disadvantages Fluids Measured
Principle
DP An obstruction in the flow, Low initial cost Not highly accurate, Liquids
(Differential measure pressure No moving parts particularly in gas flow Gases
Pressure) differential before and after Handle dirty media Orifice plate and pitot tube Steam
Orifice plate the obstruction Easy to use can become clogged
Pitot tube Well understood technology High maintenance to
Variable area Supported by AGA and API maintain accuracy
Venturi Typically low turndown
V-Cone Pressure drop
Accelabar
Vortex Bluff body creates High accuracy Can be affected by pipe Liquids
Inline alternating vortices, vortex No moving parts vibration Gases
Insertion shedding frequency equal to No maintenance Cannot measure low flows Steam
fluid velocity Measures dirty fluids
Turbine Turbine rotates as fluid High accuracy Moving parts require higher Liquids
Inline passes by, fluid velocity Low flow rates maintenance Gases
Insertion equal to blade rotational Good for steam Clean fluids only Steam
Dual turbine frequency Wide turndown
Magnetic Measures voltage generated High Accuracy Conductive fluids only Conductive
Mag by electrically conductive Wide turndown Expensive to use on large liquids
Electromagnetic liquid as it moves through a Bi-directional pipes (condensate)
magnetic field, induced No moving parts
voltage is equal to fluid No pressure loss to system
velocity
23
Technologies Cont’d
Technology Operating Advantages Disadvantages Fluids Measured
Principle
Transit-time Fluid velocity measured by time Low cost clamp-on installation Typically not used on Most liquids
Ultrasonic arrival difference of sound Non-intrusive pipes < 2” (condensate)
waves from upstream and No maintenance Less accurate than inline or Gas (when spool-
downstream transducers Bi-directional insertion meters piece)
Best for larger pipes Used primarily for liquids
Susceptible to changes in fluid
sonic properties
Doppler Fluid velocity measured by Low-cost, clamp-on installation Can’t be used in clean liquids Most liquids
Ultrasonic sensing signals from Non-intrusive Less accurate than in-line or containing
reflective materials within the Measures liquids containing transit-time ultrasonic reflective
liquid and measuring the particulates or bubbles materials
frequency shift due to the Low maintenance
motion of these reflective Best for larger pipes
materials
Thermal Measure heat loss of heated Measure flow at low pressure Susceptible to sensor wear and Gases
Mass wire thermistor in fluid flow Relative low cost failure
Measure fluids not dense enough Not very accurate
for mechanical technologies Limited to fluids with known
Easier to maintain than DP meter heat capacities
24
Orifice Plate Flowmeter
The orifice plate is a differential pressure
flow meter (Primary element).
25
Orifice Plate Flowmeter
26
Orifice Plates
27
Variable orifice flow meter
Line sizes 2-8”
Temp up to 842°F
(450°C)
Accuracy ±1.0% of
rate
Gas and Steam
applications
Compact installation -
6 up and 3 down
Up to 100:1 turndown
28
Digital variable orifice flow meter
Line sizes 2-4”
Saturated Steam ONLY
347°F (175°C)
Accuracy ±2.0% of
flow
Internal RTD for
Integrated mass flow
measurement
Compact installation -
6 up and 3 down
Up to 50:1 turndown
29
Vortex Flowmeter
Liquid, Gas, and Steam
1-12” (25 to 300mm)
Temperature up to 750°F(400°C)
EZ-Logic menu-driven user
interface
In-process removable sensor
(below 750psig)
Fully welded design with no leak
path
Optional remote mount electronic
Accuracy
Liquid ±0.7% of rate
Gas and Steam ±1.0% of rate
Turndown up to 20:1 Vortex
30
Insertion Vortex Meter
Liquid, Gas, and Steam
Model 60/60S Hot Tap, retractable
Model 700 Insertion low temp, low
pressure
Model 910/960 Hot tap, retractable
960-high temp up to 500°F (260°C),
high pressure
Optional Temperature and/or Pressure
Transmitter
Line sizes 3-80” (76 to 2032mm)
No moving parts
EZ-Logic menu driven user interface
Accuracy
Liquid ±1.0% of rate
Gas and Steam ±1.5% of flow rate
test conditions
Turndown up to 20:1 VBar
31
Turbo-Bar Insertion Turbine Flow Meter
Liquid, Gas, and Steam
Liquid flow velocity down to 1 ft/sec
Model 60/60S Hot Tap, retractable
Model 700 Insertion low temp, low
pressure
Model 910/960 Hot tap, retractable
960-high temp up to 750°F (400°C),
high pressure
Optional Pressure and/or Temperature
Transmitter
Line sizes 3-80” (76 to 2032mm)
EZ-Logic menu driven user interface
Nominal Accuracy
Liquids ±1.0% of rate
Gas and Steam ±1.5% of rate
Turndown up to 25:1 TMP
32
Low-cost Water Vortex Meter
No Moving Parts 2200
Flow Range 1 to 15 ft/s (0.3 to 4.5 m/sec)
Accuracy ±1.0% of Full Scale
1/2 to 20” Line Size 2300
Microprocessor-based electronics with
optional local display
Maximum Fluid temperature 160°F
(70°C)
Model 2300 for acids, solvents, De-
ionized, and ultra pure water (1/2 to 8”)
Model 2200 Fixed Insertion for (2 to 20”)
1200
Model 1200 for water, water/glycol (1-3”)
3100
Model 3100 retractable insertion (3-20”)
Models 1200 and 2200 have Aluminum
Enclosure option for wet environments
or heavy industrial installations
33
Transit Time
Ultrasonic Flowmeter
Liquid applications-Clean
2-100” (50 to 2540mm)
Accuracy typically ±2.0%
of rate
Non-Intrusive
No wetted parts
Multiple outputs available
EZ-Logic menu driven user
interface
Bi-Directional
Transducer cable length
up to 300’
Sono-Trak
34
Electromagnetic Flowmeter
Field Serviceable Design
Field replaceable sensors and coils
No Liner Required
No liner failure
Solid State Sensor Design
Encapsulated coil and electrode
assembly insensitive to shock and
Vibration
Plurality of Sensors
Uniquely powerful magnetic field
Non-standard Flow Tube Lengths
Easy replacement of existing meters
Measures Low Conductivity Media
Conductivity down to 0.8 µS/cm
35
THERMAL MASS FLOW METERS
FOR MEASURING GAS FLOW
WHAT IS A THERMAL MASS
FLOW METER?
Itis a Meter that directly measures
the Gas Mass Flow based on the
principle of conductive and convective
heat transfer – more detail later…
MEASURE MASS FLOW RATE
OR TOTALIZE COMMON GASES
Air (Compressed Air, Blower Air, Blast Furnace
Air, Combustion Air, Plant Air, Make-Up Air)
Natural Gas Industrial (Plant Usage, Sub-
Metering, Boiler Efficiency, Combustion Control)
Natural Gas Commercial & Governmental
(Building Automation – Reduce Energy Costs,
LEED Credits, Meet Regulations)
Digester Gas, Bio Gas, Landfill Gas (especially
for EPA regulations and Carbon Credits)
Flare Gas (Vent Gas and Upset – Dual Range)
Powerful State-of-The-Art
Microprocessor Technology
High Performance Mass Flow
Measurement at Low Cost-of-Ownership
Proprietary Digital Sensor Drive Circuit
Provides Enhanced Signal Stability
Low Power Dissipation, under 2.5 Watts
(<100 ma at 24 VDC)
SAGE PRIMETM
(Continued)
High Contrast Photo-Emissive Organic
LEDs (OLEDs)
Displays Calibration Milliwatts (mw) for
Ongoing Diagnostics (Zero Calibration Check)
Modbus Compliant RS485 RTU
Communications (IEEE 32 Bit Floating Point)
Remote Style has Lead-Length Compensation
– Up to 1000 Feet
24 VDC or 115/230 VAC Power
Leak Detection
Energy Conservation
Compressor Optimization
Performance Testing
??????????????????????