Mechanical Workshop Presenters: Chris Akpan & Adeboye O
Mechanical Workshop Presenters: Chris Akpan & Adeboye O
Adeboye O.
INTRODUCTION
• EQUIPMENT/MATERIALS REQUIRED:
Step 3. Ensure you have all the require tools and materials as
mentioned above
Step 4. Prepare the machine you are to align, electric motor to
pump or coupling to electric motor. Remove all existing shims
from under the feet if old shims are to be use, clean them
thoroughly. Always use minimum amount of shims, clean the
base thoroughly, scrape and file away all rust, nicks and burrs.
Examine the base bolts and holes, re-tap or replace bolts if
necessary.
Step 5. Clean mounting surfaces, file off nicks and burrs,
check indicators for sticking and loose niddle, aim indicator
stem directly towards center line of shaft. Measure distance
between the two indicators, measure distance between
indicator and front feet and measure distance between front
and back feet. The horizontal move is the part of the
alignment process that aligns the shafts center lines from
side to side. View the machine from the pump end, zero the
indicators on the left, and then rotate and read on the right.
Make sure that you view the pump from the same direction
in other for you to keep the left and right directions correct
Alignment Check
It is extremely important that the driver-to-compressor
alignment
be checked before start-up.
NOTE
The following procedure is designed for a standard flex type
coupling alignment.
A check of the drive alignment is required before starting the
unit. The purpose of this drive
alignment is to verify that, during positioning of the skid, the
alignment of the driver crankshaft to the
compressor crankshaft has not shifted. The following procedure
applies to the coupling drive
arrangement normally supplied:
1. Make a suitable fixture to mount two dial indicators at the
coupling hub.
2. After the fixture is securely fastened to the coupling hub,
mount a dial indicator to read on
the outer rim of the compressor coupling hub and another
indicator to read on the face of the hub.
3. Rotate the driver through one complete revolution and
bring both indicators to the top
vertical position with the respect to the driver flywheel; then,
using a marking pencil or
chalk, place reference marks on the flywheel and flywheel
housing. These will be the zero
reference marks.
4. Mark the flywheel housing at the 90º, 180º and 270º
positions. These marks will be used as
reference points to take the dial indicator readings.
5. Using a bar, shift both crankshafts against their stops in
the same direction.
6. Zero the dial indicators, with the driver flywheel at the top
vertical reference marks, then
rotate the driver to the 90º mark and take an indicator
reading; repeat at the 180º and 270º
marks and then return to the starting point. Recheck the
zero settings at the starting point.
Be sure the driver and compressor crankshafts are first
shifted per Step 5 before recording
the indicator reading at each reference point
7. Compare the dial indicator readings to determine the main point of
misalignment. If readings
taken at the 180º reference point indicate that the driver is high or low at the
drive-coupling
end, this will, in most cases, indicate that the driver end of the skid is not properly
leveled
with respect to the compressor end. Correct this misalignment by raising or
lowering the
driver by readjusting the shimming at the driver mounting points.
8. When it has been determined that any possible misalignment has been
corrected by
raising or lowering the driver, take a final set of indicator readings at each of the
reference
points. The coupling misalignment should be as close to zero as possible and
must not
exceed 0.005 inch (0.13 mm) Total Indicator Reading when the equipment is up
to operating
temperature. Therefore a tolerance for thermal growth should be considered
When performing this cold alignment procedure. (Ensure you do
it to the specifications of the manufacturer).
If further alignment adjustments are necessary, do this by adding
or removing shims from the driver mounting points and by
moving the driver sideways, if required,
using Jack screws against the sides of the driver base.
NOTE
In most cases, Dresser-Rand specifies coupling misalignment
Limits that are much tighter than those allowed by the coupling
manufacturers.
Always adhere to the Dresser-Rand limits.
COMPRESSOR
• Maintenance
• Trouble shooting
• Operations
• FLM (Front Line Maintenance).
LUBRICATION SYSTEM
Lubrication: Is the process, or technique employed to
reduce wear of one or both surfaces in close proximity, and
moving relative to each another, by interposing a substance
called lubricant between the surfaces to carry or to help
carry the load (pressure generated) between the opposing
surfaces. The interposed lubricant film can be a solid, (e.g.
graphite, a solid/liquid dispersion, a liquid, a liquid-liquid
dispersion gasses exceptionally a gas.
In the most common case the applied load is carried by
pressure generated within the fluid due to the frictional
viscous resistance to motion of the lubricating fluid between
the surfaces.
Lubrication can also describe the phenomenon such
reduction of wear occurs without human intervention
(hydroplaning on a road
LUBRICATION SYSTEM CONT.
Lubrication of the ship steam engine crankshaft. The two bottles with lubricant are attached to the piston and move while the engine is operating.
Besides supporting the load the lubricant may have to perform other
functions as well, for instance it may cool the contact areas and remove
wear products. While carrying out these functions the lubricant is
constantly replaced from the contact areas either by the relative
movement (hydrodynamics) or by externally induced forces.
Lubrication is required for correct operation of mechanical systems
pistons, pumps, cams, bearings, turbines, cutting tools etc. where
without lubrication the pressure between the surfaces in close proximity
would generate enough heat for rapid surface damage which in a
coarsened condition may literally weld the surfaces together, causing
seizure.
In some applications, such as piston engines, the film between the piston
and the cylinder wall also seals the combustion chamber, preventing
combustion gases from escaping into the crankcase.
, LUBRICATION.
If the machine has set for over 6 months
proceed with the following:
1. Remove the outer head and inboard suction
valve assembly from each compressor cylinder
and inspect the cylinder bores.
2. Reassemble the cylinders using adequate
lubricating oil.
NOTE
For cylinders operating in non-lube service, re-
assemble cylinders dry.
LUBRICATION for the grade and quantity.
Recommendations:
1. The operator uses a manual hand pump or motor-driven
priming pump to circulate the oil
and fill the lubricating system (vent air from oil filter while
circulating). The bearings may
suffer from a “dry” start. Add oil to the frame sump as
required. Do not fill above the level
mark on the level gauge because the rotating compressor
parts may strike the oil surface,
causing foaming and loss of oil pressure.
2. Continue to operate the priming pump until pressure
indication is seen at the gauge. Check
external oil piping during this period for tight connections
All precautionary measures specified by the
Occupational Safety
and Health Act of 1970 (OSHA) must be complied
with when
starting, handling, or using solvents.
Check all oil piping for tight connections.
Fill the frame oil sump to the level indicator on the oil
level gauge
Cylinder Unloading
Unloading of a cylinder end is done by retracting the suction
valve from the unloaded
end. This has the effect of reducing the capacity of the
machine by the amount of flow the
unloaded end is capable of generating. This method of
capacity control reduces the horsepower
requirements by approximately 50 percent. Unloading
sequences not initially approved or
reviewed can lead to overloads, non-reversal, overheating,
and/or valve reliability problems.
Consult with a Dresser-Rand representative if such
unloading sequences have not been
approved.
Suction Pressure Control
Controlling the suction pressure to the compressor can also
be used to control capacity. This
is most often used when horsepower is limited and the flow
rate is higher than the unit can handle. A
suction control valve is used to hold the suction pressure to a
preset limit, thereby limiting flow.
Performance must be run at the desired set point to ensure
that temperature and rod load limits
Of the compressor are not exceeded. This method of
capacity control offers the advantage of a stable
operating condition for the unit.
Capacity Control Bypass
A unit bypass system may be used to control capacity,
particularly when the unit is
oversized, or when the suction pressure is not stable and has
a tendency to fall below a desirable
limit. This method utilizes a pressure control valve in the
bypass system around the unit, set to
operate at the minimum operating point for the compressor.
When this method is used, it is important
that the bypass gas stream be taken downstream of a
process after cooler. This will avoid an
uncontrolled temperature rise during continuous operation.
Figure 3-1 illustrates a typical bypass
system.
COMPRESSOR LOADING AND UNLOADING
It is important that the compressor be unloaded prior to and during startup.
There are two basic methods to loading and unloading a compressor.
Which of the two is best suited for a particular
installation depends on site conditions. The following should be considered
prior to designing
The two methods are as follows:
(1)• Bypass and discharge check valve method
(2)• Vent valve method
Probably the simplest, most reliable and safest method, is by use of a
Bypass and discharge check valve method.
This is illustrated in Figure 3-2. With this set-up, there is little danger of
exceeding rated rod
load and the rate of loading can be controlled by the rate of closing the
bypass valve. On multiple-stage
units, this set-up works well for sequence loading because each bock
valve is opened or closed
separately. It should be noted that with this method, when the compressor
cylinders and piping are
pressurized to suction gas pressure, the load on the unit will be dependent
on the sizing of the bypass
valve and associated piping, Also, the sizing of the bypass valve and
piping will be the limiting factor on
the period of time the unit can be bypassed without excessive
gas heating.
The other method of loading and unloading is the vent valve
method. This is illustrated in Figure
3-3. This method results in the venting of excess gas during
loading which may not be acceptable in
certain situations at particular sites. Also, during idling periods
the compressor will pull partial vacuum on
the suction piping downstream of the suction valve, and it is
extremely important that the unit is purged
prior to loading. Additionally, the suction valve must be fully
open prior to closing the vent valve to prevent
the possibility of generating excessive rod loads
Loading/Unloading Procedure – Bypass and Discharge Check Valve
Method
1. Prior to starting the unit, ensure the suction and discharge valves are
closed. Then, open the
bypass valve and the vent valve to de-pressurize the compressor cylinders
and piping to atmosphere.
2. Start the driver and allow it to idle and warm up; after ten minutes of
warm-up, bring it up to fast idle.
3. Open the discharge valve, which will allow discharge pressure to back
up against the Discharge check valve
4. Partially open the suction valve to purge the compressor cylinders and
piping.
5. Pressurize the compressor cylinders and piping by closing the vent
valve and opening the suction valve.
6. Load the unit by closing the bypass valve.
7. Reverse the preceding steps to UNLOAD.
Loading/Unloading Procedure – Vent Valve Method
1. Prior to starting the unit, ensure the suction and discharge
valves are closed. Then, open the
vent valve to( de-) pressurize the compressor cylinders and
piping to atmospheric pressure.
2. Start the driver and allow it to idle and warm up; after ten
minutes of warm-up, bring it up to fast idle.
3. Open the discharge valve, which will allow discharge
pressure to back up against the discharge CHECK VALVE,
4. Partially open the suction valve to purge the compressor
cylinders and piping.
5. Load the unit by opening the suction valve fully, then by
closing the vent valve.
6. Reverse the preceding steps to UNLOAD.
During loading
Description on Loading
During Unloading
Unloading Description
COOLING SYSTEM (COMP.)
Methods
There are many different methods of filtration; all
aim to attain the separation of substances.
Separation is achieved by some form of
interaction between the substance or objects to
be removed and the filter. The substance that is to
pass through the filter must be a fluid, i.e. a liquid
or gas. Methods of filtration vary depending on
the location of the targeted material, i.e. whether
it is dissolved in the fluid phase or suspended as
a solid
Air Filters, Dust Filters & Gas Filters
Providing filtration solutions to your design or ours
FILTRATION CONT.
Applications
Filtration is used to separate particles and fluid in a suspension,
where the fluid can be a liquid, a gas or a supercritical fluid.
Depending on the application, either one or both of the
components may be isolated.
Filtration, as a physical operation is very important in chemistry for
the separation of materials of different chemical composition. A
solvent is chosen which dissolves one component, while not
dissolving the other. By dissolving the mixture in the chosen
solvent, one component will go into the solution and pass through
the filter, while the other will be retained. This is one of the most
important techniques used by chemists to purify compounds.
Filtration is also important and widely used as one of the unit
operations of chemical engineering. It may be simultaneously
combined with other unit operations to process the feed stream.
APPLICATION CONT.
Filtration differs from sieving, where separation
occurs at a single perforated layer (a sieve). In
sieving, particles that are too big to pass through the
holes of the sieve are retained (see particle size
distribution). In filtration, a multilayer lattice retains
those particles that are unable to follow the tortuous
channels of the filter.[1] Oversize particles may form a
cake layer on top of the filter and may also block the
filter lattice, preventing the fluid phase from crossing
the filter (blinding). Commercially, the term filter is
applied to membranes where the separation lattice is
so thin that the surface becomes the main zone of
particle separation, even though these products
might be described as sieves.
Air Filters, Dust Filters & Gas Filters
Showing variety of filters and designed for filtration
solutions.
FILTRATION CONT.
Filtration differs from adsorption, where it is not the
physical size of particles that causes separation but the
effects of surface charge. Some adsorption devices
containing activated charcoal and ion exchange resin
are commercially called filters, although filtration is not
their principal function.
Filtration differs from removal of magnetic contaminants
from fluids with magnets (typically lubrication oil,
coolants and fuel oils), because there is no filter
medium. Commercial devices called "magnetic filters"
are sold, but the name reflects their use, not their mode
of operation.
The remainder of this article focuses primarily on liquid
filtration
FILTRATION CONT.
Two main types of filter media are employed in the chemical laboratory—
surface filter, a solid sieve which traps the solid particles, with or without
the aid of filter paper (e.g. Büchner funnel, Belt filter, Rotary vacuum-drum
filter, Cross-flow filters, Screen filter), and a depth filter, a bed of granular
material which retains the solid particles as it passes (e.g. sand filter). The
first type allows the solid particles, i.e. the residue, to be collected intact;
the second type does not permit this. However, the second type is less
prone to clogging due to the greater surface area where the particles can
be trapped. Also, when the solid particles are very fine, it is often cheaper
and easier to discard the contaminated granules than to clean the solid
sieve.
Filter media can be cleaned by rinsing with solvents or detergents.
Alternatively, in engineering applications, such as swimming pool water
treatment plants, they may be cleaned by backwashing. Self-cleaning
screen filters utilize point-of-suction backwashing to clean the screen
without interrupting system flow
FILTRATION CONT.
Characteristics
A regenerative desiccant dryer typically delivers
a dew point of between -40°F(-40°C) and -100°F
(-73°C)
A refrigerated dryer delivers a dew point not
lower than approximately 35°F (2°C)
A deliquescent dryer delivers a dew point
suppression that fluctuates with air temperature.
Typically this suppression is 20F below the
compressed air temperature.
DRYERS CONT.
Refrigerated dryer
Refrigeration dryers employ two heat exchangers, one for air-to-air and one
for air to refrigeration. However, there is also a single TRISAB heat
exchanger that combines both functions. The compressors used in this type
of dryer are usually of the hermetic type and the most common gas used is
R-134a. The goal of having two heat exchangers is that the cold outgoing air
cools down the hot incoming air and reduces the size of compressor
required. At the same time the increase in the temperature of outgoing air
prevents re-condensation.
Most manufacturers produce "cycling dryers". These store a cold mass that
cools the air when the compressor is OFF. When the refrigeration
compressor runs, the large mass takes much longer to cool, so the
compressor runs longer, and stays OFF longer. These units operate at lower
dew points, typically in the 35 to 40 degree F range. When selected with the
optional "cold coalescing filter", these units can deliver compressed air with
lower dew points.
DRYERS CONT.
Deliquescent dryer
A deliquescent dryer typically consists of a pressure vessel
filled with a hygroscopic media that absorbs water vapor. The
media gradually dissolves—or deliquesces—to form a
solution at the base of the pressure vessel. The liquid must
be regularly drained from the vessel and new media must be
added. The media is usually in tablet or briquette form.
Deliquescent dryers have no moving parts and don't require
electrical power for operation. Common applications
therefore often involve remote, hazardous, or mobile
worksites. Deliquescent dryers are used for removing water
vapor from compressed air, natural gas, and waste gases
such as landfill gas and digester gas.
The performance of a deliquescent dryer, as measured by
outlet dew point, is highly dependent on the temperature of
the air or gas being processed, with cooler temperatures
DRYERS CONT.
Desiccant dryer
The term "desiccant dryer" refers to a broad class of dryers. Other terms
commonly used are regenerative dryer and twin tower dryer, and to a lesser
extent adsorption dryer.
The compressed air is passed through a pressure vessel filled with an
adsorbent media such as activated alumina, silica gel, molecular sieve or other
desiccant material. The desiccant can bring the dew-point of the water vapor in
the air down to -40 degrees Celsius or below. This means that the air will not
condense (deposition) water until it is cooled to -40 degrees Celsius. In practice
two cylinders with desiccant are used; one is drying the air, while the other
vessel is being regenerated. The switching of the vessels and the regeneration
sequence is typically done automatically via solenoid operated valves.
The regeneration of the desiccant vessel can be during three different methods:
Heatless "pressure-swing" drying which uses part of the dry compressed air
coming from the other vessel to dry the desiccant in the vessel being generated
at lower pressure.
Heated dryer, this can use a hot air blower, so there is no loss of compressed
air.
Heat of compression. This can only be used with an oilfree compressor.
A typical comp. diagram showing drying system
COMPRESSOR SEALING SYSTEM
Inspect the bearing and Dry Gas Seal assembly prior to installation.
Clean Seal Element compartment.
Centralize shaft for labyrinth seal installation using DTI and OEM special
tools.
Install labyrinth seal and ensure it fits into the casing locking slot.
Install the mechanical seal (Dry Gas Seal) using the special tool and
ensure it fits into the casing frame.
Remove the Dry Gas Seal transportation plates.
Install the Barrier seal using the OEM tool.
Remove the transportation plate and install end plate/lock ring.
Install radial and axial bearings including temperature probes.
Install coupling hub and make ready for cold alignment.
Cover casing and clean work site
Installation Procedure cont.
The bearing
housing cover is
removed and
Unit is prepared
for
transportation
bearing
extraction.
Thrust collar Extraction
.
The arrays of airfoils are set in rows, usually as pairs: one rotating and one stationary. The
rotating airfoils, also known as blades or rotors, accelerate the fluid. The stationary airfoils,
also known as stators or vanes, decelerate and re-direct the flow direction of the fluid,
preparing it for the rotor blades of the next stage. Axial compressors are almost always multi-
staged, with the cross-sectional area of the gas passage diminishing along the compressor to
maintain an optimum axial Mach number. Beyond about 5 stages or a 4:1 design pressure
ratio, variable geometry is normally used to improve operation.
Rotary screw comp.
7. Defective gauge.
8. Plugged sump suction
Strainer
NOISE IN CYLINDER 1. Loose piston 1. Tighten piston assembly to
2. Piston hitting outer head or piston rod per instructions.
frame head. 2. Adjust end clearance to
3. Loose crosshead jam nut. specifications.
4. Broken or leaking valve. 3. Tighten jam nut.
5. Piston rings broken. 4. Repair or replace valves.
6. Liquids 5. Replace piston rings.
1. Lubrication failure. 6. Remove liquids. 1. Replace
PACKING lubrication check
2. Improper lube oil or feed
OVERHEATING rate. valve or lubricator pump.
3. Insufficient cooling. 2. Use correct oil; increase feed
(Especially with water-cooled rate.
packing.) 3. Clean coolant passages,
4. Inadequate side clearance install water filter, increase
supply pressure or rate.
Reduce coolant temperature at
inlet..
4. Replace packing rings
1. Worn packing rings. 1. Replace packing rings.
2. Improper lube oil or lube oil 2. Use correct oil or increase feed
rate..
feed rate. (Blue Hot) 3. Clean packing, piping and
PACKING LEAKAGE 3. Dirt in packing. ensure gas supply is clean.
4. Pressure increase too fast. 4. Reduce pressure and
AND/OR BLOWBY 5. Rings incorrectly assembled. increase at lower rate.
6. Improper end or side 5. Reassemble per Instruction book.
6. Check and adjust clearances.
Clearance
7. Unlock and provide low-point
7. Packing vent plugged. drains.
8. Scored piston rod. 8. Replace piston rod.
9. Excessive rod run-out 9. Check crosshead clearances
and piston
1. Too much cylinder lube oil. 1. Adjust supply rate.
2. Wrong cylinder lube oil, too 2. Use correct oil for application.
light; high carbon residue. See chart in Instruction
EXCESSIVE 3. Oil carryover from inlet or Manual.
CARBON ON previous stage. 3. Install separator/drain
4. Broken or leaking valves; system.
VALVES high temperature. 4. Replace or repair valves.
5. Excessive pressure ratio 5. Clean intercoolers; valves.
across cylinder, high Look for failed valve in
temperature cylinder, upstream or
downstream
1. Excessive ratio across 1. Replace leaking inlet valves
cylinder. Rings leaking on or piston rings.
next higher stage. 2. Clean intercooler or piping;
HIGH DISCHARGE 2. Fouled intercooler or piping. reduce lube feed rate.
3. Leaking discharge valves or 3. Repair/replace parts as
TEMPERATURE piston rings. necessary.
4. High inlet gas temperature. 4. Clean intercooler.
5. Fouled cylinder water 5. Clean water jackets.
jackets. 6. Use correct lube oil and
6. Improper cylinder lube oil or correct the feed rate.
lube feed rate.
• Gas Turbine
• TROUBLE SHOOTING.
• MAINTENANCE.
• The sequence of events that occur when fuel is sprayed into the
cylinder may be considered as happening in three separate phases.
In the initial phase the fuel is admitted but does not burn; some of
the fuel evaporates, and the vapour is raised to its self-ignition
temperature.
• In the second phase, rapid combustion occurs as the flame spreads,
and there is a sharp rise in pressure.
• Finally, in the third phase, the rest of the charge burns as it enters
the combustion chamber, and this maintains or increases the
pressure.
• In the small high-speed automotive engine these three stages may
occur in about one thousandth of a second.
• Trouble Shooting: When an engine develops a
faults, it is not always manifested at its source. Example:
If the white metal of a connecting rod bearing suddenly
starts to wear, the effect “Knocking” – would be
immediately noticeable and the engine would be stopped
by the lubricating oil pressure safety switch. By closed
inspection it would soon be found that a bearing had
failed. It would be unlikely however, that the trouble
would be cured simply by renewing the bearing
concerned; renewal would suffice if the bearing had
actually been faulty by normal wear and tear, but not if
the cause of the failure lay elsewhere, as it probably
would.
Trouble shooting cont.
• It would therefore, be necessary to find what had
caused the bearing failure in the first place before
attempting to replace it or them.
• Always look for the primary cause of any operating
trouble. It must be firmly understood however, that the
art of trouble shooting does not solely depend on
knowledge alone, but to a large extent on experience in,
and with, the actual equipment under examination. It
must also be borne in mind that trouble shooting consists
of eliminating possibilities until the actual trouble is
found. One would be well advised to look for the logical
rather than the unusual possibilities.
• Floor open for interaction on Problem solving, Diesel
engine and Trouble shooting, Gas engine.