0% found this document useful (0 votes)
86 views

Study On Grounding System and Safety Practices

This document discusses grounding systems and safety practices. It covers the introduction to grounding, effects of electric fault current, types of grounding including system and equipment grounding, fault return conductors, and methods of sensing and clearing faults. The purpose of grounding systems is to minimize hazards from electric faults by limiting fault voltage and current duration. Proper grounding and overcurrent protection are both required to enhance safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
86 views

Study On Grounding System and Safety Practices

This document discusses grounding systems and safety practices. It covers the introduction to grounding, effects of electric fault current, types of grounding including system and equipment grounding, fault return conductors, and methods of sensing and clearing faults. The purpose of grounding systems is to minimize hazards from electric faults by limiting fault voltage and current duration. Proper grounding and overcurrent protection are both required to enhance safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 29

STUDY ON GROUNDING SYSTEM AND

SAFETY PRACTICES

MOHAMMED FAIZ M
S7 EE
ROLL NO. 25

DEPARTMENT OF ELECTRICAL AND ELECTRONICS


COLLEGE OF ENGINEERING KIDANGOOR

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 1


CONTENTS
1. INTRODUCTION
2. EFFECT OF ELECTRIC FAULT CURRENT
3. TYPES OF GROUNDING
4. FAULT RETURN CONDUCTOR
5. METHODS OF SENSING AND CLEARING A FAULT TO EQUIPMENT
6. OTHER PATHWAYS
7. CONCLUSIONS
8. REFERENCES

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 2


INTRODUCTION
Grounding, generally means providing a connection from one conductor of the
system to an electrode that is buried in the earth.
Grounding is generally accepted as an operation to make systems safe.
The fault return conductor brings the potential at equipment enclosures to ground
but only when there is no fault current.
The potential rise due to the fault current flow can raise the potential to a
hazardous level.
Simple grounding does not provide for safe systems.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 3


INTRODUCTION(Contd… )

The fault return conductor and the overcurrent protective device, in combination,
may prevent ventricular fibrillation and provide safer systems.
Grounding or connection to earth, is an action to minimise the consequence on
electrical faults.
If the enclosure is at earth potential and an individual is in contact with the earth,
there will be no difference in the potential to result in a shock.
For a fault current flows in the connection to the earth, the enclosure is raised in
potential equal to the product of the fault current and the impedance to the earth.
Now there will be a difference of potential between the enclosure and the body in
contact with the earth, and a shock potential is established.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 4


INTRODUCTION(Contd… )

Non-normal electric current flow results in electric shock and fire.


Fires are started by raising the temperature of a combustible material above its
ignition point.
The power generated by a current flowing through a resistive element is
determined by the i2R function.
The power dissipated in the resistive element can raise the temperature.
Minimizing the total time that the fault current flows will minimize the total energy
developed.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 5


EFFECTS OF ELECTRIC FAULT
CURRENT
The effects of an electric current through the body (1000ohm) from 5 to 95
percentile have been measured as follows (independent of time):
Threshold of feeling: 1 mA
Let-go current: 6-14 mA for women and 9-22 mA for men
Arrest respiration: 20 - 40 mA across chest.

Thus, maximum fault voltage of 6 V is desirable.


Obtaining this low level of fault voltage may not be practical.
The two factors which defines the level of safety of an electrical system:
magnitude
duration

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 6


EFFECTS OF ELECTRIC FAULT
CURRENT(Contd… )

The relatively safer system is one that minimizes the magnitude of the fault voltage
and/or the duration that the fault current exists.
The fault magnitude is determined by:
 the impedance of the fault path
 the fault voltage.

The impedance of the body, including the contact impedance where the current
enters and where it leaves the body is the limiting factor.
The fault duration is determined by:
 how long the body is subjected to the fault current.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 7


TYPES OF GROUNDING

System Grounding
Equipment Grounding

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 8


System Grounding

NEEDS OF SYSTEM GROUNDING:

1. to limit the voltage imposed by lightning


2. to limit the voltage due to unintentional contact with higher-voltage lines
3. to limit the voltage due to line surges
4. to stabilize the voltage to the earth during normal operation.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 9


Fig 1. System Grounding

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 10


System Grounding (Contd… )

The supply system has a connection to ground and is "system" grounded.


When lightning strike to a load side conductor, system grounding provides a path
for the lightning current to travel to the earth.
There is no electrical connection from the faulted supply conductor and the human
in contact with the enclosure.
Line surges, if they are voltage, cannot be reduced by system grounding which is a
current path.
Only surge protective devices can provide a means of short circuiting an
overvoltage to ground.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 11


System Grounding (Contd… )

Sudden opening of single conductor in a 3 phase long distribution system leads to


unstable voltage.
The capacitance to ground and the inductance of the line react to result in ferro-
resonance and an overvoltage can occur.
System grounding changes the capacitance vs inductance relationship and prevents
the overvoltage from occurring.
System grounding provides little assistance in minimizing the amplitude or duration
of downstream faults at equipment.
 The fault current must return through the earth with its relatively high resistance
compared to fault supply current conductors.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 12


Equipment Grounding

NEEDS OF EQUIPMENT GROUNDING:

1. to facilitate fault current clearing


2. to minimize the hazardous fault voltage

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 13


Fig 2. Equipment Grounding

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 14


Equipment Grounding (Contd…)

The supply system has a connection to the earth and is "grounded".


There is a fault at load equipment between the supply ungrounded conductor and
the metal enclosure of the load.
There is a connection to the earth from the equipment enclosure and the equipment
is "grounded". This conductor is truly an "equipment grounding conductor"

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 15


Equipment Grounding (Contd…)
The fault voltage at the enclosure with respect to local ground is:
𝑉𝑓𝑎𝑢𝑙𝑡 = 𝐼𝑓𝑎𝑢𝑙𝑡 × 𝑍𝑟𝑒𝑡𝑢𝑟𝑛
𝑉𝑠𝑢𝑝𝑝𝑙𝑦
𝐼𝑓𝑎𝑢𝑙𝑡 = 𝑍
𝑝ℎ𝑎𝑠𝑒 +𝑍𝑟𝑒𝑡𝑢𝑟𝑛

𝑉𝑠𝑢𝑝𝑝𝑙𝑦
𝑉𝑓𝑎𝑢𝑙𝑡 = 𝑍 × 𝑍𝑟𝑒𝑡𝑢𝑟𝑛
𝑝ℎ𝑎𝑠𝑒 +𝑍𝑟𝑒𝑡𝑢𝑟𝑛

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 16


Equipment Grounding (Contd…)
The fault voltage will be very close to the supply voltage by Ohm's Law for series
circuits.
Any increase in conductor size or reduction of circuit length will merely make the
fault voltage higher.
Fault current magnitude is minimal due to the relatively high resistance through the
earth back to the system grounding connection and finally to the source.
Thus equipment grounding, there fore, does not minimize the fault voltage.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 17


FAULT RETURN CONDUCTOR

Fig 3. Fault Return Conductor

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 18


FAULT RETURN CONDUCTOR (Contd…)

The conductor connecting the enclosure directly to the earth has been removed.
A separate conductor has been added between the enclosure and the source.
The added conductor provides a path for the fault current to the source without
passing through the earth.
 This conductor is known as “fault return conductor”.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 19


FAULT RETURN CONDUCTOR (Contd…)

The magnitude of the fault voltage can be calculated because the resistance of the
return path is a known quantity.
To provide a high level of fault current, a low-impedance electrically conductive
path from potentially faulted piece of equipment to the system source is necessary.
If that path is through the earth, the impedance of the earth will generally limit the
fault current to low levels that are insufficient for fault clearing.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 20


METHODS OF SENSING AND CLEARING
A FAULT TO EQUIPMENT

Zero-sequence current sensing:


 Use a current transformer to sense the current going and leave the load.
 If the currents are not equal, there is a fault current returning to the source by some other
path.
 The current transformer output is used to operate the overcurrent device.
 Commonly found in kitchens, bathrooms etc.
 These devices are capable of opening the circuit in under 1 s.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 21


METHODS OF SENSING AND CLEARING A FAULT
TO EQUIPMENT (Contd…)
By the use of a current transformer surrounding all of the circuit conductors.
 If the net current is not zero, the current transformer secondary output is used to trip the
supplying overcurrent device.

Circuit overcurrent protection device:


 Circuit breaker, fuse, or relay can provide fault current clearing if the fault current is in
excess of the normal device rating.
 Most of these devices have an inverse time-current characteristics.
 To operate this device quickly it is necessary to provide a high overcurrent.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 22


OTHER PATHWAYS
There may be one or more fault return paths in parallel with the fault return wire
conductor.
The other paths are metallic raceways and building steel.
Metallic raceways are considered as a fault return conductor without regard to
material or size.
Raceway encircles the phase conductor, the net magnetic field is near zero inside
raceway, resulting in minimum impedance.
In buildings that have a structural steel metal frame, electrical equipment is often
fastened to the structural steel.
The structural steel is generally bonded to the earth and is a parallel path for the
fault current to return to the source.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 23


OTHER PATHWAYS (Contd…)

Issues that reduce the effectiveness of the raceway as a conductor:


 High fault currents flow on the inner surface of the raceway due to eddy currents on
the outer surface.
 Reduces the effective cross-sectional area and thus increases the impedance of the
raceway.
 High fault currents will saturate the steel and hence increasing the impedance of the
raceway.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 24


OTHER PATHWAYS (Contd…)

The parallel paths make the system safe in following ways:


 It reduces the effective fault return impedance.
 It reduces the fault voltage.
 It reduces the fault current through the human.
 It increases the fault current through the overcurrent protective device.
 It fasten fault clearing.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 25


CONCLUSIONS
The act of grounding does not make systems safer.
In fact, grounding minimizes the hazardous voltage due to an enclosure fault is a
myth.
The relatively safer system is one that minimizes the magnitude of the fault voltage
and/or the duration of the fault current.
This is accomplished by a combination of an adequately sized fault return
conductor and an overcurrent device with a current versus time characteristic
adequate to operate rapidly.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 26


REFERENCES
1. E. Rappaport, “Grounding vs. bonding—What the National Electrical Code
Does Not Explain”, IEEE Transactions on Industry Applications, Year-2014,
Volume: 50, Issue: 4, Pages: 2776-2779.
2. E.Rappaport, “Does Grounding Make A System Safe? Analyzing the factors
that contribute to electrical safety”, IEEE Industry Applications Magazine •
May|june 2015 Pages:48-57.
3. John P. Nelson ,” Improved Electrical Safety Through High Resistance
Grounding ” IEEE Transactions on Industry Applications, Year: 2015, Volume:
51, Issue: 6 Pages: 5198 – 5203.
4. S. K. Kaul; Jai Kishore , Electrical safety in india - a perspective , Electrical
Safety In Industry, 2000. Proceedings of 2000 IEEE IAS Workshop ,Year: 2000,
Pages: 42 – 47.

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 27


REFERENCES (Contd…)

5. https://en.wikipedia.org/wiki/Ground_(electricity)
6. http://electrical-engineering-portal.com/good-grounding-system
7. http://electrical-engineering-portal.com/what-is-the-difference-between-bonding-
grounding-and-earthing
8. http://ecmweb.com/power-quality/ground

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 28


THANK YOU

10:18 AM DEPARTMENT OF ELECTRICAL AND ELECTRONICS, CE, KIDANGOOR 29

You might also like