Testing of Transformers: T.R.Sathyanarayana Rao
Testing of Transformers: T.R.Sathyanarayana Rao
T.R.Sathyanarayana Rao.
Email : [email protected]
Tel: 080 23390918 Mobile: 94496 52508
Type Tests
Routine Tests.
Special Tests.
Pre commissioning Tests
Diagnostic Tests
Type Tests
The second is caused by molecular distortion whereby the imposed electric field
distorts the negative charge of the electron shells circulating around the nucleus
toward the positive voltage.
The third is due to the alignment of polarized molecules within the electric field
applied. This alignment is fairly random in a neutral state, but when an electric field
is applied, these polarized molecules line up with the field to a greater or lesser
extent.
Surface Leakage Current
The surface leakage current is present because the surface of the insulation is
contaminated with moisture or salts. The current is constant with time and depends on
the degree of ionization present, which is itself dependent on temperature.
It is often ignored as a separate current, being included with the conduction current
below as the total leakage current.
Conduction Current
Conduction current is steady through the insulation and is usually represented by a
very high value resistor in parallel with the capacitance of the insulation. It is a
component of the Leakage Current, which is the current that would be measured when
the insulation is fully charged and full absorption has taken place. Note that it includes
surface leakage, which can be reduced or eliminated by the use of the guard terminal.
Dielectric Discharge Test
The Dielectric Discharge test (DD) is a relatively new test method that
was developed by EdF, France’s national power utility, and based on
years of research.
4-7 Poor
2-4 Questionable
Less than 2 OK
Routine Tests.
•Measurement of Winding Resistance
•Measuring of Voltage Ratio
•Measurement of Voltage Vector Relationship
•Measurement of No load Loss and Currents
•Measurement of Insulation Resistance.
•Dielectric Tests
•Tests on On-Load Tap changers
•Measurement of Impedance Voltage/
Short- circuit Impedance
Special Tests
•Dielectric Tests
•Measurement of Zero-Sequence Impedance of
3 Transformer
•Short –Circuit Test
•Measurement of Harmonics of No-load current
•Measurement of Acoustic noise level
•Measurement of power taken by fans and oil pumps
•Any other tests mutually agreed
Measurement of Winding Resistance
• The resistance of winding,the terminals between
it is measured and temperature of winding shall be recorder.
• Direct current shall be used.
• Self inductance effect shall be minimized.
• After the Transformer has been under oil without excitation
for at least 3 hours , the average temperature shall
deemed to be the same as the average oil temperature.
The average temperature of oil is taken as mean of top
and bottom oil Temperatures.
Measurement of Voltage Ratio
Check of Voltage Vector Relationship.
rated current .
oil if necessary.
Measurement Of No-load Loss
at ambient Temperature.
continued
Dielectric tests consists of
a) Short duration Power frequency test.
b) Lightning Impulse test.
(as per IS 2026 part 3)
Winding are categorized depending upon Highest
system voltage, separately for uniform and non-uniform
insulation.
Each of the winding of a transformer is assigned a value
Of Highest Voltage, which is the maximum value of the
highest voltage of a system to which the winding may be
connected in respect of its insulation
continued
Separate source power frequency voltage withstand test
power frequency withstand strength along the winding under test, between its
continued
If a Transformer has already with stood
complete dielectric acceptance tests and if
the tests are to be repeated,The test voltage
level shall be reduced to 75% of original value
Unless otherwise agreed, and provided that
the internal insulation has not been modified
in the mean time.
Temperature Rise Test.