Lecture 10 - Ex N
Lecture 10 - Ex N
Ex n slide 1
Certification
• Ex N complies with
– BS 4683: Part 3 (1971) or
– BS 6941:1988
• Ex n complies with
– EN 50021:1999 or
– IEC 79-15
Ex n slide 2
Ex n: Non-incentive
• Non sparking (- the predominant type)
– simplified Ex e (e.g. terminals, junction boxes,
luminaires, motors)
• Exclusion of flammable gas
– simplified Ex p and Ex m
• Energy limitation
– simplified Ex i (e.g. in-cab computers, PLCs)
• Enclosed break
– simplified Ex d (e.g. small volume lamp holders)
Ex n slide 3
Ex n enclosures
Glands must also maintain IP54;
Case withstands
washer required
3.5 J impact
Material suitable
for environment Gasket or O-ring to
(frequently plastic) give IP54 minimum
Ex n slide 4
Non-sparking (EEx nA)
• Simplified Ex e
• Enclosure usually IP54 minimum
• Condition of gaskets and O-rings is important
• Common examples are JBs, luminaires and
motors
Ex n slide 5
Energy limitation (EEx nL)
• Simplified intrinsic safety
• Local protection of switches, etc.
a simplified ‘barrier’ may be used
power
supply
Terminal box
Ex n slide 7
Enclosed break (EEx nC)
• Simplified flameproof
• Max. enclosure volume 20 cm3
• Relatively unimportant - switches, lamp holders, etc.
Lamp
Ex n slide 8
Encapsulation & hermetically-
sealed (EEx nC)
Ex n slide 9
Simplified pressurisation
(EEx nP)
Ex n slide 10
Cables and glands
• Cables
– as for zone 1
– much rugged industrial cabling is adequate
• Glands
– certification not required
– normally required to be IP54 minimum
– special consideration for glands into restricted
breathing enclosures
Ex n slide 11