Battery Bank
1
Content
This module would cover the following:
Working and Types of Lead Acid Battery. (Slides 3-10)
Reasons of using Lead Acid Battery.(Slide 10)
Specification of Lead-Acid battery.(Slides 11-14)
Information for VRLA Battery user. (Slides 15-24)
Handling the battery. (Slides 26-30)
Maintaining the battery. (Slides 32-42)
Dos & Don'ts and General Instructions. (Slides 44-50)
Trouble shooting and root cause analysis for BB troubles. (Slides 51-52)
2
Lead-Acid Battery
3
A cell holds chemical energy that gets converted to electrical energy
‘Cell’ ‘Battery’
1) 2 plates 1) Plates in multiples of 2
2) 2 volts (Lead-Acid) 2) Voltage in multiples of 2volts
Basic Lead-Acid (LA) Cell
PbO2 Pb
4
Battery = Cells in series
(where all the cells may / may not be in the same case / container)
Primary battery Secondary battery
Non-rechargeable Chargeable
(Zinc-Chlorine, Alkaline) (Lead-Acid, Nickel-Cadmium)
5
Types of Lead-Acid Battery used with DC power-
plants & UPS
Open type cell / battery -
This type of battery does not have cover
In case if it has cover then
Either cover would have lot of Air-gaps
Or cover can be removed easily during operational time
SMF cell / battery - (Sealed-Maintenance-Free)
This type of battery is totally sealed & cover can not be opened any time
SMF VRLA cell / battery - (Valve-Regulated)
This type of battery has a pressure valve (Rest these are same as SMF)
Valves are not supposed to be tempered
6
Types of Lead-Acid Battery used with DC power-
plants & UPS
Open type cell / battery -
Advantages No pressure build-up
Easy measurement of charge status
Easy visual inspection
Disadvantages Requires topping-up
Fumes , hence requires separate room
Less safe to work with/near it
SMF (Sealed-Maintenance-Free) cell / battery -
Advantages No topping required
No fumes
More safe to work with / near
Disadvantages Chances of pressure build-up exists
Cannot directly measure charge status
Visual inspection impossible
7
Types of Lead-Acid Battery used with DC power-
plants & UPS
SMF VRLA (Valve-Regulated Lead Acid) cell / battery -
Advantage Pressure build-up is taken care of
Note: Rest all Advantages & Disadvantages are same as SMF
8
9
Reasons of using Lead-Acid Battery
Inexpensive & simple to manufacture
Most economical for larger power applications where
weight is of little concern
Mature, reliable & well understood technology.
Long life
Lowest self discharge
Capability of high discharge rates.
Voltage per cell is maximum
Less maintenance for VRLA battery
10
Important specification of Lead-Acid battery
• Rated Voltage / System Voltage
• AH (Ampere-Hour)
• Designed rate of discharge (Hour Rate)….. C5, C10, etc.
• Charging Voltage-per-Cell
• End-cell voltage
• Ideal ambient temperature
• Stack design and Weight
11
Important specification of Lead-Acid battery…contd
• K factor
• Max. charging current as % of AH (under various conditions)
• Chart/graph showing capacity vs. ambient temperature
• Life expectancy & its variation with respect to temperature, charging
voltage, etc.
• Charge & Discharge curves of factory-testing or type-testing
• Internal impedance value for a new & charged cell
12
Typical Charging Characteristics
13
Typical Discharging Characteristics
14
Important points about Battery we should know
A
discharge
1. Life of a battery is quoted in 2 ways, whichever ends first – followed
• Number of years (represents stand by mode life) by a
• Number of charge/discharge cycles @ specified DOD (Depth Of Discharge) complete
charge of a
battery
2. Numbers of cycles in a battery life is dependent upon depth of discharge
1200 cycles @80% DOD
2000 cycles @ 50% DOD Depth of
discharge
4000 cycles @ 20% DOD
3. As max VRLA capacity is limited, cell paralleling is permitted but after due
matching of conductance.
4. AGM – VRLA battery is in use for BIL (AGM = Absorbed Glass Mat)
5. Gel – VRLA battery having better cyclic life than AGM have been tried out
15
Important points about Battery we should know
6. Battery life is maintained chiefly with regulated & full charging and
maintaining the required temp of the battery enclosure (27°C).
7. Batteries are designed for a particular ambient temperature –
Indian batteries: Generally 27ºC
• European batteries: Generally 22ºC
8. Factors affecting the life of a battery
Ambient temperature (higher the temperature, lower the life)
• Charging voltage (higher the charging voltage, lower the life)
• Improper storage (should be stored as per manufacturer’s
recommendation & should be charged every 6 months of storage)
16
Important points about Battery we should know
9. K-factor
If actual rate of discharge is different than designed rate of
discharge, then the battery capacity needs to be de-rated. The
de-rating factor is K-factor.
10. Aging factor: Decay in AH capacity from day-1 to end-of-life
11. Capacity available is sensitive to rate of discharge & ambient
temperature.
• Higher the discharge rate, lower the capacity
• Higher the temperature, higher the capacity
12. Current it takes in stand-by mode is called “Float charging
current”. Its about 1% of the AH
13. Boost charging current is typically 10-15% of the AH
17
Important points about Battery we should know
14. Trickle charging & boost charging voltage
- It is generally same (unless specifically mentioned)
- As per recommendation of battery manufacturer, battery can
be boost charged at a higher voltage for few hours every few
days.
18
48 v- 600 Ah front view
VRLA
19
Effect of High Temperature
The effect of operating temperature on VRLA battery is same as that of on any
other lead acid battery and the effect will be as follows,
Higher than normal
Discharge
Higher capacity
Higher rate of corrosion
Charge
Excessive over charge
Electrolysis of water
Shortened service life
To some extent this can be compensated by adjusting the charger voltage
setting by -3 mV per cell per degree raise in the temperature1
20
Effect of Low Temperature
Lower than normal
Discharge
• Lower capacity
• Low rate of grid corrosion
Charge
• Under charging of the battery
• Sulphation of the plates
• Shortened life
To some extent this can be compensated by adjusting the charger voltage setting
by +3 mV per cell per degree fall in the temperature
21
Effect of Temperature
22
Battery – Capacity Selection
• Battery capacity Depends upon discharge current, back-up time
required, operating voltage window and temperature
• Different correction factors used for capacity selection
‘k’ factor – To consider available battery capacity available at
particular discharge rate for a particular end cell voltage (ECV)
Temp correction factor – Battery capacity derates with lower of
temp
Ageing factor – 1.25 as per IEEE standard 485
Design margin – 1.1 to take care of design uncertainties
Max %DOD permissible during normal site operation (so that
spare capacity is available in case DG fails to start)
• Capacity in AH = Load current * K factor for backup hrs required * 1.25
* 1.1 * temp correction factor (if ambient temp is lower to 27°C) /
Normal %DOD permissible
23
Example: Battery Capacity Selection
Inputs –
DC Load (of BTS & MW) = 1.5kW
Hence Load current (for BTS & MW) = 31.25A ……. (1500/48 = 31.25)
Backup hrs reqd = 4hrs
K-factor for 4hrs = 4.76
Ambient temperature for BB = 27 Deg C
Max %DOD permissible = 80%
Computation –
AH = 31.25 x 4.76 x 1.25 x 1.1 x 1 / 0.8 = 255.66AH
Hence BB selected should be 300AH (as 255AH is not available in
market)
24
Handling the battery
25
Handling the battery
Installation of Battery bank requires the following to be done
as per the battery manual –
Receiving Inspection
Installation considerations
System assembly
Post preparation
Connections
Maintenance of battery consists of -
System monitoring
Trouble Shooting
26
Precautions while handling the battery
The precautions that need to be taken while
handling the Battery are:
– Use insulated tools only
– Lifting equipment must withstand the module weight
– Always start with connection drawing
– Avoid installation damages
– Avoid short circuits
27
Receiving Inspection
Unpack the battery module, accessories box and check the following:
1. Quantity of the accessories as per the packing note
2. Transit damages
Note: Damage/short supply needs to be reported in writing
within a week for insurance claim
28
Installation Considerations
Space considerations . . .
• Install the battery bank in a clean, cool and dry location
• Floor should be reasonably level
• A location having an ambient temperature of 24° C to 30° C
will result in optimum battery life and performance
29
Installation Considerations
Floor loading . . .
• System weight and dimensions are provided in the drawing
• If floor loading exceeds the permissible limits, assemble the
batteries on a steel sheet of min. 5-mm thickness.
Note: Provision of the same is the responsibility of the user.
30
Maintaining the Battery
31
System Monitoring
Routine Checks:
S.No. Checks Action
Physical damages, any leakage, bulging of Replace the cell
01
cell, Cracking of cover & container
Check the over voltage cut off and under If varies, reset the
voltage trip. same in the SMPS
02
(Over voltage cutoff: 2.33VPC, Under
Voltage trip: 1.75 VPC)
32
Routine Check…..contd
Description of the check
Check the float charging voltage and current (Voltage: 2.23 volts per cell, Current: 10% of
cell rated capacity)
Note down the average ambient battery room temps.
(Battery will give optimum performance when operated at 27C. The temperature
compensation factor is – 3 mV/cell º C rise from the ambient temp. of 27º C and vice versa)
Maintain battery record
Before starting this test ensure that the batteries are in fully charged condition. Note down
individual cell voltage readings after discharging the battery bank for 30 min (with current
of min 10% & max. 20% of the rated capacity) by switching OFF the rectifier to identify
weak cells if any in the battery string
Manual Boosts charge the batteries for 24 Hrs.
(Voltage: 2.30 VPC, Current: 20% (max.) of cell rated capacity
Check for terminal post corrosion, if any remove the connector, clean with brass brush or
emery paper & Re-torque the terminal Bolts to 11Nm.
Test discharge of the battery bank @ C10 rate
Monthly Quarterly Half-yearly Yearly
33
Quarterly Preventive Maintenance Schedule- Battery Bank
S. No. Check Points
1 Carry out Battery Bank Cleaning
2 Check leakage from battery cells. If Yes, take corrective action to prevent it
3 Check vent plug, inter cell connections and cable for tightness
4 Check Battery Bank Stand earthing for tightness
Check SMPS Temperature Compensation (TC) probe is mounted to battery
5
casing/base
6 Check for protection covers availability on Battery Bank
7 Check individual cell/ connector temperature for abnormal overheating
8 Check Battery Bank Voltage
9 Check battery chiller operation
10 Check battery chiller door for free operation & proper locking
11 Check no air leakage from battery chiller door
12 Check & record Battery Bank charging current
34
Quarterly Monitoring:
Discharge the battery bank with equipment load (normally 10% of the
rated capacity) for 30 minutes and note down the individual cell
readings
Calculate the average cell voltage of the battery bank as follows :-
Average cell voltage = Total bank voltage
No. of cells
If the average cell voltage is >2.0 volts, Individual cell readings should
be with in a range of + 0.03 V
If the average cell voltage is <2.0 volts, Individual cell readings should
be with in a range of + 0.1 V
35
Quarterly Monitoring…..contd
• If any cell voltage reading falls out of the above range those cells
should be monitored very closely since there is a possibility that these
cells can become faulty in future
• Equalization charging needs to be given if the above mentioned voltage
variation is found
• Wherever the above discharge test is not possible, use a suitable on
line discharge equipment to determine the health of the battery bank.
36
Equalization Charge:
The equalization charging of the batteries needs to be done whenever the battery
cell voltages are not equal (differ by more than+ 0.03V) .This can be found out from
Short-term discharge test or from annual discharge test. The following precautions
need to be taken before the equalization charge:
1 Check DG set is healthy & Fuel tank is full.
2 Start DG set in manual & take on load manually. Wait for 10 minutes after switch
over of Load.
3 Isolate Battery bank from SMPS by removing battery fuse in SMPS.
4 Connect external load to battery bank through isolator
37 (MCB).
Equalization Charge…..contd
5 Start discharge with discharge current limited to 10% of Battery AH.
6 The battery bank has to be completely discharged up to end cell voltage i.e.
1.75 V for 2V battery.
7 Continuous monitoring of the individual cell voltage and the bank voltage has
to be ensured.
8 The readings shall be recorded in the format used for Battery discharge test.
9 As soon as cell reaches ECV of 1.75V, stop discharge test & bypass the cell &
9 continue with discharge test. 38
Equalization Charge…..contd
11 Charge the battery bank with 0.1 C to 0.2 C rate current for a period of at least 21
hours.
12 Check the individual cell voltages after the charging. If the variation is more than 0.1 V
in the cells, carry out discharge test .
13 Carry out discharge test & check Battery back up, if during discharge test cells marked
prior to Equalisation test are not showing any improvement & voltage is dropping wrt to
other cells, cells called for replacement.
39
Yearly Monitoring:
1. Charge the batteries at a constant voltage of 2.30 volts per cell with
current limited
to 20% of the rated capacity for 48 hr. or
to 10% of the rated capacity for 72 hr.
2. Then discharge the batteries at C10 rate. i.e. 10% current of the battery
rated Ah capacity
3. Note down the hourly readings in test data sheet.
40
Yearly Monitoring…..contd
4. After completing the test, if the capacity obtained is more than 90% of
the rated capacity then the same may be connected back to load after
recharge as mentioned in point (i) above.
5. If the capacity obtained is less than 80% to 90% repeat point # 1
6. If the capacity obtained is still less than 80% contact the nearest service
center
.
41
Procedure for monthly boost charging of VRLA battery bank
42
Dos & Don’ts
And
General Instructions
43
DOs for VRLA Battery
• During “discharge-charge” test, find out the cell/battery with
maximum rate of voltage decrease. Mark it as the “weak cell” &
monitor its voltage during each discharge
• Keep the batteries away from heat source, sparks, fire etc.
• Clean the batteries as and when dust accumulates
44
DOs for VRLA Battery
• Wherever cables are used ensure • Torque all terminal bolts to 11 Nm
(100 Lb.-inch)
using proper cable size and
• Re- torque the terminal bolts once
crimping of the lug to the cable
in every six months
• Approx. Cable sizing thumb rule =
1.5 A per 1sq.mm of copper
45
DON’Ts for VRLA Battery
• Do not tamper the safety valves • Do not over tighten the terminal
bolts
46
DON’Ts for VRLA Battery
• Do not allow any metal objects to fall • Do not install physically damaged
across the battery terminals cells
• Do not attempt dismantling a
cell even if its to be disposed off
47
DON’Ts for VRLA Battery
• Do not mix the batteries of different • Do not allow any direct sunlight to
capacities or makes fall on batteries
• Do not mix ordinary conventional/low
maintenance batteries with maintenance
Free VRLA batteries
48
General instructions about VRLA batteries
Nominal voltage of cell/Battery : 2V/48V
Storage and installation
Store the batteries in covered area
Provide normal ventilation. Do not install in airtight area
Keep away from Sparks, Heat, Fire & direct sunlight
While doing terminations all terminals should be clean
49
General instructions about VRLA batteries
Apply a thin film of petroleum jelly on the terminal post to contactor joints ,
after the connections are made
Affix cell number stickers and polarity labels
Fill the date of installation on the Nameplate using a marker pen
Do not take tap connections
If the batteries are stored beyond 6 months, give a freshening charge at
regular basis
50
BATTERY BANK FAULT ANALYSIS
51
BATTERY BANK TROUBLE SHOOTING ACTION PLAN
52
Thank You
53